Specifications

ELECTRICAL DATA
CONDENSING UNITS
UNIT
538S
V-PH-Hz
OPERATING
VOLTAGE
MINIMUM*
OPERATING
VOLTAGE
MAXIMUM*
COMPRESSOR FAN POWER SUPPLY
Quantity
RLA
(Ea)
LRA
(Ea)
FLA MCA
Max Fuse
or HACR-Type
Circuit Breaker Amps
024
208/230-1-60 187 254
1
12.9 62.5
0.70 16.8 25
048 2 1.45 30.5 40
LEGEND
FLA Full Load Amps
HACR Heating, Air Conditioning, Refrigeration
LRA Locked Rotor Amps
MCA Minimum Circuit Amps per NEC Section 430-24
NEC National Electrical Code
RLA Rated Load Amps (Compressor)
*Permissible limits of the voltage range at which unit will operate
satisfactorily.
NOTES:
1. The 538S units contain a 24-v transformer; additional transformers
are not required.
2. All motors and compressors contain internal overload protection.
3. In compliance with NEC requirements for multimotor and combina-
tion load equipment (refer to NEC Articles 430 and 440), the over-
current protective device for the unit shall be fuse or HACR breaker.
4. Motor RLA values are established in accordance with UL (Underwrit-
ers’ Laboratories) Standard 1995.
FAN COIL UNITS
UNIT V-PH-Hz
OPERATING
VOLTAGE
MINIMUM*
OPERATING
VOLTAGE
MAXIMUM*
FAN (EA) POWER
MIN
WIRE
SIZE
FLA
MOTOR
POWER
MCA MOCP FLA
619C024† 208/230-1-60 187 253 0.50
1
16
hp 0.63 15 0.50 14
619E018 208/230-1-60 187 253 0.53 44 w 0.66 15 0.53 14
619E024 208/230-1-60 187 253 0.53 49 w 0.66 15 0.53 14
619F024 208/230-1-60 187 253 0.44
1
16
hp 0.55 15 0.44 14
619F036 208/230-1-60 187 253 0.44
1
16
hp 1.10 15 0.88 14
LEGEND
FLA Full Load Amps
HACR Heating, Air Conditioning, Refrigeration
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection Amps
(Fuse or HACR Circuit Breaker)
*Permissible limits of the voltage range at which units will operate
satisfactorily.
†Electrical data is identical for both the 18,000 Btuh field reconfigured
and the full 24,000 Btuh units.
NOTE: Refer to Heat Pump product data literature for electrical data for
heat pump fan coils matched with cooling-only condensing units.
35