Specifications

PERFORMANCE DATA (cont)
COOLING CAPACITIES (cont)
TABLE NO. 9* 538S024 (or 1 Circuit of 538S048 System) CONDENSING UNIT WITH
ONE 619E018 HIGH WALL UNIT
TEMP (F)
AIR ENTERING
CONDENSER
(Edb)
AIR ENTEIRNG EVAPORATOR CFM/BF
360/0.20 414/0.22 480/0.25
Air Entering Evaporator Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
55
TCG 15.6 17.1 18.7 20.4 16.2 17.8 19.4 21.1 16.9 18.4 20.1 21.8
SHG 14.4 12.9 11.3 9.72 15.4 13.7 11.9 10.1 16.4 14.6 12.6 10.5
TC 15.5 16.9 18.6 20.3 16.1 17.6 19.2 21.0 16.7 18.3 19.9 21.7
kW 1.32 1.31 1.30 1.30 1.32 1.31 1.31 1.30 1.33 1.32 1.31 1.30
CMP 1.14 1.13 1.12 1.12 1.14 1.13 1.12 1.11 1.13 1.12 1.12 1.11
65
TCG 15.1 16.6 18.2 19.8 15.7 17.2 18.8 20.5 16.3 17.9 19.5 21.2
SHG 14.2 12.6 11.1 9.46 15.1 13.4 11.6 9.83 16.1 14.3 12.3 10.3
TC 15.0 16.5 18.0 19.7 15.6 17.1 18.7 20.4 16.2 17.7 19.3 21.0
kW 1.46 1.45 1.45 1.44 1.46 1.46 1.45 1.44 1.47 1.46 1.45 1.45
CMP 1.28 1.27 1.27 1.26 1.28 1.27 1.26 1.26 1.28 1.27 1.26 1.25
75
TCG 14.7 16.1 17.6 19.2 15.2 16.7 18.3 19.9 15.8 17.3 18.9 20.6
SHG 13.9 12.4 10.8 9.20 14.8 13.1 11.4 9.57 15.7 14.0 12.0 9.99
TC 14.5 16.0 17.5 19.1 15.1 16.6 18.1 19.7 15.7 17.1 18.7 20.4
kW 1.62 1.61 1.61 1.60 1.62 1.62 1.61 1.61 1.63 1.62 1.61 1.61
CMP 1.44 1.43 1.43 1.42 1.44 1.43 1.42 1.42 1.43 1.43 1.42 1.42
85
TCG 14.2 15.6 17.1 18.7 14.8 16.2 17.7 19.3 15.4 16.8 18.3 19.9
SHG 13.6 12.1 10.5 8.95 14.4 12.8 11.1 9.30 15.3 13.7 11.7 9.70
TC 14.1 15.5 17.0 18.6 14.6 16.0 17.6 19.1 15.2 16.6 18.1 19.7
kW 1.80 1.79 1.79 1.78 1.80 1.79 1.79 1.79 1.81 1.80 1.79 1.79
CMP 1.62 1.61 1.61 1.60 1.61 1.61 1.61 1.60 1.61 1.61 1.60 1.60
95
TCG 13.8 15.1 16.6 18.1 14.3 15.7 17.1 18.6 14.9 16.2 17.7 19.2
SHG 13.3 11.8 10.3 8.68 14.1 12.6 10.8 9.03 14.9 13.4 11.4 9.42
TC 13.6 15.0 16.4 17.9 14.1 15.5 17.0 18.5 14.7 16.0 17.5 19.0
kW 2.00 2.00 1.99 1.99 2.00 2.00 2.00 1.99 2.01 2.00 2.00 2.00
CMP 1.82 1.82 1.81 1.81 1.82 1.81 1.81 1.81 1.81 1.81 1.81 1.81
105
TCG 13.3 14.6 16.0 17.5 13.8 15.1 16.5 18.0 14.5 15.6 17.1 18.5
SHG 13.0 11.6 10.0 8.42 13.8 12.3 10.5 8.77 14.5 13.1 11.1 9.14
TC 13.2 14.5 15.9 17.4 13.7 15.0 16.4 17.9 14.3 15.5 16.9 18.3
kW 2.22 2.22 2.22 2.22 2.23 2.23 2.23 2.23 2.24 2.23 2.23 2.23
CMP 2.04 2.04 2.04 2.04 2.04 2.04 2.04 2.04 2.05 2.04 2.04 2.04
115
TCG 12.9 14.1 15.5 16.9 13.4 14.6 16.0 17.4 14.1 15.1 16.4 17.8
SHG 12.7 11.3 9.76 8.17 13.4 12.0 10.3 8.49 14.1 12.9 10.9 8.86
TC 12.8 14.0 15.4 16.8 13.2 14.5 15.8 17.2 13.9 14.9 16.3 17.7
kW 2.48 2.48 2.48 2.49 2.48 2.49 2.49 2.49 2.50 2.49 2.50 2.50
CMP 2.30 2.30 2.30 2.31 2.30 2.30 2.31 2.31 2.30 2.30 2.31 2.31
125
TCG 12.4 13.6 14.9 16.3 13.0 14.1 15.4 16.7 13.6 14.5 15.8 17.2
SHG 12.4 11.0 9.49 7.91 13.0 11.8 10.0 8.23 13.6 12.6 10.6 8.59
TC 12.3 13.5 14.8 16.1 12.8 13.9 15.2 16.6 13.4 14.4 15.7 17.0
kW 2.77 2.78 2.78 2.79 2.78 2.79 2.79 2.80 2.79 2.79 2.80 2.80
CMP 2.59 2.60 2.60 2.61 2.59 2.60 2.60 2.61 2.59 2.60 2.61 2.61
Rating condition.
LEGEND
BF Bypass Factor
CMP Compressor Power
Edb Entering Dry Bulb
Ewb Entering Wet Bulb
kW Total Power (Includes CMP)
SHG Gross Sensible Capacity (1000 Btuh)
TC Total Net Cooling Capacity (1000 Btuh)
TCG Gross Cooling Capacity (1000 Btuh)
*Refer to Systems Index Table on page 21 for table number references.
Many multi-split systems require the use of more than one cooling ca-
pacity table to determine system total capacity and power.
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHG is based on 80 F edb temperature of air entering indoor
coil.
Below 80 F edb, subtract (corr factor x cfm) from SHG.
Above 80 F edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 BF) x (edb 80).
31