Product data
ENGINEER’S SPECIFICATION GUIDE — CEILING-SUSPENDED FAN COIL UNITS (Model 619C)
GENERAL: Furnish and install indoor, under-ceiling mounted,
direct expansion fan coil unit to be used without ductwork. Unit
shall consist of centrifugal blower type fan, fan motor, cooling
coil, piping connectors, electrical controls, solid-state electro-
mechanical control system, and ceiling mounting brackets. Unit
shall be capable of being used in a refrigerant circuit with a
matching air-cooled outdoor condensing unit.
Nominal unit electrical characteristics shall be
v, single
phase, 60 Hz. The unit shall be capable of satisfactory operation
within voltage limits of
vto v.
Unit shall be capable of providing a constant volume of air at a
specified external static pressure within the unit nominal oper-
ating range.
MAXIMUM DIMENSIONS: Indoor unit — width
in.,
depth
in., height inches.
CABINET: Cabinet shall be zinc-coated bonderized steel fin-
ished with a baked enamel paint. Inlet grilles shall be attractively
styled, high-impact polystyrene. Matching mounting brackets
shall be provided.
FAN SECTION: Fan shall be centrifugal blower type with air in-
take in the bottom rear of the unit and discharge in the front. Au-
tomatic, motor-driven, vertical air sweep shall be provided
standard.
COIL SECTION: Coil shall be copper tube with aluminum fins
and galvanized steel tube sheets. Fins shall be bonded to
the tubes by mechanical expansion. A drip pan under the coil
shall have a drain connection for attachment of piping to remove
condensate.
CONTROLS: Controls shall consist of a solid-state electrome-
chanical control system which shall provide the following func-
tions as a minimum: automatic restart, non-programmable
thermostat, filter status indicator, automatic airsweep control,
fan-only operation, user-selectable fan speed control, and com-
pressor restart time delay.
APPROVALS: Unit shall be rated (when matched with a 538A
condensing unit) per ARI Standards 210/240 and shall be listed
in the ARI directory as a matched system. Units shall be UL and
CSA listed.
ACCESSORIES: Automatic start-stop timer, internal conden-
sate pump, fresh air intake kit, indoor guard kit, electronic pro-
grammable thermostat, and power ventilation kit.
59