Product data

ELECTRICAL DATA
538A CONDENSING UNITS
UNIT
SIZE
538A
V-PH-Hz
OPERATING
VOLTAGE
MINIMUM*
OPERATING
VOLTAGE
MAXIMUM*
COMP
RLA
COMP
FLA
FAN
FLA
POWER
MCA MOCP FLA
018
208/230-1-60 187 254
8.0 49.0 0.7 10.7 15 8.70
024 12.9 62.5 0.7 16.8 25 13.60
030 15.0 76.0 0.7 19.5 30 15.70
036
208/230-1-60 187 254 17.9 88.0 0.7 23.1 40 18.60
208/230-3-60 187 254 11.4 77.0 0.7 15.0 25 12.10
460-3-60 414 508 5.7 38.5 0.4 7.5 15 6.10
048
208/230-1-60 187 254 26.4 129.0 1.45 34.5 60 27.85
208/230-3-60 187 254 15.0 99.0 1.45 20.2 35 16.45
460-3-60 414 508 8.2 49.5 0.8 11.1 15 9.00
060
208/230-1-60 187 254 28.9 165.0 1.45 36.6 60 30.35
208/230-3-60 187 254 16.0 125.0 1.45 21.5 35 17.45
460-3-60 414 508 8.0 62.5 0.8 10.8 15 8.80
538C CONDENSING UNITS†
UNIT
538C
V-PH-Hz
OPERATING
VOLTAGE
MINIMUM*
OPERATING
VOLTAGE
MAXIMUM*
COMP
RLA
COMP
LRA
FAN
FLA
POWER
MCA** MOCP** FLA
009 115-1-60 104 127 7.6 46.5 0.76 12.1 15 12.86
012 208/230-1-60 187 253 5.5 30.0 0.35 8.5 15 8.85
FAN COIL UNITS
UNIT V-PH-Hz
OPERATING
VOLTAGE
MINIMUM*
OPERATING
VOLTAGE
MAXIMUM*
FAN POWER
MIN
WIRE
SIZE
FLA MOTOR POWER MCA MOCP FLA
619E009 115-1-60 104 127 0.41 34 W †† †† 0.41 14
619E012 208/230-1-60 187 253 0.23 35 W †† †† 0.23 14
619E018 208/230-1-60 187 253 0.53 44 W 0.66 15 0.53 14
619E024 208/230-1-60 187 253 0.53 49 W 0.66 15 0.53 14
619C018,024| 208/230-1-60 187 253 0.50
1
16
hp 0.63 15 0.50 14
619C036 208/230-1-60 187 253 1.30
1
6
hp 1.60 15 1.30 14
619C048 208/230-1-60 187 253
1.10
0.50
1
6
hp
1
16
hp
2.00 15 1.60 14
619C060 208/230-1-60 187 253
1.30
1.30
1
6
hp
1
6
hp
3.30 15 2.60 14
619F024 208/230-1-60 187 253 0.44
1
16
hp 0.55 15 0.44 14
619F036 208/230-1-60 187 253
0.44
0.44
1
16
hp
1
16
hp
1.10 15 0.88 14
LEGEND
COMP Compressor
FLA Full Load Amps
HACR Heating, Air Conditioning, and Refrigeration
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection Amps
(Fuse or HACR Circuit Breaker)
RLA Rated Load Amps
*Permissible limits of the voltage range at which units will operate
satisfactorily.
†These units can only be used with 619E high wall fan coil units.
**MCA and MOCP are for both indoor and outdoor units.
††Indoor fan coil must be connected to outdoor unit. See outdoor unit
for required data.
\ The 619C018 fan coil is a 619C024 fan coil, but uses a different motor
speed fan tap plug than the 619C024. Electrical data is identical for
both units.
NOTE: Refer to 538B,D Series Heat Pump Product Data literature for
electrical data for heat pump fan coils matched with cooling-only con-
densing units.
36