Product data
ELECTRICAL DATA
538A CONDENSING UNITS
UNIT
SIZE
538A
V-PH-Hz
OPERATING
VOLTAGE
MINIMUM*
OPERATING
VOLTAGE
MAXIMUM*
COMP
RLA
COMP
FLA
FAN
FLA
POWER
MCA MOCP FLA
018
208/230-1-60 187 254
8.0 49.0 0.7 10.7 15 8.70
024 12.9 62.5 0.7 16.8 25 13.60
030 15.0 76.0 0.7 19.5 30 15.70
036
208/230-1-60 187 254 17.9 88.0 0.7 23.1 40 18.60
208/230-3-60 187 254 11.4 77.0 0.7 15.0 25 12.10
460-3-60 414 508 5.7 38.5 0.4 7.5 15 6.10
048
208/230-1-60 187 254 26.4 129.0 1.45 34.5 60 27.85
208/230-3-60 187 254 15.0 99.0 1.45 20.2 35 16.45
460-3-60 414 508 8.2 49.5 0.8 11.1 15 9.00
060
208/230-1-60 187 254 28.9 165.0 1.45 36.6 60 30.35
208/230-3-60 187 254 16.0 125.0 1.45 21.5 35 17.45
460-3-60 414 508 8.0 62.5 0.8 10.8 15 8.80
538C CONDENSING UNITS†
UNIT
538C
V-PH-Hz
OPERATING
VOLTAGE
MINIMUM*
OPERATING
VOLTAGE
MAXIMUM*
COMP
RLA
COMP
LRA
FAN
FLA
POWER
MCA** MOCP** FLA
009 115-1-60 104 127 7.6 46.5 0.76 12.1 15 12.86
012 208/230-1-60 187 253 5.5 30.0 0.35 8.5 15 8.85
FAN COIL UNITS
UNIT V-PH-Hz
OPERATING
VOLTAGE
MINIMUM*
OPERATING
VOLTAGE
MAXIMUM*
FAN POWER
MIN
WIRE
SIZE
FLA MOTOR POWER MCA MOCP FLA
619E009 115-1-60 104 127 0.41 34 W †† †† 0.41 14
619E012 208/230-1-60 187 253 0.23 35 W †† †† 0.23 14
619E018 208/230-1-60 187 253 0.53 44 W 0.66 15 0.53 14
619E024 208/230-1-60 187 253 0.53 49 W 0.66 15 0.53 14
619C018,024| 208/230-1-60 187 253 0.50
1
⁄
16
hp 0.63 15 0.50 14
619C036 208/230-1-60 187 253 1.30
1
⁄
6
hp 1.60 15 1.30 14
619C048 208/230-1-60 187 253
1.10
0.50
1
⁄
6
hp
1
⁄
16
hp
2.00 15 1.60 14
619C060 208/230-1-60 187 253
1.30
1.30
1
⁄
6
hp
1
⁄
6
hp
3.30 15 2.60 14
619F024 208/230-1-60 187 253 0.44
1
⁄
16
hp 0.55 15 0.44 14
619F036 208/230-1-60 187 253
0.44
0.44
1
⁄
16
hp
1
⁄
16
hp
1.10 15 0.88 14
LEGEND
COMP — Compressor
FLA — Full Load Amps
HACR — Heating, Air Conditioning, and Refrigeration
LRA — Locked Rotor Amps
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection Amps
(Fuse or HACR Circuit Breaker)
RLA — Rated Load Amps
*Permissible limits of the voltage range at which units will operate
satisfactorily.
†These units can only be used with 619E high wall fan coil units.
**MCA and MOCP are for both indoor and outdoor units.
††Indoor fan coil must be connected to outdoor unit. See outdoor unit
for required data.
\ The 619C018 fan coil is a 619C024 fan coil, but uses a different motor
speed fan tap plug than the 619C024. Electrical data is identical for
both units.
NOTE: Refer to 538B,D Series Heat Pump Product Data literature for
electrical data for heat pump fan coils matched with cooling-only con-
densing units.