Product data

GROSS COOLING CAPACITIES (cont)
SYSTEM 3* HIGH WALL SYSTEM; 538A018 WITH 619E018
TEMP (F)
AIR ENTERING
CONDENSER
(Edb)
AIR ENTERING EVAPORATOR CFM/BF
360/0.12 414/0.13 480/0.15
Air Entering Evaporator Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
55
TCG 16.1 16.9 17.4 17.6 16.5 17.2 17.3 17.8 17.0 17.4 17.8 18.0
SHG 15.2 13.0 10.7 8.63 16.0 13.3 10.8 8.76 16.8 13.9 11.3 8.91
TC 16.0 16.8 17.3 17.5 16.4 17.1 17.2 17.6 16.8 17.2 17.7 17.8
kW 1.01 1.02 1.02 1.03 1.02 1.03 1.03 1.03 1.03 1.04 1.04 1.04
CMP 0.860 0.868 0.873 0.874 0.864 0.871 0.871 0.878 0.871 0.873 0.879 0.881
LDB 41.4 47.1 52.9 58.2 44.7 50.3 56.3 60.8 48.0 53.7 58.7 63.2
LWB 38.1 44.2 50.7 57.5 40.5 46.6 53.3 59.6 42.6 48.9 55.0 61.4
65
TCG 15.8 17.0 17.7 18.2 16.3 17.3 17.8 18.4 16.8 17.7 18.5 18.6
SHG 15.2 13.2 10.9 8.87 16.1 13.9 11.2 8.99 16.8 14.6 11.8 9.18
TC 15.7 16.8 17.5 18.1 16.2 17.2 17.6 18.2 16.6 17.6 18.3 18.4
kW 1.11 1.12 1.13 1.14 1.12 1.13 1.14 1.15 1.13 1.15 1.16 1.16
CMP 0.958 0.971 0.979 0.989 0.964 0.976 0.980 0.990 0.968 0.982 0.993 0.993
LDB 41.3 46.5 52.3 57.6 44.4 49.5 55.5 60.3 48.0 52.3 57.6 62.7
LWB 38.6 44.1 50.5 56.9 40.7 46.5 52.9 59.1 42.8 48.6 54.6 61.0
75
TCG 15.1 16.5 17.6 18.6 15.8 17.0 18.1 18.5 16.6 17.5 18.4 18.9
SHG 14.9 13.1 11.0 9.01 15.8 13.9 11.6 9.08 16.6 14.7 12.0 9.37
TC 15.0 16.4 17.5 18.5 15.7 16.9 18.0 18.4 16.4 17.3 18.2 18.7
kW 1.20 1.22 1.24 1.26 1.22 1.24 1.25 1.26 1.24 1.25 1.27 1.28
CMP 1.05 1.07 1.09 1.11 1.06 1.08 1.10 1.10 1.07 1.09 1.10 1.11
LDB 42.2 46.8 52.1 57.3 45.1 49.4 54.6 60.1 48.5 52.0 57.2 62.3
LWB 39.4 44.7 50.5 56.6 41.3 46.8 52.6 59.0 43.0 48.8 54.6 60.8
85
TCG 14.4 15.9 17.3 18.6 15.2 16.4 17.7 18.8 16.0 16.9 18.1 18.8
SHG 14.4 12.9 10.9 8.98 15.2 13.7 11.5 9.24 16.0 14.7 12.0 9.39
TC 14.3 15.7 17.2 18.4 15.0 16.3 17.6 18.7 15.9 16.7 17.9 18.7
kW 1.28 1.32 1.35 1.38 1.31 1.34 1.36 1.39 1.34 1.35 1.38 1.39
CMP 1.13 1.17 1.20 1.23 1.15 1.18 1.21 1.23 1.18 1.19 1.21 1.23
LDB 43.5 47.4 52.3 57.4 46.5 49.8 54.7 59.8 49.5 52.2 57.2 62.3
LWB 40.4 45.5 50.9 56.6 42.0 47.4 52.9 58.7 43.6 49.3 54.9 60.8
95
TCG 13.7 15.0 16.6 17.9 14.5 15.5 17.1 18.3 15.3 16.1 17.5 18.5
SHG 13.7 12.4 10.7 8.71 14.5 13.4 11.3 9.04 15.3 14.4 11.9 9.34
TC 13.6 14.9 16.4 17.8 14.4 15.4 16.9 18.1 15.1 15.9 17.3 18.4
kW 1.37 1.41 1.45 1.48 1.40 1.43 1.47 1.50 1.43 1.45 1.49 1.51
CMP 1.22 1.26 1.30 1.33 1.24 1.27 1.31 1.34 1.27 1.29 1.32 1.35
LDB 45.2 48.5 53.1 58.0 48.1 50.6 55.3 60.2 50.9 52.7 57.4 62.4
LWB 41.4 46.5 51.7 57.2 42.8 48.3 53.5 59.2 44.3 50.0 55.3 61.0
105
TCG 13.0 14.1 15.7 17.3 13.8 14.6 16.2 17.7 14.6 15.1 16.7 17.9
SHG 13.0 12.0 10.3 8.47 13.8 12.9 11.0 8.82 14.6 13.9 11.7 9.15
TC 12.9 14.0 15.6 17.2 13.6 14.4 16.1 17.5 14.4 14.9 16.5 17.7
kW 1.45 1.49 1.55 1.60 1.48 1.51 1.57 1.61 1.52 1.54 1.59 1.62
CMP 1.30 1.34 1.40 1.45 1.33 1.35 1.41 1.46 1.35 1.37 1.43 1.46
LDB 47.0 49.6 54.0 58.7 49.6 51.6 55.9 60.7 52.4 53.6 57.9 62.8
LWB 42.3 47.6 52.6 57.8 43.6 49.3 54.3 59.7 45.0 50.8 55.9 61.4
115
TCG 12.4 13.2 14.7 16.4 13.1 13.6 15.2 16.8 13.8 14.1 15.7 17.1
SHG 12.4 11.6 9.86 8.12 13.1 12.4 10.5 8.52 13.8 13.4 11.3 8.93
TC 12.2 13.1 14.6 16.3 12.9 13.5 15.1 16.7 13.6 13.9 15.5 17.0
kW 1.53 1.56 1.63 1.70 1.57 1.59 1.66 1.72 1.60 1.62 1.68 1.73
CMP 1.38 1.41 1.48 1.55 1.41 1.43 1.50 1.56 1.44 1.45 1.52 1.57
LDB 48.7 50.8 55.1 59.6 51.2 52.6 56.9 61.4 53.8 54.6 58.6 63.2
LWB 43.1 48.7 53.6 58.7 44.4 50.2 55.2 60.3 45.7 51.6 56.7 61.9
125
TCG 11.6 12.2 13.7 15.3 12.3 12.7 14.2 15.8 13.0 13.1 14.6 16.2
SHG 11.6 11.1 9.44 7.70 12.3 12.0 10.1 8.14 13.0 12.9 10.9 8.61
TC 11.4 12.1 13.6 15.2 12.1 12.5 14.0 15.6 12.8 12.9 14.4 16.0
kW 1.61 1.64 1.71 1.79 1.65 1.66 1.73 1.81 1.68 1.69 1.76 1.84
CMP 1.46 1.48 1.56 1.64 1.49 1.50 1.58 1.66 1.52 1.53 1.60 1.67
LDB 50.7 52.0 56.2 60.6 53.0 53.7 57.8 62.2 55.3 55.6 59.5 63.8
LWB 44.1 49.8 54.7 59.7 45.3 51.1 56.1 61.2 46.4 52.4 57.5 62.6
Rating condition.
Not recommended for long-term operation.
LEGEND
BF Bypass Factor
CMP Compressor
Edb Entering Dry Bulb
Ewb Entering Wet Bulb
kW Total Power
LDB Leaving Dry Bulb
LWB Leaving Wet Bulb
SHG Gross Sensible Capacity (1000 Btuh)
TC Total Net Cooling Capacity (1000 Btuh)
TCG Gross Cooling Capacity (1000 Btuh)
*Refer to Systems Index Table on page 21.
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHG is based on 80 F edb temperature of air entering indoor
coil.
Below 80 F edb, subtract (corr factor x cfm) from SHG.
Above 80 F edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 BF) x (edb 80).