Product data

GROSS COOLING CAPACITIES (cont)
SYSTEM 2* HIGH WALL SYSTEM; 538C012 WITH 619E012
TEMP (F)
AIR ENTERING
CONDENSER
(Edb)
AIR ENTERING EVAPORATOR CFM/BF
245/0.12 280/0.14 302/0.15
Air Entering Evaporator Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
55
TCG 10.6 10.9 11.1 11.2 10.6 11.0 11.2 11.3 10.7 11.0 11.2 11.1
SHG 9.99 8.37 6.81 5.53 10.2 8.55 6.94 5.58 10.4 8.61 6.98 5.54
TC 10.5 10.8 10.9 11.1 10.5 10.9 11.0 11.1 10.6 10.9 11.0 11.0
kW 0.742 0.750 0.752 0.756 0.747 0.756 0.759 0.761 0.752 0.758 0.761 0.760
CMP 0.635 0.642 0.644 0.647 0.635 0.643 0.647 0.649 0.637 0.642 0.646 0.645
LDB 42.8 48.8 54.8 59.6 46.6 52.2 57.5 62.0 48.5 54.1 59.1 63.5
LWB 38.9 45.3 52.0 58.7 41.4 47.6 54.0 60.5 42.6 48.8 55.1 61.6
65
TCG 10.7 11.2 11.6 12.0 10.9 11.4 11.6 11.9 11.1 11.5 11.6 11.8
SHG 10.3 8.67 7.21 5.84 10.8 9.01 7.30 5.84 11.1 9.21 7.35 5.81
TC 10.6 11.0 11.5 11.9 10.8 11.2 11.5 11.8 11.0 11.3 11.5 11.6
kW 0.826 0.832 0.844 0.853 0.833 0.842 0.848 0.855 0.842 0.847 0.851 0.853
CMP 0.718 0.725 0.737 0.746 0.721 0.729 0.736 0.743 0.727 0.732 0.736 0.738
LDB 41.5 47.7 53.2 58.4 44.9 50.7 56.3 61.1 46.5 52.2 57.9 62.6
LWB 38.7 44.9 51.1 57.6 40.9 47.0 53.4 59.7 41.9 48.2 54.5 60.9
75
TCG 10.5 11.2 11.8 12.3 10.9 11.4 12.0 12.3 11.1 11.6 12.1 12.2
SHG 10.3 8.85 7.38 5.95 10.9 9.27 7.65 6.01 11.1 9.55 7.78 6.03
TC 10.4 11.1 11.7 12.2 10.8 11.3 11.9 12.2 11.0 11.5 12.0 12.1
kW 0.911 0.924 0.938 0.950 0.923 0.933 0.948 0.954 0.931 0.941 0.954 0.955
CMP 0.804 0.816 0.831 0.842 0.811 0.821 0.836 0.842 0.816 0.826 0.839 0.840
LDB 41.6 47.1 52.6 58.0 44.5 49.8 55.2 60.6 46.4 51.2 56.6 62.0
LWB 39.0 44.8 50.8 57.1 41.0 46.9 52.8 59.3 42.0 48.0 53.9 60.4
85
TCG 9.83 11.0 11.8 12.3 10.5 11.3 12.0 12.4 10.9 11.4 12.1 12.5
SHG 9.83 8.85 7.44 5.98 10.5 9.36 7.73 6.10 10.9 9.65 7.92 6.16
TC 9.72 10.9 11.7 12.2 10.4 11.1 11.9 12.3 10.8 11.3 12.0 12.3
kW 1.00 1.02 1.04 1.05 1.02 1.03 1.05 1.06 1.03 1.04 1.05 1.06
CMP 0.896 0.915 0.933 0.946 0.909 0.922 0.937 0.947 0.913 0.924 0.940 0.948
LDB 43.4 47.1 52.4 57.9 45.8 49.6 54.9 60.3 47.0 50.9 56.2 61.6
LWB 40.4 45.2 50.8 57.0 41.7 47.2 52.9 59.1 42.3 48.2 53.9 60.1
95
TCG 9.18 10.1 11.6 12.3 9.73 10.5 11.8 12.5 10.2 10.8 11.9 12.7
SHG 9.18 8.38 7.39 5.96 9.73 9.03 7.75 6.17 10.2 9.42 7.94 6.28
TC 9.07 9.95 11.5 12.2 9.61 10.4 11.7 12.4 10.0 10.6 11.6 12.5
kW 1.10 1.12 1.15 1.17 1.12 1.13 1.16 1.18 1.13 1.14 1.17 1.19
CMP 0.994 1.01 1.04 1.06 1.01 1.02 1.05 1.07 1.02 1.03 1.05 1.07
LDB 45.8 48.8 52.6 57.9 48.3 50.6 54.9 60.1 49.4 51.6 56.1 61.2
LWB 41.7 46.8 51.2 57.1 42.9 48.3 53.1 59.0 43.5 49.1 54.2 59.9
105
TCG 8.50 9.14 10.6 12.0 9.03 9.53 11.0 12.3 9.43 9.76 11.3 12.4
SHG 8.50 7.95 6.95 5.87 9.03 8.57 7.42 6.09 9.43 8.95 7.70 6.22
TC 8.39 9.02 10.5 11.9 8.90 9.40 10.9 12.1 9.30 9.62 11.1 12.3
kW 1.21 1.22 1.26 1.29 1.23 1.24 1.28 1.30 1.24 1.25 1.28 1.31
CMP 1.10 1.12 1.15 1.18 1.12 1.13 1.16 1.19 1.12 1.13 1.17 1.19
LDB 48.4 50.5 54.2 58.3 50.6 52.1 55.9 60.3 51.6 53.1 56.9 61.4
LWB 43.0 48.4 52.8 57.5 44.1 49.8 54.2 59.3 44.6 50.5 55.0 60.2
115
TCG 7.95 8.10 9.47 11.3 8.40 8.47 9.84 11.8 8.65 8.69 10.1 12.0
SHG 7.95 7.47 6.47 5.56 8.40 8.08 6.93 5.90 8.65 8.44 7.21 6.09
TC 7.84 7.99 9.36 11.2 8.27 8.34 9.72 11.6 8.51 8.55 9.92 11.9
kW 1.33 1.34 1.37 1.41 1.35 1.35 1.39 1.43 1.36 1.36 1.40 1.44
CMP 1.22 1.23 1.27 1.31 1.23 1.24 1.28 1.32 1.24 1.24 1.28 1.33
LDB 50.4 52.3 56.0 59.4 52.7 53.8 57.5 60.9 54.0 54.6 58.4 61.8
LWB 44.0 50.2 54.5 58.6 45.1 51.3 55.8 59.9 45.7 51.9 56.4 60.6
125
TCG 7.27 7.40 8.52 10.1 7.68 7.69 8.87 10.5 7.92 7.89 9.08 10.7
SHG 7.27 7.14 6.08 5.11 7.68 7.67 6.54 5.42 7.92 7.89 6.82 5.60
TC 7.16 7.29 8.41 9.97 7.55 7.56 8.75 10.3 7.78 7.75 8.94 10.5
kW 1.46 1.46 1.50 1.54 1.48 1.47 1.51 1.56 1.49 1.49 1.52 1.57
CMP 1.35 1.35 1.39 1.43 1.36 1.36 1.40 1.44 1.37 1.37 1.40 1.45
LDB 53.0 53.5 57.5 61.2 55.1 55.1 58.8 62.5 56.2 56.3 59.6 63.3
LWB 45.3 51.3 55.9 60.2 46.3 52.4 57.0 61.4 46.8 52.9 57.6 62.1
Rating condition.
Not recommended for long-term operation.
LEGEND
BF Bypass Factor
CMP Compressor
Edb Entering Dry Bulb
Ewb Entering Wet Bulb
kW Total Power
LDB Leaving Dry Bulb
LWB Leaving Wet Bulb
SHG Gross Sensible Capacity (1000 Btuh)
TC Total Net Cooling Capacity (1000 Btuh)
TCG Gross Cooling Capacity (1000 Btuh)
*Refer to Systems Index Table on page 21.
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHG is based on 80 F edb temperature of air entering indoor
coil.
Below 80 F edb, subtract (corr factor x cfm) from SHG.
Above 80 F edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 BF) x (edb 80).
23