Product data
SPECIFICATIONS — 619F IN-CEILING CASSETTE UNITS
UNIT 619F 024 036
NOMINAL CAPACITY (Tons) 1
1
⁄
2
3
NOMINAL SIZE (Btuh) 18,000 36,000
OPERATING WEIGHT (lb) 61.6 105.8
MOISTURE REMOVAL RATE (Pints/Hr) 7.0 9.6
FINISH Ceiling White with Black Discharge Grille
REFRIGERANT R-22
Control (Cooling) AccuRaterT Metering Device
System Charge Required (lb)* 4.8 6.0
INDOOR FAN Direct Drive Centrifugal
Rpm...Cfm High 1190...525 970...915
Rpm...Cfm Medium 930...415 790...745
Rpm...Cfm Low 840...375 635...635
High Speed Watts 100 180
Motor (Quantity) Hp (1)
1
⁄
16
(2)
1
⁄
16
Blowers — No. ...Size (in.) 1...10 x 8 2...10 x 8
INDOOR COIL Copper Tube, Aluminum Fin
Face Area (sq ft) 2.66 5.67
No. of Rows 32
Fins/in. 14.0 14.0
Circuits 44
FILTERS Cleanable
(Quantity) Size (in.) (1) 16
1
⁄
2
x16
1
⁄
2
(2) 16
1
⁄
2
x16
1
⁄
2
AIRSWEEP None
CONTROLS Solid-State Electromechanical
Remote Controller Hard Wired
Auto. Restart Yes
Diagnostics Yes (with accessory programmable thermostat)
Timer Mode 24-Hour Countdown Type
Test Mode Yes
Fan Mode High/Medium/Low/—/Auto/Continuous
Control Voltage 24 v (provided)
REFRIGERANT LINES
Connection Type Flare
Liquid Line OD (in.)
3
⁄
8
Vapor Line OD (in.)
5
⁄
8
3
⁄
4
Maximum Length (ft) 200
Maximum Lift Fan Coil (Above Outdoor) (ft) 65
Maximum Lift Fan Coil (Below Outdoor) (ft) 150
CONDENSATE DRAIN CONNECTION Hose
CONDENSATE DRAIN SIZE (in.) 1.0
*The condensing (outdoor) unit is shipped with a full charge. The amount of charge shown is for small-
est system combination and is determined based on 15 ft of line. See Application Data section on
page 41 for information on longer line lengths and condensing unit combinations.