Specifications

ELECTRICAL DATA
538D HEAT PUMPS
UNIT
538D
V-PH-Hz
OPERATING
VOLTAGE
MINIMUM*
OPERATING
VOLTAGE
MAXIMUM*
COMP RLA COMP LRA FAN FLA
POWER
MCA MOCP FLA
009 115-1-60 104 127 9.0 45.0 0.76 11.2 15 9.76
012 208/230-1-60 187 253 5.8 30.0 0.35 8.9 15 6.15
018 208/230-1-60 187 253 9.8 49.0 0.70 13.0 20 10.5
024 208/230-1-60 187 253 11.7 61.0 0.70 15.3 25 12.4
538B HEAT PUMPS
UNIT SIZE
538B
V-PH-Hz
OPERATING
VOLTAGE
MINIMUM*
OPERATING
VOLTAGE
MAXIMUM*
COMP RLA COMP LRA FAN FLA
POWER
MCA MOCP FLA
018
208/230-1-60 187 253
9.8 49.0 0.70 13.0 20 10.5
024 11.7 61.0 0.70 15.3 25 12.4
030 13.5 76.0 0.70 17.6 30 14.2
036
208/230-1-60 187 253 17.9 90.5 0.70 23.1 40 18.6
208/230-3-60 187 253 11.2 66.0 1.45 15.5 25 12.7
460-3-60 414 506 5.2 35.0 0.80 7.3 15 6.0
048
208/230-1-60 187 253 23.2 110.0 1.45 30.5 50 24.7
208/230-3-60 187 253 15.3 92.0 1.45 20.6 35 16.8
460-3-60 414 506 7.3 46.0 0.80 9.9 15 8.1
060
208/230-1-60 187 253 31.7 135.0 1.45 42.0 60 33.2
208/230-3-60 187 253 20.4 105.0 1.45 27.0 45 21.9
460-3-60 414 506 10.8 55.0 0.80 15.0 25 11.6
FAN COIL UNITS
UNIT V-PH-Hz
OPERATING
VOLTAGE
—MINIMUM*
OPERATING
VOLTAGE
—MAXIMUM*
FAN FLA
HEATER POWER
MINIMUM
WIRE SIZE
kW FLA MCA MOCP FLA
619C018,024 208/230-1-60 187 253 0.50 2.00 8.66 9.29 15 11.29 14
619C036 208/230-1-60 187 253 1.30 3.00 13.00 17.70 20 14.30 14
619C048 208/230-1-60 187 253 1.60† 4.00 17.40 23.80 25 19.00 12
619C060 208/230-1-60 187 253 2.60** 5.00 2.17 28.70 30 24.30 10
619E009 115-1-60 104 127 0.41 †† †† 0.41 14
619E012 208/230-1-60 187 253 0.23 †† †† 0.23 14
619E018 208/230-1-60 187 253 0.53 0.66 15 0.53 14
619E024 208/230-1-60 187 253 0.53 0.66 15 0.53 14
619F024 208/230-1-60 187 253 0.44 1.80\ 7.50 0.6/ 7.5 15/15 7.94 14/14
619F036 208/230-1-60 187 253 0.78 2.70\ 11.25 10.0/15.0 15/15 12.80 14/14
619F048 208/230-1-60 187 253 1.04 2.70\ 11.25 10.0/15.0 15/15 12.03 14/14
LEGEND
FLA Full Load Amps
HACR Heating, Air Conditioning, and Refrigeration
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection Amps (Fuse or HACR
Circuit Breaker)
RLA Rated Load Amps
*Permissible limits of the voltage range at which units will operate
satisfactorily.
†One fan is 1.1 amps, and the other is 0.5 amp.
**Two fans, each operating at 1.3 amps.
††MCA and MOCP are for both indoor and outdoor units (system) and
are listed in the outdoor unit tables.
\Separate heater and unit circuits required.
NOTE: Two MCA, MOCP, and minimum wire size values are shown for
units with separate unit and heater circuits. The first value applies to the
unit circuit; the second applies to the heater circuit.
59