Specifications

PERFORMANCE DATA (cont)
INSTANTANEOUS AND INTEGRATED HEATING RATINGS (cont)
SYSTEM 10* CEILING-SUSPENDED SYSTEM (538B048 WITH 619C048)
TEMP (F)
AIR
ENTERING
INDOOR UNIT
AIR
ENTERING
INDOOR UNIT
(CFM)
AIR TEMPERATURE ENTERING OUTDOOR COIL (F)
010172030404760
55
820
Cap 20.60 19.00 25.70 23.50 29.30 26.70 30.80 27.80 35.80 31.40 41.70 41.70 46.40 46.40 53.50 53.50
kW 3.26 3.44 3.56 3.60 3.75 3.92 4.05 4.14
975
Cap 21.30 19.60 26.40 24.20 30.00 27.40 31.60 28.50 36.70 32.20 42.90 42.90 47.30 47.30 54.30 53.40
kW 3.29 3.45 3.56 3.60 3.72 3.86 3.93 3.93
1130
Cap 21.90 20.10 27.00 24.70 30.60 27.90 32.20 29.00 37.50 32.80 43.40 43.40 46.80 46.80 53.50 53.50
kW 3.33 3.48 3.58 3.61 3.71 3.80 3.80 3.82
60
820
Cap 19.70 18.10 24.80 22.70 28.40 25.90 29.90 27.00 35.00 30.70 40.90 40.90 45.40 45.40 53.00 53.00
kW 3.29 3.48 3.61 3.66 3.82 4.00 4.13 4.27
975
Cap 20.40 18.70 25.50 23.40 29.20 26.60 30.70 27.70 36.00 31.50 42.10 42.10 46.50 46.50 53.30 53.30
kW 3.33 3.50 3.62 3.66 3.80 3.95 4.03 4.08
1130
Cap 20.90 19.20 26.10 23.90 29.80 27.20 31.40 28.30 36.70 32.10 42.60 42.60 46.40 46.40 53.60 53.60
kW 3.37 3.53 3.64 3.67 3.79 3.90 3.92 3.99
65
820
Cap 18.70 17.20 23.90 21.80 27.50 25.10 29.00 26.20 34.20 30.00 40.00 40.00 44.50 44.50 52.40 52.40
kW 3.33 3.53 3.66 3.72 3.89 4.07 4.21 4.41
975
Cap 19.40 17.90 24.70 22.60 28.30 25.80 29.90 27.00 35.20 30.80 41.20 41.20 45.70 45.70 53.10 53.10
kW 3.37 3.55 3.68 3.72 3.87 4.03 4.13 4.24
1130
Cap 20.00 18.40 25.30 23.10 29.00 26.40 30.60 27.60 35.90 31.50 41.90 41.90 45.90 45.90 53.60 53.60
kW 3.41 3.58 3.70 3.74 3.87 4.00 4.04 4.15
70
820
Cap 17.80 16.40 23.00 21.00 26.60 24.30 28.20 25.40 33.50 29.30 39.20 39.20 43.50 43.50 51.80 51.80
kW 3.36 3.57 3.72 3.77 3.96 4.15 4.29 4.54
975
Cap 18.50 17.00 23.80 21.80 27.50 25.10 29.10 26.30 34.40 30.20 40.30 40.30 44.80 44.80 53.00 53.00
kW 3.41 3.60 3.73 3.78 3.95 4.12 4.24 4.40
1130
Cap 19.00 17.50 24.40 22.30 28.20 25.70† 29.80 26.90 35.10 30.80 41.20 41.20 45.50 45.50† 53.70 53.70
kW 3.45 3.63 3.76 3.80 3.95 4.10 4.17 4.31
75
820
Cap 16.80 15.40 22.00 20.10 25.60 23.30 27.20 24.50 32.60 28.50 38.30 38.30 42.60 42.60 50.80 50.80
kW 3.39 3.61 3.76 3.82 4.02 4.23 4.37 4.62
975
Cap 17.40 16.00 22.80 20.80 26.50 24.20 28.20 25.40 33.60 29.40 39.50 39.50 43.90 43.90 52.20 52.20
kW 3.44 3.64 3.78 3.84 4.01 4.19 4.32 4.53
1130
Cap 18.00 16.50 23.50 21.50 27.30 24.90 28.90 26.10 34.40 30.10 40.30 40.30 44.80 44.80 52.40 52.40
kW 3.49 3.68 3.81 3.86 4.02 4.18 4.28 4.38
80
820
Cap 15.70 14.50 20.90 19.20 24.60 22.40 26.20 23.70 31.70 27.80 37.50 37.50 41.70 41.70 49.70 49.70
kW 3.42 3.65 3.81 3.97 4.08 4.30 4.45 4.71
975
Cap 16.40 15.10 21.80 19.90 25.50 23.30 27.20 24.50 32.80 28.70 38.60 38.60 43.00 43.00 51.50 51.50
kW 3.47 3.69 3.84 3.89 4.08 4.27 4.41 4.66
1130
Cap 16.40 15.10 21.80 19.90 25.50 23.30 27.20 24.50 32.80 28.70 38.60 38.60 43.00 43.00 51.50 51.50
kW 3.47 3.69 3.84 3.89 4.08 4.27 4.41 4.66
Indicates rating condition.
Indicates integrated rating.
LEGEND
Cap Heating Capacity (1000 Btuh) (includes indoor-fan motor heat)
kW Total Power Input (includes compressor motor power input, outdoor-
fan motor power input, and indoor-fan motor power input)
*Refer to Systems Index Table on page 26.
†Integrated Rating.
NOTE: Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the
outdoor coil and the heat required to defrost it.
52