Specifications
PERFORMANCE DATA (cont)
COOLING CAPACITIES (cont)
SYSTEM 16* — IN-CEILING CASSETTE SYSTEM (538B036 3-PHASE UNIT WITH 619F048)
TEMP (F)
AIR ENTERING
OUTDOOR UNIT
(Edb)
AIR ENTERING INDOOR UNIT — CFM/BF
680/0.08 880/0.11 1100/0.14
Air Entering Indoor Unit — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
55
TCG 35.4 35.7 38.9 35.7 35.9 36.6 38.2 35.6 38.1 35.6 35.0 34.8
SHG 33.9 27.1 23.8 17.5 35.9 28.6 23.7 17.4 38.1 28.1 21.3 16.9
TC 35.0 35.3 38.4 35.3 35.4 36.0 37.6 35.0 37.4 34.9 34.3 34.1
kW 2.15 2.04 2.19 2.06 2.12 2.14 2.17 2.05 2.26 2.13 2.06 2.03
CMP 1.80 1.69 1.84 1.70 1.74 1.76 1.79 1.67 1.84 1.71 1.65 1.62
LDB 39.4 47.9 51.8 59.6 47.0 54.0 58.6 64.5 52.0 59.9 65.0 68.2
LWB 37.3 44.3 49.8 58.5 42.3 48.6 54.6 62.1 44.8 52.0 58.4 64.5
65
TCG 33.2 34.3 37.3 35.9 34.5 35.4 37.5 36.4 36.6 35.1 35.7 36.3
SHG 32.2 26.6 23.1 17.5 34.5 28.6 23.8 17.9 36.6 29.2 22.9 18.0
TC 32.8 33.9 36.9 35.5 33.9 34.9 36.9 35.9 35.9 34.4 35.0 35.6
kW 2.43 2.39 2.53 2.46 2.45 2.48 2.55 2.50 2.57 2.50 2.50 2.52
CMP 2.07 2.03 2.16 2.10 2.06 2.09 2.15 2.10 2.15 2.07 2.07 2.09
LDB 40.5 47.5 51.8 58.8 47.4 53.1 57.7 63.4 52.4 58.2 63.1 66.8
LWB 38.2 44.6 50.0 57.8 42.5 48.7 54.4 61.3 45.0 51.8 57.8 63.8
75
TCG 31.0 32.9 35.8 36.2 33.0 34.2 36.8 37.3 35.0 34.6 36.4 37.8
SHG 30.5 26.1 22.4 17.6 33.0 28.6 23.9 18.5 35.0 30.3 24.5 19.1
TC 30.6 32.5 35.4 35.7 32.5 33.7 36.2 36.8 34.3 34.0 35.8 37.2
kW 2.71 2.75 2.86 2.87 2.79 2.83 2.92 2.94 2.89 2.87 2.94 3.00
CMP 2.34 2.38 2.49 2.49 2.39 2.42 2.52 2.54 2.46 2.43 2.50 2.56
LDB 41.5 47.0 51.8 58.0 47.8 52.2 56.8 62.2 52.8 56.5 61.1 65.4
LWB 39.1 44.8 50.3 57.1 42.7 48.7 54.3 60.6 45.2 51.6 57.2 63.0
85
TCG 28.8 31.5 34.3 36.4 31.6 33.1 36.0 38.1 33.4 34.1 37.1 39.4
SHG 28.7 25.6 21.8 17.6 31.6 28.6 24.1 19.0 33.4 31.4 26.1 20.2
TC 28.4 31.1 33.9 36.0 31.1 32.5 35.5 37.6 32.8 33.5 36.5 38.7
kW 2.99 3.11 3.19 3.27 3.13 3.17 3.30 3.38 3.21 3.24 3.38 3.48
CMP 2.60 2.72 2.81 2.89 2.71 2.75 2.88 2.97 2.76 2.79 2.93 3.03
LDB 42.5 46.6 51.7 57.2 48.2 51.3 55.9 61.1 53.2 54.8 59.2 64.0
LWB 39.9 45.1 50.5 56.5 42.9 48.8 54.1 59.9 45.4 51.3 56.6 62.3
95
TCG 26.6 28.9 32.1 34.8 29.4 30.7 33.7 36.5 31.6 32.2 35.0 37.9
SHG 26.6 24.0 20.7 16.9 29.4 27.5 23.0 18.4 31.6 30.8 25.4 19.8
TC 26.2 28.5 31.7 34.5 28.9 30.2 33.2 36.0 31.0 31.6 34.4 37.2
kW 3.25 3.38 3.55 3.65 3.43 3.51 3.64 3.77 3.59 3.62 3.74 3.88
CMP 2.86 2.98 3.15 3.26 3.00 3.08 3.21 3.34 3.12 3.15 3.28 3.42
LDB 44.1 47.7 52.3 57.4 49.5 51.5 56.2 61.1 53.8 54.5 59.1 63.8
LWB 40.8 46.1 51.2 56.7 43.6 49.4 54.6 60.0 45.7 51.7 56.9 62.3
105
TCG 24.6 26.4 29.3 32.4 27.1 28.0 30.9 34.2 29.1 29.3 32.2 35.3
SHG 24.6 22.5 19.2 15.9 27.1 25.8 21.7 17.5 29.1 28.8 24.1 18.9
TC 24.2 26.0 28.9 32.1 26.6 27.5 30.5 33.8 28.5 28.7 31.6 34.7
kW 3.53 3.65 3.83 4.04 3.72 3.78 3.97 4.18 3.89 3.91 4.09 4.26
CMP 3.13 3.24 3.43 3.63 3.28 3.34 3.54 3.75 3.42 3.43 3.61 3.78
LDB 45.8 48.7 53.3 58.1 51.0 52.4 56.8 61.4 55.1 55.4 59.4 64.0
LWB 41.7 47.2 52.2 57.3 44.3 50.2 55.3 60.4 46.3 52.3 57.5 62.7
115
TCG 22.5 23.9 26.6 29.5 24.8 25.3 28.0 31.1 26.7 26.7 29.1 32.2
SHG 22.5 21.0 17.8 14.6 24.8 24.0 20.2 16.1 26.7 26.7 22.5 17.6
TC 22.2 23.5 26.2 29.1 24.3 24.9 27.6 30.6 26.1 26.1 28.5 31.6
kW 3.83 3.93 4.13 4.35 4.03 4.07 4.27 4.50 4.20 4.20 4.39 4.62
CMP 3.41 3.51 3.71 3.93 3.58 3.62 3.82 4.05 3.72 3.72 3.90 4.13
LDB 47.5 49.9 54.4 59.1 52.5 53.3 57.7 62.3 56.4 56.4 60.1 64.6
LWB 42.6 48.2 53.2 58.3 45.0 51.0 56.1 61.2 46.9 52.9 58.2 63.3
125
TCG 20.6 21.4 23.9 26.6 22.6 22.8 25.2 28.0 24.3 24.2 26.1 29.0
SHG 20.6 19.4 16.5 13.4 22.6 22.3 18.7 14.8 24.3 24.2 21.0 16.3
TC 20.2 21.1 23.6 26.3 22.1 22.3 24.7 27.5 23.7 23.7 25.5 28.4
kW 4.13 4.21 4.43 4.66 4.34 4.36 4.57 4.82 4.52 4.52 4.69 4.94
CMP 3.70 3.79 4.00 4.24 3.88 3.90 4.11 4.36 4.02 4.02 4.19 4.44
LDB 49.3 51.0 55.5 60.1 54.0 54.3 58.6 63.1 57.7 57.7 60.8 65.3
LWB 43.4 49.3 54.3 59.3 45.8 51.9 56.9 62.0 47.5 53.5 58.8 63.9
Rating condition.
Not recommended for long-term operation.
LEGEND
BF — Bypass Factor
CMP — Compressor
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW — Total Power
LDB — Leaving Dry Bulb
LWB — Leaving Wet Bulb
SHG — Gross Sensible Capacity (1000 Btuh)
TC — Total Net Cooling Capacity (1000 Btuh)
TCG — Gross Cooling Capacity (1000 Btuh)
*Refer to Systems Index Table on page 26.
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHG is based on 80 F edb temperature of air entering indoor
coil.
Below 80 F edb, subtract (corr factor x cfm) from SHG.
Above 80 F edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).