Specifications
PERFORMANCE DATA (cont)
COOLING CAPACITIES (cont)
SYSTEM 15* — IN-CEILING CASSETTE SYSTEM (538B036 SINGLE-PHASE UNIT WITH 619F048)
TEMP (F)
AIR ENTERING
OUTDOOR UNIT
(Edb)
AIR ENTERING INDOOR UNIT — CFM/BF
680/0.09 880/0.12 1100/0.15
Air Entering Indoor Unit — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
55
TCG 32.3 34.6 36.4 38.0 34.3 36.1 37.0 38.5 35.7 36.9 38.0 39.5
SHG 31.5 27.4 22.8 18.4 34.3 30.3 24.1 19.1 35.7 32.8 25.8 20.0
TC 31.9 34.2 36.0 37.6 33.8 35.5 36.5 38.0 35.1 36.3 37.3 38.8
kW 2.15 2.18 2.22 2.25 2.21 2.25 2.26 2.29 2.27 2.30 2.32 2.35
CMP 1.87 1.90 1.94 1.97 1.90 1.93 1.94 1.98 1.92 1.95 1.97 2.00
LDB 41.3 46.5 52.1 57.6 47.5 51.4 57.3 62.2 53.0 55.3 60.7 65.1
LWB 38.8 44.4 50.5 56.8 42.6 48.4 54.6 60.6 45.3 51.1 57.1 62.9
65
TCG 31.1 33.6 35.6 37.8 33.3 34.9 36.8 38.1 35.2 36.0 38.0 39.0
SHG 30.6 26.9 22.4 18.3 33.3 29.7 24.3 19.0 35.2 32.6 26.4 20.0
TC 30.7 33.1 35.2 37.4 32.8 34.3 36.2 37.6 34.5 35.3 37.3 38.4
kW 2.39 2.43 2.46 2.51 2.45 2.48 2.51 2.54 2.52 2.54 2.58 2.61
CMP 2.11 2.15 2.18 2.23 2.14 2.17 2.20 2.23 2.17 2.19 2.23 2.26
LDB 41.5 46.3 51.9 57.2 47.8 51.3 56.6 61.9 52.8 54.8 59.7 64.8
LWB 39.1 44.6 50.5 56.5 42.7 48.5 54.3 60.4 45.2 51.2 56.8 62.7
75
TCG 29.4 31.9 34.2 36.5 31.9 33.4 35.6 37.3 33.8 34.5 36.8 38.0
SHG 29.2 25.8 21.8 17.7 31.9 29.0 23.8 18.7 33.8 32.0 26.0 19.7
TC 29.0 31.5 33.8 36.1 31.4 32.9 35.1 36.8 33.2 33.9 36.1 37.4
kW 2.64 2.69 2.74 2.79 2.72 2.76 2.80 2.84 2.80 2.82 2.87 2.90
CMP 2.36 2.42 2.46 2.51 2.41 2.45 2.49 2.53 2.46 2.47 2.52 2.55
LDB 42.4 46.8 52.1 57.4 48.4 51.3 56.5 61.7 53.3 54.7 59.5 64.6
LWB 39.8 45.1 50.8 56.7 43.0 48.8 54.5 60.4 45.4 51.4 56.9 62.8
85
TCG 27.8 30.2 32.9 35.2 30.5 31.9 34.4 36.5 32.5 33.1 35.5 37.0
SHG 27.8 24.8 21.1 17.1 30.5 28.2 23.4 18.4 32.5 31.4 25.6 19.4
TC 27.4 29.8 32.5 34.8 30.0 31.4 33.9 36.0 31.8 32.5 34.9 36.3
kW 2.89 2.96 3.02 3.07 3.00 3.04 3.09 3.14 3.08 3.10 3.16 3.19
CMP 2.61 2.68 2.75 2.80 2.69 2.73 2.78 2.83 2.74 2.76 2.82 2.84
LDB 43.4 47.3 52.3 57.6 49.1 51.4 56.4 61.5 53.7 54.6 59.3 64.5
LWB 40.4 45.7 51.1 56.8 43.3 49.1 54.6 60.3 45.6 51.6 57.0 62.8
95
TCG 26.2 28.2 31.1 33.7 28.7 29.8 32.6 35.0 30.8 31.2 33.6 35.8
SHG 26.2 23.6 20.2 16.5 28.7 26.9 22.5 17.8 30.8 30.1 24.8 19.0
TC 25.8 27.9 30.7 33.3 28.2 29.3 32.1 34.5 30.2 30.6 33.0 35.2
kW 3.17 3.24 3.34 3.41 3.29 3.33 3.41 3.47 3.40 3.41 3.47 3.54
CMP 2.90 2.97 3.07 3.14 2.98 3.02 3.11 3.17 3.06 3.07 3.13 3.20
LDB 44.6 48.1 52.8 57.9 50.1 52.0 56.7 61.7 54.4 55.0 59.5 64.4
LWB 41.0 46.5 51.6 57.2 43.8 49.7 55.0 60.6 46.0 52.0 57.3 62.9
105
TCG 24.6 26.3 29.0 31.9 26.9 27.8 30.5 33.1 28.8 29.0 31.6 34.0
SHG 24.6 22.4 19.1 15.7 26.9 25.6 21.5 17.0 28.8 28.6 23.8 18.3
TC 24.3 25.9 28.6 31.5 26.5 27.3 30.1 32.6 28.3 28.4 31.0 33.4
kW 3.48 3.54 3.65 3.78 3.60 3.63 3.75 3.83 3.71 3.72 3.82 3.90
CMP 3.21 3.27 3.38 3.51 3.30 3.33 3.44 3.53 3.37 3.38 3.49 3.56
LDB 45.8 48.9 53.6 58.5 51.2 52.7 57.2 62.0 55.4 55.7 59.8 64.6
LWB 41.7 47.3 52.4 57.7 44.4 50.3 55.5 60.9 46.4 52.5 57.7 63.1
115
TCG 23.1 24.4 26.9 29.6 25.2 25.7 28.3 31.0 26.9 27.0 29.2 31.9
SHG 23.1 21.3 18.0 14.7 25.2 24.3 20.3 16.1 26.9 26.9 22.6 17.5
TC 22.7 24.0 26.5 29.3 24.7 25.3 27.8 30.5 26.4 26.4 28.7 31.3
kW 3.81 3.87 3.98 4.11 3.93 3.96 4.08 4.21 4.05 4.05 4.16 4.28
CMP 3.54 3.60 3.71 3.85 3.63 3.66 3.78 3.91 3.72 3.72 3.83 3.95
LDB 47.2 49.8 54.5 59.3 52.4 53.4 57.8 62.5 56.5 56.5 60.3 64.9
LWB 42.4 48.1 53.2 58.4 45.0 51.0 56.2 61.4 46.9 53.0 58.2 63.5
125
TCG 21.5 22.5 24.8 27.3 23.5 23.7 26.0 28.6 25.0 25.0 26.8 29.6
SHG 21.5 20.1 17.0 13.7 23.5 23.0 19.2 15.2 25.0 25.0 21.4 16.6
TC 21.1 22.1 24.5 27.0 23.0 23.2 25.6 28.2 24.5 24.4 26.3 29.0
kW 4.15 4.20 4.33 4.47 4.28 4.30 4.42 4.60 4.40 4.40 4.51 4.68
CMP 3.88 3.94 4.06 4.21 3.99 4.00 4.13 4.30 4.07 4.07 4.18 4.35
LDB 48.6 50.6 55.3 60.1 53.6 54.1 58.5 63.1 57.5 57.5 60.9 65.3
LWB 43.1 48.9 54.1 59.3 45.6 51.6 56.8 62.0 47.4 53.4 58.8 63.9
Rating condition.
Not recommended for long-term operation.
LEGEND
BF — Bypass Factor
CMP — Compressor
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW — Total Power
LDB — Leaving Dry Bulb
LWB — Leaving Wet Bulb
SHG — Gross Sensible Capacity (1000 Btuh)
TC — Total Net Cooling Capacity (1000 Btuh)
TCG — Gross Cooling Capacity (1000 Btuh)
*Refer to Systems Index Table on page 26.
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHG is based on 80 F edb temperature of air entering indoor
coil.
Below 80 F edb, subtract (corr factor x cfm) from SHG.
Above 80 F edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).