Specifications

PERFORMANCE DATA (cont)
COOLING CAPACITIES (cont)
SYSTEM 9* CEILING-SUSPENDED SYSTEM (538B036 3-PHASE UNIT WITH 619C036)
TEMP (F)
AIR ENTERING
OUTDOOR UNIT
(Edb)
AIR ENTERING INDOOR UNIT CFM/BF
630/0.03 750/0.04 870/0.05
Air Entering Indoor Unit Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
55
TCG 40.4 43.0 43.2 43.8 41.9 43.7 44.7 41.3 43.2 43.1 43.9 39.3
SHG 37.7 32.6 26.4 21.1 40.9 34.2 27.8 20.2 43.2 34.8 27.8 19.4
TC 39.9 42.4 42.7 43.3 41.2 43.0 44.0 40.7 42.4 42.3 43.1 38.5
kW 2.05 1.97 1.93 1.96 2.01 2.00 2.03 1.89 2.04 1.99 2.01 1.85
CMP 1.70 1.63 1.59 1.61 1.64 1.63 1.66 1.52 1.65 1.60 1.62 1.45
LDB 34.4 40.8 48.6 55.1 38.6 45.7 52.3 60.3 42.4 50.2 56.4 64.0
LWB 33.6 39.6 47.3 54.6 37.2 43.6 50.4 59.0 39.9 46.9 53.4 61.7
65
TCG 37.3 40.0 41.3 42.5 38.9 41.0 42.5 41.2 40.4 41.0 42.3 39.9
SHG 35.2 30.7 25.4 20.4 38.2 32.6 26.7 20.1 40.4 33.7 27.2 19.8
TC 36.7 39.5 40.7 41.9 38.2 40.3 41.9 40.5 39.6 40.2 41.5 39.2
kW 2.34 2.33 2.34 2.37 2.35 2.37 2.41 2.35 2.40 2.38 2.42 2.33
CMP 1.98 1.97 1.97 2.01 1.96 1.98 2.02 1.96 1.99 1.97 2.01 1.92
LDB 35.8 41.5 48.4 54.7 39.7 45.8 52.1 59.3 43.4 49.7 55.7 62.6
LWB 34.8 40.4 47.3 54.2 38.1 44.1 50.5 58.2 40.4 47.0 53.3 60.8
75
TCG 34.1 37.0 39.3 41.2 35.9 38.3 40.4 41.0 37.6 38.9 40.7 40.6
SHG 32.7 28.8 24.3 19.8 35.5 31.0 25.7 20.0 37.6 32.6 26.6 20.1
TC 33.5 36.5 38.8 40.6 35.2 37.7 39.8 40.4 36.9 38.1 40.0 39.8
kW 2.63 2.69 2.74 2.79 2.68 2.74 2.79 2.81 2.76 2.77 2.83 2.82
CMP 2.25 2.30 2.36 2.41 2.28 2.33 2.39 2.40 2.33 2.34 2.39 2.39
LDB 37.1 42.2 48.3 54.3 40.9 46.0 51.9 58.3 44.4 49.2 55.0 61.3
LWB 36.0 41.3 47.4 53.8 38.9 44.6 50.6 57.3 40.9 47.1 53.1 59.8
85
TCG 30.9 34.1 37.4 39.8 32.8 35.6 38.3 40.9 34.8 36.8 39.2 41.2
SHG 30.1 26.9 23.2 19.1 32.8 29.3 24.6 19.9 34.8 31.6 26.0 20.5
TC 30.4 33.6 36.9 39.3 32.2 35.0 37.7 40.3 34.1 36.1 38.5 40.5
kW 2.92 3.05 3.15 3.21 3.02 3.11 3.18 3.27 3.12 3.17 3.23 3.30
CMP 2.52 2.64 2.74 2.81 2.59 2.68 2.75 2.85 2.67 2.71 2.78 2.85
LDB 38.5 43.0 48.1 54.0 42.0 46.2 51.7 57.2 45.3 48.6 54.3 59.9
LWB 37.2 42.2 47.4 53.5 39.7 45.1 50.7 56.5 41.4 47.2 52.9 58.9
95
TCG 27.8 30.7 34.0 37.1 29.8 32.2 35.5 38.4 31.6 33.4 36.7 39.3
SHG 27.6 24.7 21.4 17.8 29.8 27.2 23.1 18.8 31.6 29.4 24.8 19.7
TC 27.4 30.2 33.6 36.6 29.3 31.6 34.9 37.8 31.0 32.7 36.0 38.6
kW 3.23 3.36 3.52 3.63 3.35 3.46 3.60 3.71 3.46 3.55 3.67 3.77
CMP 2.81 2.94 3.10 3.21 2.90 3.02 3.15 3.26 2.99 3.07 3.20 3.29
LDB 39.9 44.2 49.0 54.4 43.7 47.0 52.0 57.4 46.9 49.2 54.2 59.7
LWB 38.4 43.4 48.4 53.9 40.6 46.0 51.1 56.7 42.2 48.0 53.2 58.8
105
TCG 25.0 27.4 30.5 33.8 26.9 28.8 31.9 35.1 28.6 29.8 33.0 36.0
SHG 25.0 22.6 19.5 16.3 26.9 24.9 21.2 17.3 28.6 27.0 22.8 18.2
TC 24.5 27.0 30.1 33.4 26.4 28.2 31.4 34.6 27.9 29.2 32.4 35.4
kW 3.56 3.70 3.88 4.07 3.70 3.81 3.99 4.15 3.82 3.89 4.08 4.22
CMP 3.12 3.26 3.44 3.63 3.23 3.34 3.52 3.68 3.33 3.40 3.58 3.72
LDB 41.7 45.5 50.3 55.2 45.4 48.1 52.9 58.0 48.4 50.2 54.9 60.1
LWB 39.5 44.6 49.6 54.7 41.5 47.0 52.1 57.3 43.0 48.9 54.0 59.3
115
TCG 22.4 24.3 27.1 30.1 24.1 25.4 28.3 31.4 25.6 26.4 29.2 32.4
SHG 22.4 20.5 17.6 14.7 24.1 22.6 19.2 15.7 25.6 24.6 20.7 16.7
TC 22.0 23.9 26.7 29.7 23.6 24.9 27.8 30.9 25.0 25.8 28.6 31.8
kW 3.93 4.06 4.25 4.46 4.08 4.17 4.36 4.58 4.20 4.26 4.46 4.68
CMP 3.47 3.60 3.79 4.00 3.59 3.68 3.88 4.09 3.69 3.74 3.94 4.16
LDB 43.7 46.8 51.5 56.4 47.2 49.3 54.0 58.9 50.1 51.3 55.9 60.8
LWB 40.6 45.9 50.8 55.9 42.4 48.1 53.1 58.2 43.8 49.8 54.9 60.0
125
TCG 19.9 21.2 23.8 26.5 21.4 22.3 24.8 27.6 22.7 23.0 25.5 28.4
SHG 19.9 18.5 15.9 13.1 21.4 20.5 17.3 14.0 22.7 22.2 18.7 14.9
TC 19.5 20.8 23.4 26.1 20.9 21.8 24.3 27.1 22.1 22.5 25.0 27.8
kW 4.31 4.42 4.64 4.87 4.46 4.54 4.75 4.99 4.60 4.64 4.85 5.09
CMP 3.83 3.95 4.16 4.39 3.96 4.03 4.25 4.48 4.06 4.10 4.31 4.55
LDB 45.7 48.1 52.8 57.7 49.0 50.4 55.1 59.9 51.8 52.4 56.8 61.7
LWB 41.6 47.2 52.0 57.1 43.3 49.2 54.2 59.2 44.7 50.8 55.8 60.9
Rating condition.
Not recommended for long-term operation.
LEGEND
BF Bypass Factor
CMP Compressor
Edb Entering Dry Bulb
Ewb Entering Wet Bulb
kW Total Power
LDB Leaving Dry Bulb
LWB Leaving Wet Bulb
SHG Gross Sensible Capacity (1000 Btuh)
TC Total Net Cooling Capacity (1000 Btuh)
TCG Gross Cooling Capacity (1000 Btuh)
*Refer to Systems Index Table on page 26.
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHG is based on 80 F edb temperature of air entering indoor
coil.
Below 80 F edb, subtract (corr factor x cfm) from SHG.
Above 80 F edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 BF) x (edb 80).
35