Specifications

PERFORMANCE DATA (cont)
COOLING CAPACITIES (cont)
SYSTEM 5* CEILING-SUSPENDED SYSTEM (538B018 WITH 619C024)
TEMP (F)
AIR ENTERING
OUTDOOR UNIT
(Edb)
AIR ENTERING INDOOR UNIT CFM/BF
320/0.01 400/0.02 480/0.02
Air Entering Indoor Unit Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
55
TCG 36.5 40.6 44.6 47.2 38.9 42.7 46.4 49.2 41.3 44.9 48.2 51.1
SHG 33.6 30.1 26.6 22.2 37.4 33.3 28.6 23.4 41.2 36.5 30.7 24.7
TC 35.9 40.1 44.1 46.7 38.2 42.1 45.7 48.5 40.5 44.1 47.4 50.3
kW 2.67 2.74 2.79 2.82 2.75 2.81 2.86 2.90 2.83 2.88 2.93 2.98
CMP 2.17 2.25 2.29 2.33 2.22 2.28 2.32 2.36 2.26 2.31 2.35 2.40
LDB 33.1 38.1 43.4 49.8 36.7 41.5 47.0 53.2 40.3 44.9 50.7 56.5
LWB 32.9 37.7 43.0 49.5 35.8 40.9 46.4 52.6 38.7 44.0 49.7 55.8
65
TCG 30.3 34.0 37.5 40.3 32.5 35.8 39.1 42.0 34.7 37.6 40.8 43.7
SHG 28.8 25.5 22.5 18.9 31.7 28.3 24.4 20.1 34.7 31.1 26.3 21.3
TC 29.8 33.5 37.0 39.9 31.9 35.2 38.5 41.4 34.0 36.9 40.1 43.0
kW 2.47 2.55 2.61 2.66 2.55 2.62 2.68 2.73 2.63 2.69 2.74 2.80
CMP 2.04 2.12 2.18 2.23 2.09 2.15 2.21 2.27 2.13 2.19 2.24 2.30
LDB 34.2 39.5 44.6 50.5 38.0 42.7 47.9 53.7 41.9 45.8 51.3 56.9
LWB 34.4 39.1 44.2 50.1 37.0 42.0 47.3 53.1 39.6 45.0 50.4 56.2
75
TCG 24.1 27.3 30.4 33.5 26.2 28.8 31.9 34.9 28.2 30.3 33.3 36.3
SHG 23.9 20.8 18.3 15.7 26.1 23.2 20.1 16.7 28.2 25.7 21.9 17.8
TC 23.7 26.9 30.0 33.1 25.7 28.3 31.4 34.4 27.6 29.7 32.7 35.7
kW 2.27 2.35 2.44 2.50 2.35 2.42 2.50 2.56 2.44 2.49 2.56 2.63
CMP 1.91 1.99 2.07 2.13 1.96 2.03 2.10 2.17 2.01 2.07 2.13 2.20
LDB 35.3 41.0 45.8 51.2 39.4 43.9 48.8 54.2 43.5 46.8 51.8 57.2
LWB 35.9 40.4 45.4 50.7 38.2 43.2 48.3 53.7 40.5 46.0 51.1 56.6
85
TCG 19.0 21.4 23.8 26.4 20.6 22.5 24.9 27.6 22.2 23.6 26.1 28.7
SHG 19.0 16.5 14.5 12.4 20.6 18.5 16.0 13.3 22.2 20.5 17.5 14.2
TC 18.6 21.1 23.4 26.1 20.2 22.1 24.5 27.1 21.7 23.1 25.6 28.2
kW 1.99 2.07 2.15 2.23 2.07 2.13 2.21 2.28 2.15 2.19 2.27 2.33
CMP 1.69 1.77 1.85 1.93 1.75 1.81 1.88 1.95 1.80 1.84 1.92 1.98
LDB 37.1 42.4 47.3 52.4 41.2 45.1 50.1 55.2 45.2 47.8 52.8 58.0
LWB 37.1 41.8 46.8 51.9 39.2 44.4 49.4 54.6 41.3 47.0 52.1 57.4
95
TCG 14.3 15.9 17.7 19.7 15.5 16.7 18.6 20.6 16.7 17.5 19.4 21.5
SHG 14.3 12.6 11.0 9.29 15.5 14.1 12.1 10.0 16.7 15.7 13.3 10.8
TC 14.0 15.6 17.5 19.4 15.2 16.4 18.2 20.3 16.3 17.1 19.0 21.1
kW 1.67 1.73 1.80 1.87 1.74 1.78 1.85 1.92 1.80 1.83 1.90 1.97
CMP 1.43 1.50 1.56 1.63 1.48 1.53 1.59 1.66 1.53 1.56 1.62 1.69
LDB 39.1 43.8 48.7 53.8 43.0 46.3 51.3 56.3 46.8 48.9 53.8 58.9
LWB 38.2 43.3 48.1 53.2 40.2 45.7 50.6 55.8 42.2 48.0 53.1 58.3
105
TCG 9.95 10.9 12.2 13.6 10.8 11.5 12.8 14.2 11.6 12.0 13.3 14.8
SHG 9.95 8.86 7.68 6.47 10.8 9.98 8.51 7.01 11.6 11.1 9.35 7.54
TC 9.75 10.7 12.0 13.4 10.5 11.2 12.5 14.0 11.3 11.7 13.0 14.5
kW 1.29 1.34 1.39 1.45 1.34 1.37 1.43 1.49 1.39 1.41 1.47 1.53
CMP 1.12 1.16 1.22 1.28 1.16 1.19 1.24 1.30 1.19 1.21 1.27 1.32
LDB 41.3 45.2 50.1 55.1 44.9 47.6 52.5 57.5 48.6 50.0 54.9 59.9
LWB 39.3 44.6 49.5 54.6 41.2 46.9 51.8 56.9 43.1 49.1 54.2 59.2
115
TCG 5.98 6.47 7.28 8.12 6.47 6.79 7.58 8.44 6.97 7.11 7.88 8.76
SHG 5.98 5.41 4.66 3.90 6.47 6.10 5.18 4.23 6.97 6.78 5.71 4.56
TC 5.85 6.35 7.16 7.99 6.32 6.63 7.43 8.28 6.78 6.92 7.70 8.58
kW 0.860 0.886 0.925 0.966 0.894 0.911 0.950 0.991 0.929 0.936 0.974 1.02
CMP 0.750 0.776 0.815 0.856 0.775 0.792 0.831 0.872 0.801 0.808 0.846 0.888
LDB 43.4 46.5 51.4 56.4 46.9 48.9 53.7 58.7 50.4 51.2 55.9 60.9
LWB 40.5 46.0 50.8 55.9 42.2 48.1 53.0 58.1 44.0 50.1 55.2 60.2
125
TCG 2.37 2.53 2.88 3.22 2.58 2.66 2.99 3.34 2.78 2.80 3.10 3.46
SHG 2.37 2.21 1.89 1.57 2.58 2.49 2.11 1.71 2.78 2.77 2.33 1.85
TC 2.32 2.47 2.83 3.17 2.51 2.60 2.93 3.28 2.70 2.72 3.03 3.38
kW 0.378 0.386 0.405 0.424 0.393 0.397 0.415 0.434 0.408 0.408 0.426 0.445
CMP 0.332 0.340 0.359 0.378 0.343 0.347 0.365 0.384 0.354 0.355 0.372 0.391
LDB 46.0 48.0 52.8 57.7 49.1 50.2 54.9 59.8 52.3 52.4 56.9 61.9
LWB 41.8 47.6 52.2 57.2 43.4 49.3 54.2 59.2 44.9 51.1 56.2 61.2
Rating condition.
Not recommended for long-term operation.
LEGEND
BF Bypass Factor
CMP Compressor
Edb Entering Dry Bulb
Ewb Entering Wet Bulb
kW Total Power
LDB Leaving Dry Bulb
LWB Leaving Wet Bulb
SHG Gross Sensible Capacity (1000 Btuh)
TC Total Net Cooling Capacity (1000 Btuh)
TCG Gross Cooling Capacity (1000 Btuh)
*Refer to Systems Index Table on page 26.
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHG is based on 80 F edb temperature of air entering indoor
coil.
Below 80 F edb, subtract (corr factor x cfm) from SHG.
Above 80 F edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 BF) x (edb 80).
31