PERFORMANCE DATA (cont)
COOLING CAPACITIES (cont)
SYSTEM 2* — HIGH WALL SYSTEM (538D012 WITH 619E012)
TEMP (F)
AIR ENTERING
OUTDOOR UNIT
(Edb)
AIR ENTERING INDOOR UNIT — CFM/BF
245/0.12 280/0.14 302/0.15
Air Entering Indoor Unit — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
55
TCG 11.1 11.7 12.4 12.8 11.5 12.0 12.6 12.8 11.8 12.1 12.7 12.7
SHG 10.5 8.95 7.61 6.21 11.2 9.36 7.79 6.23 11.6 9.57 7.92 6.24
TC 11.1 11.6 12.3 12.7 11.5 11.9 12.5 12.7 11.7 12.0 12.6 12.6
kW 0.76 0.77 0.78 0.78 0.77 0.77 0.78 0.78 0.78 0.78 0.79 0.79
CMP 0.66 0.67 0.68 0.69 0.67 0.67 0.68 0.68 0.67 0.67 0.68 0.68
LDB 39.8 45.7 50.9 56.3 42.5 48.6 54.0 59.2 44.1 50.3 55.5 60.7
LWB 37.1 43.2 49.2 55.8 39.3 45.5 51.6 58.2 40.4 46.7 52.8 59.4
65
TCG 10.9 11.6 12.4 13.1 11.3 11.9 12.7 13.2 11.5 12.0 12.8 13.2
SHG 10.4 8.99 7.65 6.31 11.1 9.38 7.92 6.43 11.4 9.65 8.08 6.46
TC 10.8 11.5 12.3 13.0 11.2 11.8 12.6 13.2 11.4 11.9 12.7 13.1
kW 0.84 0.85 0.86 0.87 0.85 0.86 0.87 0.88 0.86 0.86 0.88 0.88
CMP 0.75 0.75 0.77 0.78 0.75 0.76 0.77 0.78 0.76 0.76 0.77 0.78
LDB 40.1 45.6 50.7 55.9 42.9 48.6 53.5 58.6 44.4 50.0 55.0 60.1
LWB 37.6 43.4 49.2 55.4 39.8 45.7 51.5 57.6 40.8 46.9 52.6 58.9
75
TCG 10.6 11.4 12.2 13.1 11.0 11.7 12.6 13.3 11.3 11.9 12.7 13.4
SHG 10.2 8.92 7.59 6.30 10.9 9.39 7.93 6.46 11.3 9.69 8.11 6.55
TC 10.5 11.3 12.2 13.0 10.9 11.6 12.5 13.2 11.2 11.8 12.6 13.3
kW 0.94 0.95 0.96 0.98 0.95 0.95 0.97 0.99 0.95 0.96 0.97 0.99
CMP 0.84 0.85 0.86 0.88 0.85 0.85 0.87 0.89 0.85 0.86 0.87 0.89
LDB 40.7 45.8 51.0 55.9 43.3 48.5 53.5 58.4 44.9 49.9 54.9 59.8
LWB 38.3 43.8 49.5 55.4 40.2 46.0 51.6 57.5 41.2 47.1 52.8 58.6
85
TCG 9.83 11.1 12.0 12.8 10.6 11.4 12.3 13.1 11.0 11.6 12.4 13.2
SHG 9.78 8.83 7.48 6.17 10.6 9.31 7.85 6.36 11.0 9.62 8.06 6.46
TC 9.74 11.0 11.9 12.7 10.5 11.3 12.2 13.0 10.9 11.5 12.3 13.1
kW 1.04 1.05 1.07 1.08 1.05 1.06 1.08 1.09 1.06 1.07 1.08 1.10
CMP 0.94 0.96 0.97 0.99 0.95 0.96 0.98 0.99 0.95 0.96 0.98 1.00
LDB 42.5 46.2 51.4 56.5 44.6 48.8 53.8 58.8 45.9 50.1 55.0 60.0
LWB 39.9 44.4 50.0 55.8 41.0 46.5 52.0 57.9 41.7 47.5 53.1 58.9
95
TCG 9.43 10.5 11.7 12.5 10.0 10.9 11.9 12.7 10.4 11.2 12.1 12.9
SHG 9.43 8.52 7.36 6.02 10.0 9.12 7.72 6.23 10.4 9.49 7.95 6.34
TC 9.35 10.4 11.6 12.4 9.91 10.8 11.8 12.6 10.3 11.1 12.0 12.8
kW 1.15 1.16 1.19 1.20 1.16 1.18 1.19 1.21 1.17 1.18 1.20 1.21
CMP 1.05 1.07 1.09 1.10 1.06 1.08 1.09 1.11 1.07 1.08 1.10 1.11
LDB 43.9 47.4 51.8 57.1 46.5 49.4 54.2 59.2 47.6 50.6 55.4 60.4
LWB 40.7 45.5 50.5 56.3 42.0 47.2 52.5 58.3 42.6 48.1 53.5 59.3
105
TCG 8.97 9.81 11.2 12.1 9.45 10.2 11.5 12.3 9.83 10.4 11.7 12.5
SHG 8.97 8.17 7.18 5.85 9.45 8.78 7.56 6.07 9.83 9.15 7.79 6.19
TC 8.89 9.73 11.1 12.0 9.35 10.1 11.4 12.2 9.73 10.3 11.6 12.4
kW 1.27 1.29 1.31 1.33 1.29 1.30 1.32 1.34 1.30 1.31 1.33 1.35
CMP 1.18 1.19 1.22 1.23 1.19 1.20 1.22 1.24 1.19 1.20 1.23 1.24
LDB 45.6 48.7 52.6 57.7 48.4 50.6 54.7 59.8 49.5 51.6 55.9 60.9
LWB 41.6 46.8 51.2 56.9 43.0 48.3 53.1 58.8 43.5 49.1 54.1 59.7
115
TCG 8.70 9.09 10.4 11.7 9.06 9.47 10.9 11.9 9.23 9.68 11.1 12.0
SHG 8.70 7.82 6.83 5.69 9.06 8.44 7.29 5.90 9.23 8.80 7.56 6.03
TC 8.62 9.01 10.4 11.6 8.96 9.38 10.8 11.8 9.13 9.58 11.0 11.9
kW 1.41 1.42 1.45 1.48 1.42 1.43 1.46 1.48 1.43 1.44 1.47 1.49
CMP 1.31 1.32 1.35 1.38 1.32 1.33 1.36 1.38 1.33 1.34 1.37 1.39
LDB 46.7 50.1 53.9 58.3 49.7 51.8 55.6 60.4 51.4 52.7 56.6 61.4
LWB 42.1 48.1 52.5 57.5 43.6 49.4 54.0 59.3 44.5 50.2 54.8 60.3
125
TCG 8.18 8.32 9.73 11.2 8.50 8.69 10.1 11.4 8.64 8.88 10.3 11.6
SHG 8.18 7.48 6.52 5.50 8.50 8.08 6.98 5.73 8.64 8.43 7.25 5.87
TC 8.09 8.24 9.65 11.1 8.41 8.60 10.0 11.3 8.54 8.78 10.2 11.5
kW 1.56 1.57 1.60 1.63 1.57 1.58 1.61 1.64 1.58 1.59 1.62 1.65
CMP 1.46 1.47 1.50 1.54 1.47 1.48 1.51 1.54 1.48 1.48 1.52 1.55
LDB 48.7 51.4 55.1 59.0 51.5 53.0 56.7 60.9 53.2 53.9 57.6 61.9
LWB 43.2 49.4 53.7 58.2 44.6 50.6 55.0 59.9 45.4 51.3 55.7 60.8
Rating condition.
Not recommended for long-term operation.
LEGEND
BF — Bypass Factor
CMP — Compressor
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW — Total Power
LDB — Leaving Dry Bulb
LWB — Leaving Wet Bulb
SHG — Gross Sensible Capacity (1000 Btuh)
TC — Total Net Cooling Capacity (1000 Btuh)
TCG — Gross Cooling Capacity (1000 Btuh)
*Refer to Systems Index Table on page 26.
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHG is based on 80 F edb temperature of air entering indoor
coil.
Below 80 F edb, subtract (corr factor x cfm) from SHG.
Above 80 F edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).
28