Table 29 – COOLING CAPACITIES 2--STAGE COOLING (RTPF ONLY) 10 TONS
580J12 COOLING CAPACITIES, UNIT WITH PERFECT HUMIDITY SYSTEM IN SUBCOOLING MODE
TEMP (F) AIR ENT
CONDENSER (Edb)
AIR ENTERING EVAPORATOR --- CFM
3000/0.04 4000/0.06 5000/0.07
A i r E n t e r i n g E v a p o r a t o r --- E w b ( F )
72 67 62 72 67 62 72 67 62
75
TC 142.85 129.44 116.93 152.09 138.44 125.76 157.99 144.23 132.06
SHC 58.38 74.88 91.58 67.96 89.45 111.02 76.63 102.94 127.93
kW 7.19 6.97 6.79 6.92 7.12 7.35 7.45 7.22 7.02
85
TC 132.33 119.68 107.86 140.92 128.03 116.10 146.41 133.41 121.98
SHC 48.44 65.56 82.83 57.37 79.50 101.68 65.65 92.58 118.12
kW 7.98 7.77 7.58 7.72 7.92 8.14 8.25 8.01 7.82
95
TC 121.41 109.52 98.43 129.35 117.22 106.04 134.43 122.20 111.50
SHC 38.19 55.92 73.78 46.47 69.22 92.01 54.34 81.92 107.96
kW 8.87 8.66 8.48 8.61 8.80 9.03 9.14 8.90 8.71
105
TC 110.04 98.92 88.56 117.27 105.94 95.53 121.88 110.46 100.54
SHC 27.59 45.94 64.39 35.16 58.57 81.98 42.56 70.82 97.40
kW 9.86 9.66 9.48 9.61 9.79 10.02 10.12 9.89 9.70
115
TC 98.09 87.74 78.13 104.62 94.08 84.45 108.76 98.13 89.01
SHC 16.52 35.47 54.53 23.37 47.44 71.46 30.32 59.25 86.31
kW 10.95 10.76 10.60 10.72 10.89 11.10 11.19 10.98 10.81
580J12 COOLING CAPACITIES, UNIT WITH PERFECT HUMIDITY SYSTEM IN HOT GAS REHEAT MODE
TEMP (F) AIR ENT
CONDENSER (Edb)
AIR ENTERING EVAPORATOR --- Ewb (F)
75 Dry Bulb
62.5 Wet Bulb
(50% Relative)
75 Dry Bulb
64 Wet Bulb
(56% Relative)
75 Dry Bulb
65.3 Wet Bulb
(60% Relative)
A i r E n t e r i n g E v a p o r a t o r --- C f m
3000 4000 5000 3000 4000 5000 3000 4000 5000
80
TC 44.78 39.41 31.89 53.22 49.44 43.38 60.56 58.12 53.32
SHC ---0.44 --- 0.57 --- 0.69 --- 0.37 --- 0.51 --- 0.61 --- 0.33 --- 0.46 --- 0.56
kW 6.96 6.77 6.52 7.26 7.13 6.91 7.54 7.45 7.27
75
TC 45.84 40.46 32.86 54.28 50.51 44.45 61.61 59.19 54.40
SHC 0.53 0.40 0.29 0.60 0.47 0.37 0.64 0.52 0.42
kW 6.77 6.56 6.29 7.11 6.95 6.72 7.41 7.31 7.12
70
TC 46.91 41.48 33.50 55.36 51.59 45.50 62.69 60.28 55.49
SHC 1.51 1.38 1.27 1.57 1.45 1.35 1.61 1.50 1.40
kW 6.54 6.32 6.02 6.90 6.74 6.49 7.23 7.13 6.92
60
TC 48.88 43.42 35.76 57.29 53.56 47.48 64.56 62.16 57.42
SHC 3.44 3.34 3.24 3.51 3.40 3.31 3.55 3.45 3.37
kW 6.45 6.16 6.70 6.93 6.72 6.39 7.38 7.24 6.96
50
TC 50.83 45.28 37.67 59.22 55.52 49.43 66.05 64.03 59.34
SHC 5.38 5.29 5.20 5.45 5.36 5.28 5.48 5.40 5.33
kW 6.46 6.01 6.34 6.98 6.71 6.29 8.15 7.38 7.02
40
TC 52.82 47.29 39.50 61.14 57.48 51.39 68.23 65.88 61.25
SHC 7.32 7.24 7.20 7.38 7.31 7.24 7.43 7.36 7.29
kW 6.29 6.09 6.12 7.05 6.72 6.29 7.78 7.55 7.10
NOTE: Perfect Humidity only available on 2---stage RTPF models.
LEGEND
Edb --- E n t e r i n g D r y --- B u l b
Ewb --- E n t e r i n g W e t --- B u l b
kW --- Compressor Motor Power Input
Idb --- L e a v i n g D r y --- B u l b
Iwb --- L e a v i n g W e t --- B u l b
SHC --- Sensible Heat Capacity (1000 Btuh) Gross
TC --- Total Capacity (1000 Btuh) Gross
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may b e used:
t
ldb
=t
edb
–
sensible capacity (Btuh)
1.10 x cfm
t
lwb
= Wet---bulb temperature corresponding to enthalpy of air
leaving evaporator coil (h
lwb
)
h
lwb
=h
ewb
–
total capacity (Btuh)
4.5 x cfm
Where: h
ewb
= Enthalpy of air entering evaporator coil
580J