Gas Heater User Manual

16
Table 12 – PHYSICAL DATA (HEATING) 7.5 -- 12.5 TONS
580J*08 580J*09 580J*12 580J*14
Gas Connection
#ofGasValves 1 1 1 1
Nat. gas supply line press (in. w.g.)/(PSIG) 4 --- 1 3 / 0 . 1 8 --- 0 . 4 7 4 --- 1 3 / 0 . 1 8 --- 0 . 4 7 4 --- 1 3 / 0 . 1 8 --- 0 . 4 7 4 --- 1 3 / 0 . 1 8 --- 0 . 4 7
Propane supply line press (in. w.g.)/(PSIG) 11 ---13 / 0.40 --- 0.47 11 ---13 / 0.40 --- 0.47 11 ---13 / 0.40 --- 0.47 11 ---13 / 0.40 --- 0.47
Heat Anticipator Setting (Amps)
1st stage 0.14 0.14 0.14 0.14
2nd stage 0.14 0.14 0.14 0.14
Natural Gas, Propane Heat
#ofstages/#ofburners(total) 1/3 1/3 2/4 2/4
LOW
Connection size 1 / 2 --- i n N P T 1 / 2 --- i n N P T 3 / 4 --- i n N P T 3 / 4 --- i n N P T
Rollout switch opens / closes 195 / 115 195 / 115 195 / 115 195 / 115
Temperatureriserange(F) 20 --- 50 20 --- 50 25 --- 65 25 --- 65
#ofstages/#ofburners(total) 2/4 2/4 2/5 2/5
MED
Connection size 3 / 4 --- i n N P T 3 / 4 --- i n N P T 3 / 4 --- i n N P T 3 / 4 --- i n N P T
Rollout switch opens / closes 195 / 115 195 / 115 195 / 115 195 / 115
Temperatureriserange(F) 35 --- 65 30 --- 65 30 --- 65 25 --- 65
#ofstages/#ofburners(total) 2/5 2/5 2/5 2/5
HIGH
Connection size 3 / 4 --- i n N P T 3 / 4 --- i n N P T 3 / 4 --- i n N P T 3 / 4 --- i n N P T
Rollout switch opens / closes 195 / 115 195 / 115 195 / 115 195 / 115
Temperatureriserange(F) 45 --- 75 40 --- 75 35 --- 70 35 --- 70
580J