Installation manual

ATC32U01A Communicating, Programmable Thermostat - IOM
Created: 1 Oct., 2012
10
4.0 Accessory Con guration
A service message will ash at the top of the Main screen
when a service timer expires to alert the user that it is time to
service these options. Refer to DXM2 AOM for instructions on
con guring DIP switches to con gure accessories. Follow the
instructions below to set service timers.
4.1 AIR FILTER
This feature displays an alert to remind the user to change
the air lter after the selected time has passed.
Adjust the Air Filter Reminder settings using the up/down
arrow buttons. Press the center button to save changes.
Cumulative Run Time (default Off) – valid range:
Off, 400 to 3600 hours (in 100 hour increments)
Calendar Time (default Off) – valid range: Off, 3
to 48 months (in 3 month increments)
4.2 HUMIDIFIER
This feature displays an alert to remind the user to change
the humidi er pad after the selected time has passed.
Adjust the Humidi er Reminder settings using the up/down
arrow buttons. Press the center button to save changes.
Cumulative Run Time (default Off) – valid range:
Off, 400 to 3600 hours (in 100 hour increments)
Calendar Time (default Off) – valid range: Off, 3
to 24 months (in 3 month increments)
4.3 UV LAMP
This feature displays an alert to remind the user to change
the UV lamps after the selected time has passed.
Adjust the UV Lamp Reminder settings using the up/down
arrow buttons. Press the center button to save changes.
Cumulative Run Time (default Off) – valid range:
Off, 400 to 3600 hours (in 100 hour increments)
Calendar Time (default Off) – valid range: Off, 3
to 48 months (in 3 month increments)
4.4 AIR CLEANER
This feature displays an alert to remind the user to clean the
lter(s) after the selected time has passed.
INSTALLER SETTINGS
THERMOSTAT CONFIG
SYSTEM CONFIG
ACCESSORY CONFIG
INPUT DEALER INFO
HUMIDITY CONFIG
TEMPERATURE ALGORITHM
DEMAND REDUCTION CNFG
SERVICE MODE
RESTORY DEFAULTS
ATC32U01
SELECT OPTION
PREVIOUS
3.6.1 MULTI-UNIT AIRFLOW SELECTION
In section 3.1, when an installer selects “Air ow
Selection” from the System Con guration menu,
the installer may choose the unit to con gure
by the last 4 digits of its serial number from the
following screen.
3.6.2 MULTI-UNIT OPTION SELECTION
In section 3.2, when an installer selects “Option
Selection” from the System Con guration menu,
the installer may choose the unit to con gure
by the last 4 digits of its serial number from the
following screen.
3.6.3 Multi-Unit, Unit, Pump, & Valve
Con guration
To con gure Unit, Pump, and Valve options in
sections 3.3-3.5, the thermostat must be
connected to only one unit at a time.
AIRFLOW SELECTION
YF024 S N - - - - - 1 2 3 4
YF024 S N - - - - - 5 6 7 8
YF036 S N - - - - - 9 0 1 2
PREVIOUS SELECT
OPTION SELECTION
YF024 S N - - - - - 1 2 3 4
YF024 S N - - - - - 5 6 7 8
YF036 S N - - - - - 9 0 1 2
PREVIOUS SELECT