Installation manual
9
TI-99-NE
0108
Model 200MAX
All units conform to
CSA and UL standards.
ENGINEERING DATA
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two airstreams. It is easi-
ly removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC motor. 5 speed
fan operation. 120 VAC, 1.4 Amps.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of case designed to accept four reinforced polyester
straps that are supplied with the unit.
DEFROST
Recirculating damper defrost system.
DEHUMIDISTAT
Adjustable Internal Dehumidistat.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance.
Insulated to prevent exterior condensation. Drain connections 2 - 1/2" (12 mm) OD.
Door balancing ports.
CONTROLS
ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode, 20 ON/40 Recirculation
mode, Recirculation mode (each mode has 5 speeds). Control pad can be removed
from HRV and remotely mounted.
Weight 71 lbs. (32.5 kg) Shipping Weight 73 lbs. (33.5 kg)
Date: ___________________________________________
Tag: _____________________Qty:___________________
Project: _________________________________________
Engineer: _______________________________________
Contractor: ______________________________________
Supplier: ________________________________________
Quote#: _________________________________________
Submitted by: ____________________________________
*Sensible Efficiency – thermal **Latent Efficiency – moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams
Efficiency – takes into account all power inputs
Performance (HVI certified)
Net supply air flow in cfm (L/s) against external static pressure
E.S.P
(external static pressure) [cfm (L/s)]
@ 0.1" (25 Pa) 207 (97)
@ 0.2" (50 Pa) 200 (94)
@ 0.3" (75 Pa) 184 (87)
@ 0.4" (100 Pa) 171 (80)
@ 0.5" (125 Pa) 152 (71)
@ 0.6" (150 Pa) 130 (61)
@ 0.7" (175 Pa) 116 (55)
@ 0.8" (200 Pa) 86 (40)
Max. Temperature Recovery 74%
Sensible Effectiveness
@ 66 cfm (31 L/s) 32°F (0°C) 74%
*Sensible Efficiency
@ 66 cfm (31 L/s) 32°F (0°C) 64%
*Sensible Efficiency
@ 109 cfm (51 L/s) -13°F (-25°C) 62%
VAC @ 60HZ 120
WATTS / Low speed. 87
WATTS / High speed 164
Amp rating 1.4
1
2
3
4
5
40
60
80
100
120
140
160
180
200
220
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
Static Pressure (in w.g.)
Air Flow (cfm)
5 - High Speed
*4 - Medium High Speed
*3 - Medium Speed
*2 - Medium Low Speed
*1 - Low speed
* Manufacturers Data
OPTIONAL MAIN CONTROLS
99-350 Lifestyle Ventilation Control 7/24 programmable ventilation, (3 wire) 20
gauge wire (min.) 100’ length
99-109 Air Sentry Air Quality Monitor designed to accept remotely mounted
Control Pad, (3 wire) 20 gauge wire (min.) 100’ length
99-250 Ventilation Dehumidistat designed to accept remotely mounted Control
Pad, (4 wire) 20 gauge wire (min.) 100’ length
OPTIONAL TIMERS
99-104 Digital Electronic Timer - initiates high speed ventilation for 20, 40 or 60
minutes, (3 wire) 20 gauge wire (min.) 100’ length
99-101 Crank Timer - Initiates high speed ventilation for up to 60 minutes, (2 wire)
20 gauge wire (min.) 100’ length
OPTIONAL ACCESSORIES
99-163 Duct Heater w/ Electronic SCR Thermostat, 1 Kw, 6” (150 mm)
99-164 Duct Heater w/ Electronic SCR Thermostat, 2 Kw, 6” (150 mm)
99-185 Weatherhoods, Two - 6” (150 mm) c/w 1/4” (6 mm) mesh screen
WARRANTY
Units carry a LIFETIME warranty on the heat
recovery core and a 5 year replacement parts war-
ranty.
BALANCING DAMPER
33 5/8"
(850 mm)
STALE AIR
FROM INSIDE
FRESH AIR
FROM OUTSIDE
STALE AIR
TO OUTSIDE
FRESH AIR
TO INSIDE
14 3/4"
(375 mm)
19"
(483 mm)
*All Duct Connections 6" (150 mm)
CONDENSATE DRAINS
FILTERS
BLOWERS
*NOTE: Front
clearance
of 25 inches
(635 mm)
is recommended
for servicing unit.
RECIRCULATING
DEFROST
DAMPER
MOTOR
CORE
DIMENSIONS 200MAX inches (mm)