Installation manual

15
TI-200ERVD
0108
All units conform to
CSA and UL standards.
Model 200ERVD
ENGINEERING DATA
LATENT RECOVERY/MOISTURE TRANSFER CORE
The cross-flow energy recovery core transfers heat and water vapour between the two
airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC motor. 5 speed
fan operation. High speed - 120 VAC.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE ERV
Four threaded inserts at corners of case designed to accept four PVC reinforced poly-
ester straps that are supplied with the unit.
DEFROST
Damper defrost system.
DEHUMIDISTAT
Adjustable internal dehumidistat.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance.
Insulated to prevent exterior condensation. Door balancing ports.
DRAIN CONNECTIONS
Two - 1/2” (12mm) O.D.
CONTROLS
ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode (each mode has 5 speeds).
Control pad can be removed from HRV and remotely mounted.
Weight 63 lbs. (28.7 kg) Shipping Weight 65 lbs. (29.6 kg)
STALE AIR
TO OUTSIDE
STALE AIR
FROM HOUSE
FRESH AIR
TO INSIDE
14
3
/4"
(375)
19"
(483)
*
All Duct Connections 6"(150mm)
FILTERS
*NOTE: Front clearance
of 25 inches (635 mm)
is recommended
for servicing unit.
MOTOR
31"
(787mm)
FRESH AIR
FROM OUTSIDE
DAMPER
DEFROST
PORT
CONDENSATE DRAINS
ENTHALPIC
CORE
BALANCING DAMPER
DIMENSIONS 200ERVD inches (mm)
Date: ___________________________________________
Tag: _____________________Qty:___________________
Project: _________________________________________
Engineer: _______________________________________
Contractor: ______________________________________
Supplier: ________________________________________
Quote#: _________________________________________
Submitted by: ____________________________________
*Sensible Efficiency thermal **Latent Efficiency moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams
Efficiency – takes into account all power inputs
Performance
Net supply air flow in cfm (L/s) against external static pressure
E.S.P
(external static pressure) [cfm (L/s)]
@ 0.1" (25 Pa) 214 (101)
@ 0.2" (50 Pa) 206 (97)
@ 0.3" (75 Pa) 193 (91)
@ 0.4" (100 Pa) 184 (87)
@ 0.5" (125 Pa) 170 (80)
@ 0.6" (150 Pa) 155 (73)
@ 0.7" (175 Pa) 137 (65)
Sensible Effectiveness
@ 127 cfm (60 L/s) 32°F (0°C) 67%
*Sensible Efficiency
@ 127 cfm (60 L/s) 32°F (0°C) 60%
Total Efficiency 55%
VAC @ 60HZ 120
WATTS / Low speed. 70
WATTS / High speed 182
Amp rating 1.4
1
2
3
20
40
60
80
100
120
140
160
180
200
220
240
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
Static Pressure (in w .g.)
Air Flow (cfm)
3 - High Speed
2 - Medium Low Speed
1 - Low speed
OPTIONAL MAIN CONTROLS
99-350 Lifestyle Ventilation Control 7/24 programmable ventilation, (3 wire) 20
gauge wire (min.) 100’ length
99-109 Air Sentry Air Quality Monitor designed to accept remotely mounted
Control Pad, (3 wire) 20 gauge wire (min.) 100’ length
99-250 Ventilation Dehumidistat designed to accept remotely mounted Control
Pad, (4 wire) 20 gauge wire (min.) 100’ length
OPTIONAL TIMERS
99-104 Digital Electronic Timer - initiates high speed ventilation for 20, 40 or 60
minutes, (3 wire) 20 gauge wire (min.) 100’ length
99-101 Crank Timer - Initiates high speed ventilation for up to 60 minutes, (2 wire)
20 gauge wire (min.) 100’ length
OPTIONAL ACCESSORIES
99-163 Duct Heater w/ Electronic SCR Thermostat, 1 Kw, 6” (150 mm)
99-164 Duct Heater w/ Electronic SCR Thermostat, 2 Kw, 6” (150 mm)
99-185 Weatherhoods, Two - 6” (150 mm) c/w 1/4” (6 mm) mesh screen
WARRANTY
Units carry a LIFETIME warranty on the heat
recovery core and a 5 year replacement parts war-
ranty.