Installation manual
14
STALE AIR
TO OUTSIDE
FRESH AIR
FROM OUTSIDE
STALE AIR
FROM INSIDE
FRESH AIR
TO INSIDE
14
3
/4"
(375)
19"
(483)
*All Duct Connections 6"(150mm)
FILTERS
BLOWERS
*NOTE: Front clearance
of 25 inches (635 mm)
is recommended
for servicing unit.
MOTOR
ENTHALPIC CORE
33-5/8"
(850)
BALANCING
DAMPER
BALANCING
DAMPER
Model 200ERV
DIMENSIONS 200ERV inches (mm)
TI-98E
0108
ENGINEERING DATA
LATENT RECOVERY/MOISTURE TRANSFER CORE
The cross-flow energy recovery core transfers heat and water vapour between the two
airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC motor. 5 speed
fan operation. High speed - 120 VAC.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE ERV
Four threaded inserts at corners of case designed to accept four PVC reinforced poly-
ester straps that are supplied with the unit.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance.
Insulated to prevent exterior condensation. Door balancing ports.
CONTROLS
ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode (each mode has 5 speeds).
Control pad can be removed from HRV and remotely mounted.
Weight 63 lbs. (28.7 kg) Shipping Weight 65 lbs. (29.6 kg)
Date: ___________________________________________
Tag: _____________________Qty:___________________
Project: _________________________________________
Engineer: _______________________________________
Contractor: ______________________________________
Supplier: ________________________________________
Quote#: _________________________________________
Submitted by: ____________________________________
All units conform to
CSA and UL standards.
1
2
3
20
40
60
80
100
120
140
160
180
200
220
240
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
Static Pressure (in w.g.)
Air Flow (cfm)
3 - High Speed
2 - Medium Low Speed
1 - Low speed
*Sensible Efficiency – thermal **Latent Efficiency – moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams
Efficiency – takes into account all power inputs
Performance
Net supply air flow in cfm (L/s) against external static pressure
E.S.P
(external static pressure) [cfm (L/s)]
@ 0.1" (25 Pa) 214 (101)
@ 0.2" (50 Pa) 206 (97)
@ 0.3" (75 Pa) 193 (91)
@ 0.4" (100 Pa) 184 (87)
@ 0.5" (125 Pa) 170 (80)
@ 0.6" (150 Pa) 155 (73)
@ 0.7" (175 Pa) 137 (65)
Sensible Effectiveness
@ 127 cfm (60 L/s) 32°F (0°C) 67%
*Sensible Efficiency
@ 127 cfm (60 L/s) 32°F (0°C) 60%
Total Efficiency 55%
VAC @ 60HZ 120
WATTS / Low speed. 70
WATTS / High speed 182
Amp rating 1.4
OPTIONAL MAIN CONTROLS
99-350 Lifestyle Ventilation Control 7/24 programmable ventilation, (3 wire) 20
gauge wire (min.) 100’ length
99-109 Air Sentry Air Quality Monitor designed to accept remotely mounted Control
Pad, (3 wire) 20 gauge wire (min.) 100’ length
99-250 Ventilation Dehumidistat designed to accept remotely mounted Control Pad,
(4 wire) 20 gauge wire (min.) 100’ length
OPTIONAL TIMERS
99-104 Digital Electronic Timer - initiates high speed ventilation for 20, 40 or 60 min-
utes, (3 wire) 20 gauge wire (min.) 100’ length
99-101 Crank Timer - Initiates high speed ventilation for up to 60 minutes, (2 wire) 20
gauge wire (min.) 100’ length
OPTIONAL ACCESSORIES
99-163 Duct Heater w/ Electronic SCR Thermostat, 1 Kw, 6” (150 mm)
99-164 Duct Heater w/ Electronic SCR Thermostat, 2 Kw, 6” (150 mm)
99-185 Weatherhoods, Two - 6” (150 mm) c/w 1/4” (6 mm) mesh screen
WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and a 5 year replacement
parts warranty.