Specifications

67RT-PRC006-EN
Performance
Data
(7½ Ton)
High Efficiency
Table PD-74 — Belt Drive Evaporator Fan Performance — 7½-Ton — YHC092A3,A4,AW *L,M — Low and Medium Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied
Low Static Drive (1)
2400 599 0.52 650 0.62 703 0.75 751 0.87 789 0.98 823 1.08 855 1.19 885 1.29 912 1.39
2700 604 0.58 651 0.68 694 0.79 741 0.91 789 1.06 832 1.19 868 1.32 900 1.44 931 1.56 959 1.68
3000 661 0.77 705 0.88 744 1.00 783 1.12 826 1.26 869 1.42 909 1.58 945 1.73 976 1.86 1004 1.99
3300 719 1.00 758 1.11 797 1.25 832 1.37 867 1.51 907 1.68 946 1.85 983 2.02 1017 2.18 1048 2.34
3600 779 1.28 813 1.39 850 1.54 883 1.68 915 1.82 948 1.97 984 2.15 1020 2.33 1055 2.52 1088 2.71
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
Table PD-74 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2400 939 1.50 965 1.60 990 1.71 1014 1.81 1039 1.92 1063 2.03 1085 2.14 1108 2.25 1131 2.36 1154 2.49
2700 985 1.79 1010 1.91 1034 2.03 1058 2.14 1081 2.26 1104 2.38 1126 2.50 1148 2.62 1169 2.74 1190 2.86
3000 1031 2.12 1056 2.25 1081 2.39 1104 2.51 1127 2.65 1148 2.77 1169 2.90 1190 3.03 1210 3.16 1231 3.30
3300 1077 2.50 1102 2.64 1127 2.78 1151 2.93 1174 3.07 1194 3.21 1216 3.36
3600 1120 2.89 1146 3.06 1172 3.22 1195 3.38 ———————
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
Table PD-75 — Belt Drive Evaporator Fan Performance — 7½-Ton — YHC092A3,A4,AW *H — High Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied
Low Static Drive (1)
2400 613 0.54 666 0.66 718 0.78 762 0.90 799 1.01 833 1.11 864 1.22 893 1.32 920 1.42
2700 621 0.61 667 0.72 710 0.83 759 0.97 804 1.10 846 1.24 880 1.36 911 1.48 941 1.60 968 1.72
3000 680 0.81 723 0.93 761 1.05 802 1.18 845 1.33 888 1.49 925 1.64 959 1.79 988 1.92 1016 2.05
3300 740 1.06 780 1.19 816 1.31 850 1.45 889 1.60 928 1.77 966 1.94 1002 2.11 1036 2.28 1063 2.42
3600 800 1.35 837 1.49 872 1.63 904 1.77 935 1.91 971 2.08 1007 2.27 1043 2.45 1077 2.64 1108 2.83
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
Table PD-75 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2400 946 1.53 972 1.64 997 1.74 1022 1.84 1045 1.95 1069 2.06 1092 2.17 1115 2.28 1137 2.40 1160 2.52
2700 994 1.84 1019 1.95 1043 2.07 1066 2.18 1089 2.30 1112 2.42 1134 2.54 1155 2.66 1177 2.78 1197 2.90
3000 1043 2.18 1067 2.31 1091 2.44 1114 2.57 1137 2.70 1158 2.83 1178 2.96 1200 3.09 1220 3.22 1240 3.35
3300 1090 2.57 1116 2.72 1140 2.86 1162 3.00 1185 3.15 1206 3.29 1227 3.43
3600 137 3.00 1163 3.17 1188 3.33 ———————
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.