Specifications

63RT-PRC006-EN
Performance
Data
(5 Ton)
High Efficiency
Table PD-66 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40
CFM RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
1600 1239 1.19 1272 1.28 1304 1.37 1336 1.46
1800 1299 1.43
2000
2200
2400
Table PD-66 — Belt Drive Evaporator Fan Performance — 5 Ton — YHC060A3,A4,AW*L,M — Low and Medium Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
1600 775 0.42 837 0.50 898 0.57 952 0.65 1000 0.72 1044 0.79 1086 0.87 1127 0.95 1166 1.03 1203 1.11
1800 856 0.58 912 0.66 967 0.74 1020 0.83 1069 0.91 1112 1.00 1152 1.08 1189 1.16 1227 1.25 1263 1.34
2000 939 0.77 990 0.86 1040 0.96 1089 1.05 1136 1.14 1180 1.24 1219 1.33 1256 1.42 1292 1.50
2200 1023 1.01 1070 1.11 1115 1.21 1160 1.31 1205 1.41 ———————
2400 1108 1.29 1151 1.39 1193 1.50 ———————
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-89 to determine additional static pressure drop due to other
options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be
necessary.
Factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature
motor failure. Our product’s warranty will not be affected.
Table PD-67 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
1600 1251 1.22 1283 1.31 1315 1.40 1345 1.49
1800 1313 1.47
2000
2200
2400
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-89 to determine additional static pressure drop due to other
options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be
necessary.
Factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature
motor failure. Our product’s warranty will not be affected.
Table PD-67 — Belt Drive Evaporator Fan Performance — 5 Ton — YHC060A3,A4,AW*H — High Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
1600 796 0.45 858 0.52 917 0.60 969 0.67 1015 0.75 1059 0.82 1100 0.90 1141 0.98 1178 1.06 1216 1.14
1800 881 0.61 935 0.70 991 0.78 1042 0.87 1087 0.95 1129 1.03 1168 1.12 1206 1.20 1244 1.29 1279 1.38
2000 967 0.82 1016 0.91 1066 1.01 1115 1.10 1160 1.19 1201 1.28 1239 1.38 1275 1.47
2200 1054 1.07 1099 1.17 1144 1.27 1189 1.38 1233 1.48 ———————
2400 1141 1.37 1183 1.48 ———————
1-HP Standard Motor &
Field Supplied Low Static Drive (1)
1-HP Standard Motor &
Field Supplied High Static Drive (1)