Specifications
RT-PRC006-EN62
Performance
Data
(5 Ton)
High Efficiency
Table PD-64 — Belt Drive Evaporator Fan Performance — 5 Ton — YHC060A3,A4,AW*L,M — Low and Medium Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1600 704 0.36 757 0.41 806 0.47 853 0.52 899 0.58 942 0.65 984 0.72 1021 0.79 1058 0.85 1092 0.92
1800 777 0.49 828 0.56 872 0.62 915 0.67 957 0.73 998 0.80 1038 0.88 1076 0.96 1112 1.04 1146 1.11
2000 851 0.66 900 0.73 942 0.80 981 0.87 1019 0.93 1057 0.99 1094 1.07 1130 1.15 1165 1.24 1199 1.33
2200 927 0.86 973 0.94 1012 1.02 1049 1.09 1084 1.17 1119 1.23 1153 1.30 1188 1.38 1220 1.46 — —
2400 1003 1.10 1045 1.19 1084 1.28 1119 1.36 1152 1.44 — — ————————
Table PD-64 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
1600 1125 0.98 1158 1.06 1190 1.13 1220 1.20 1250 1.27
1800 1178 1.19 1209 1.26 1239 1.33 1269 1.41 1296 1.48
2000 1232 1.42 1263 1.50 — — — — — —
2200 — — — — — — — — — —
2400 — — — — — — — — — —
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-89 to determine additional static pressure drop due
to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may
be necessary.
Factory supplied motors, in commercial equipment, are definite
purpose motors, specifically designed and tested to operate reliably
and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will
not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
Table PD-65 — Belt Drive Evaporator Fan Performance — 5 Ton — YHC060A3,A4,AW*H — High Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1600 723 0.38 774 0.43 822 0.48 869 0.54 914 0.60 957 0.68 997 0.75 1035 0.81 1070 0.88 1104 0.94
1800 801 0.52 847 0.58 891 0.64 933 0.70 975 0.76 1015 0.83 1054 0.91 1091 0.99 1126 1.07 1160 1.15
2000 878 0.70 922 0.77 962 0.84 1001 0.90 1039 0.96 1076 1.03 1113 1.11 1149 1.20 1183 1.28 1217 1.38
2200 957 0.91 999 0.99 1036 1.07 1072 1.14 1107 1.21 1142 1.28 1176 1.35 1209 1.43 — — — —
2400 1036 1.17 1076 1.26 1111 1.34 1144 1.42 1177 1.50 — — ————————
Table PD-65 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
1600 1137 1.01 1168 1.08 1199 1.15 1230 1.22 1260 1.29
1800 1191 1.22 1222 1.29 1252 1.37 1281 1.44 1310 1.50
1000 1248 1.46 — — — — — — — —
2200 — — — — — — — — — —
2400 — — — — — — — — — —
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-89 to determine additional static pressure drop due
to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may
be necessary.
Factory supplied motors, in commercial equipment, are definite
purpose motors, specifically designed and tested to operate reliably
and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will
not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.