Specifications

53RT-PRC006-EN
(8½ Ton)
Standard Efficiency
Performance
Data
Table PD-48 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
2720 988 1.81 1013 1.93 1037 2.05 1061 2.17 1084 2.28 1106 2.40 1128 2.52 1150 2.64 1172 2.76 1192 2.88
3060 1040 2.19 1065 2.33 1090 2.46 1113 2.59 1136 2.72 1158 2.86 1179 2.99 1199 3.12 1220 3.25 1239 3.38
3400 1091 2.62 1117 2.78 1141 2.92 1165 3.07 1188 3.22 1210 3.37 ———————
3740 1137 3.07 1166 3.27 1193 3.44 ———————
4080 ———————
Table PD-48 — Belt Drive Evaporator Fan Performance — 8½ Ton — YSC102A3,A4,AW, AK *L,M — Low and Medium Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied 2-HP Standard Motor & Drive
Low Static Drive (1)
2720 607 0.59 655 0.69 697 0.80 744 0.93 791 1.07 834 1.21 871 1.34 904 1.46 933 1.58 962 1.70
3060 672 0.81 715 0.92 755 1.04 792 1.16 834 1.31 876 1.47 917 1.63 953 1.78 985 1.93 1013 2.06
3400 739 1.09 776 1.20 814 1.34 849 1.47 882 1.61 920 1.77 958 1.94 996 2.12 1030 2.29 1063 2.47
3740 807 1.43 839 1.54 875 1.69 907 1.83 938 1.98 969 2.13 1003 2.30 1037 2.49 1072 2.69 1106 2.88
4080 875 1.83 903 1.95 935 2.10 968 2.26 997 2.42 1025 2.58 1053 2.74 1084 2.93 1116 3.13 1148 3.34
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
Table PD-49 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
2720 998 1.86 1022 1.97 1046 2.09 1069 2.21 1092 2.33 1115 2.45 1136 2.56 1158 2.69 1179 2.80 1200 2.93
3060 1052 2.26 1077 2.39 1101 2.52 1124 2.66 1146 2.79 1167 2.92 1188 3.05 1209 3.18 1229 3.31 1249 3.45
3400 1106 2.71 1131 2.86 1155 3.01 1179 3.16 1202 3.31 1222 3.45 ———————
3740 1157 3.21 1185 3.39 ———————
4080 ———————
Table PD-49 — Belt Drive Evaporator Fan Performance — 8½ Ton — YSC102A3,A4,AW, AK *H— High Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied 2-HP Standard Motor & Drive
Low Static Drive (1)
2720 625 0.63 671 0.73 713 0.84 762 0.98 807 1.12 849 1.26 883 1.38 915 1.50 944 1.62 971 1.74
3060 692 0.86 734 0.98 772 1.10 811 1.23 854 1.38 896 1.54 934 1.70 969 1.85 997 1.99 1026 2.12
3400 760 1.15 799 1.28 834 1.41 868 1.55 903 1.70 942 1.87 980 2.04 1016 2.22 1049 2.39 1079 2.56
3740 828 1.50 863 1.64 898 1.79 929 1.94 960 2.08 993 2.25 1027 2.44 1062 2.63 1096 2.82 1127 3.02
4080 898 1.92 929 2.07 962 2.23 992 2.39 1020 2.55 1048 2.71 1078 2.89 1110 3.09 1142 3.30
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.