Specifications
9
OPTIONS AND ACCESSORIES
*Factory-installed.
†Field-installed.
**Cannot be used if unit electrical rating exceeds 80 amperes.
NOTE:
Refer to 580F price pages or contact your local representative for accessory/and option package information.
ITEM OPTION* ACCESSORY†
High-Static Motor and Drive
X
EconoMi$er (Vertical only)
XX
EconoMi$er with Power Exhaust (Vertical only)
X
Power Exhaust for EconoMi$er (Vertical/Horizontal)
X
EconoMi$er (Horizontal)
X
Durablade Integrated Economizer (Includes Hood)
XX
Manual Outdoor-Air Damper
XX
Alternate Drive (090)
X
Alternate Motor and Drive (036-060,090,120,150)
X
Unit-Mounted Non-Fused Disconnect**
X
Convenience Outlet
X
LP (Liquid Propane) Conversion Kit
X
Electronic Programmable Thermostat
X
Thermostats and Subbases
X
Light Commercial Thermidistat
X
25% Open Two-Position Damper
X
100% Open Two-Position Damper
X
Roof Curbs (Vertical and Horizontal Discharge)
X
Motormaster® IV Head Pressure Control (Cycle Control)
X
Time Guard® II Control Circuit
X
Thru-the-Bottom Utility Connections
X
Condenser Coil Hail Guard Assembly
X
Condenser Coil Grille
X
Flue Shield
X
Flue Discharge Deflector
X
Fan/Filter Status
X
Outdoor Air Enthalpy Sensor (EconoMi$er Only)
X
Return Air Enthalpy Sensor (EconoMi$er Only)
X
Return Air Temperature Sensor (EconoMi$er Only)
X
Indoor Air Quality (CO
2
) Sensor (EconoMi$er Only)
X
Low Ambient Controls
The 580F standard units are designed to operate in cooling at outdoor
temperatures down to 25 F. With accessory Motormaster IV control
(condenser-fan cycling) units can operate at outdoor temperatures down
to –20 F. The head pressure controls, which mount in the condenser
section, control the condenser-fan motor to maintain correct condensing
temperature.
MOTORMASTER IV CONTROL
Bryant Commercial Programmable Thermostat
Designed specifically for use with Bryant commercial sys-
tems, this Bryant programmable thermostat features LED
occupied/unoccupied displays and setback mode which can
override continuous fan operation.
Bryant Light Commercial Thermidistat
The light commercial thermidistat combines temperature
control and humidity display in one device and provides con-
tinuous fan operation in occupied mode.
Time Guard II Control
Time Guard II control automatically prevents compressor
from restarting for at least 5 minutes after a shutdown. Acces-
sory prevents short cycling of compressor if thermostat is
changed rapidly. Time Guard II control mounts in the control
compartment of unit.