ARI* CAPACITY RATINGS
LEGEND
*Air Conditioning and Refrigeration Institute.
†Applies only to units with capacity of 65,000 Btuh or less.
**The IPLV applies only to two-stage cooling units.
NOTES:
1. Rated in accordance with ARI Standards 210/240, latest revision (for sizes
036-120) or 360, latest revision (for size 150) and 270, latest revision.
2. ARI ratings are net values, reflecting the effects of circulating fan heat.
3. Ratings are based on:
Cooling Standard:
80 F db, 67 F wb indoor entering-air temperature and 95
F db air entering outdoor unit.
IPLV Standard:
80 F db, 67 F wb indoor entering-air temperature and 80 F
db outdoor entering-air temperature.
HEATING CAPACITIES AND EFFICIENCIES
LEGEND
*California compliant three-phase high heat models.
†Three-phase standard high heat models have heating input values as shown.
Single-phase standard high heat models have one-stage heating with heating
input values as follows:
580FJV036115, 115,000 Btuh
580FJV048150, 150,000 Btuh
580FJV060150, 150,000 Btuh
**California SCAQMD compliant Low NO
x
models have combustion products that
are controlled to 40 nanograms per joule or less.
UNIT
580F
NOMINAL
TONS
STANDARD
CFM
NET COOLING
CAPACITY
(Btuh)
TOTAL
kW
SEER† SOUND
RATING
(dB)
Belt Drive Direct Drive
036
3 1200 35,000 4.0 10.0 9.7 81
048
4 1600 47,000 5.5 10.0 9.7 81
060
5 2000 57,000 6.7 10.0 9.7 81
UNIT
580F
NOMINAL
TONS
STANDARD
CFM
NET COOLING
CAPACITY
(Btuh)
TOTAL
kW
EER
SOUND
RATING
(dB)
IPLV
072
6 2100 72,000 8.0 9.0 81 **
090
7
1
/
2
2800 85,000 9.6 8.9 87 9.35
102
8
1
/
2
3000 99,000 11.0 9.0 87 9.00
120
10 4000 117,000 13.0 9.0 88 9.35
150
12
1
/
2
4500 145,000 16.1 9.0 87 9.20
dB —
Sound Levels (decibels)
db —
Dry Bulb
EER —
Energy Efficiency Ratio
IPLV —
Integrated Part-Load Values
SEER —
Seasonal Energy Efficiency Ratio
wb —
Wet Bulb
UNIT 580F
HEATING INPUT (Btuh)
Stage 2/Stage 1
OUTPUT CAPACITY
(Btuh)
TEMPERATURE
RISE (F)
AFUE
(%)
STEADY-STATE
EFFICIENCY (%)
036074
—/ 72,000 59,200 25-55 80.0 80.0
036114*
—/115,000 92,000 55-85 80.0 80.0
036115†
115,000/ 82,000 92,000 55-85 80.0 80.0
036060N**
—/ 60,000 49,000 20-50 80.0 80.0
036090N**
—/ 90,000 73,000 30-60 80.0 80.0
048074
—/ 72,000 59,200 25-55 80.0 80.0
048115
—/115,000 92,000 35-65 80.0 80.0
048149*
—/150,000 120,000 50-80 80.0 80.0
048150†
150,000/120,000 120,000 50-80 80.0 80.0
048060N**
—/ 60,000 49,000 20-50 80.0 80.0
048090N**
—/ 90,000 73,000 30-60 80.0 80.0
048120N**
—/120,000 98,000 40-70 80.0 80.0
060074
—/ 72,000 59,200 25-55 80.0 80.0
060115
—/115,000 92,000 35-65 80.0 80.0
060149*
—/150,000 120,000 50-80 80.0 80.0
060150†
150,000/120,000 120,000 50-80 80.0 80.0
060060N**
—/ 60,000 49,000 20-50 80.0 80.0
060090N**
—/ 90,000 73,000 30-60 80.0 80.0
060120N**
—/120,000 98,000 40-70 80.0 80.0
072074
—/ 72,000 59,200 25-55 80.0 80.0
072115
—/115,000 92,000 35-65 80.0 80.0
072150
150,000/120,000 120,000 50-80 80.0 80.0
090125
—/125,000 100,000 20-50 80.0 80.0
090180
180,000/120,000 144,000 35-65 80.0 80.0
090224
224,000/180,000 179,200 45-75 80.0 80.0
102125
—/125,000 100,000 20-50 80.0 80.0
102180
180,000/120,000 144,000 35-65 80.0 80.0
102224
224,000/180,000 179,200 45-75 80.0 80.0
120180
180,000/120,000 144,000 35-65 80.0 80.0
120224
224,000/180,000 179,200 35-65 80.0 80.0
120250
250,000/200,000 200,000 40-70 80.0 80.0
150224
224,000/180,000 179,200 35-65 80.0 80.0
150250
250,000/200,000 200,000 40-70 80.0 80.0
AFUE —
Annual Fuel Utilization Efficiency