COMMERCIAL SINGLE PACKAGE ROOFTOP ELECTRIC COOLING UNITS 551A, 551B, 558F, 559F DuraPac and DuraPac Plus Series Sizes 036-300 3 to 25 Tons 551B036-072 558F036-073 551A155,180 558F180-210 559F180-216 551B090-150 558F090-150 558F300 558F240 559F240-300 FEATURES/BENEFITS • Efficient cooling using hermetic compressors. • Full range of electric heat sizes available — exactly the right size for your needs. • Accessory hydronic glycol heating coils are available for unit sizes 155-300.
4. Filter driers, which trap moisture and debris in the refrigeration system. 5. A fixed orifice metering system precisely controls refrigerant flow (sizes 036-150), preventing slugging and floodback, while maintaining optimum unit performance by metering the circuits individually. TXV meeting system on sizes 155-300. Two Independent Compressor Circuits (all 090-300 size units) provide pinpoint comfort control, improved efficiency, and back-up capability.
Easily Accessible Refrigerant Access Ports on all discharge, suction, and liquid lines permit easy and accurate measurements. Resettable 24-V Circuit Breaker (Sizes 090-150) allows room for error without replacing transformers or fuses. Single-Side Utility Connections provide easy access to perform any necessary service. Color-Coded Wires permit easy tracing and diagnostics. Indoor Fan Motors are accessible through a single access door to facilitate servicing and adjusting after installation.
OPTIONS AND ACCESSORIES ITEM 100% Open Two-Position Damper (036-150) 25% Open Two-Position Damper (036-150) Barometric Relief Damper (150-300) (Not for use with horizontal roof curb) Condenser Coil Grille (036-150) Condenser Coil Hail Guard Assembly (036-300) Convenience Outlet Copper Fins Indoor and Outdoor Coil Copper Fins Outdoor Coil Double Wall in Unit Airstream (155-300) Durablade Integrated Economizer (036-150) E-Coat Outdoor Coil (Aluminum) EconoMi$er Electronic Programmable Thermostat Enthalpy or D
OPTIONS AND ACCESSORIES (cont) LOW AMBIENT CONTROLS Standard units are designed to operate in cooling at outdoor temperatures down to 25 F for size 036-150 units, 40 F for size 150-300 units. With accessory Motormaster® control (condenser-fan cycling) units can operate at outdoor temperatures down to –20 F. The head pressure controls, which mount in the condenser section, control the condenser-fan motor to maintain correct condensing temperature.
OPTIONS AND ACCESSORIES (cont) DURA-SHIELD CONDENSER COIL OPTIONS Condenser coil options are available to match coil construction to site conditions for the best corrosion durability. Pre-coated coils provide protections in mild coastal environments. All copper coils are best suited for moderate coastal applications, while E-coated coils provide superior protection in severe coastal and industrial applications.
OPTIONS AND ACCESSORIES (cont) LIGHT COMMERCIAL THERMIDISTAT BRYANT COMMERCIAL THERMOSTAT Field-installed, wall-mounted device combines temperature and humidity control in one device. The dehumidifier output is used to control the Perfect Humidity dehumidification package. The occupied space humidity has a set point range between 50% and 90% relative humidity and provides constant fan operation in occupied mode.
OPTIONS AND ACCESSORIES (cont) UNIT-MOUNTED DISCONNECT (Sizes 036-150) UNIT-MOUNTED DISCONNECT (Sizes 150-300) Factory-installed, internally-mounted, NEC (National Electrical Code) and UL (Underwriters’ Laboratories) approved non-fused switch provides unit power shutoff with disconnect lockout protection capability. The switch is accessible from outside the unit. CONVENIENCE OUTLET Factory-installed, internally mounted and externally accessible 115-v female receptacle.
OPTIONS AND ACCESSORIES (cont) HAIL GUARD COIL GUARD GRILLE (036-150 Only) Condenser coil hail guard accessory (field installed) protects coils against damage from hail and other flying debris. Coil guard grille protects coils against large objects and vandalism.
OPTIONS AND ACCESSORIES (cont) EVAPORATOR-FAN HINGED PANEL OPTION* 581B036-072 FILTER HINGED PANEL OPTION* This is included as a factory-installed option. It permits quick and simple evaporator-fan access. This is included as a factory-installed option. It permits tool-less filter access. *Hinged panels not available on 580F models. LP CONVERSION KIT BURNER SPUDS (ORIFICES) LP conversion kit allows the unit to utilize a liquid propane fuel supply in areas where natural gas is not available.
CONTROLS OPERATING SEQUENCE — SIZE 036-073 UNITS Cooling, Units Without Economizer — When the thermostat calls for cooling, terminals G and Y1 are energized. The indoor (evaporator) fan contactor (IFC), and compressor contactor no. 1 (C1) are energized and the indoor (evaporator) fan motor (IFM), compressor no. 1, and condenser fan start. The outdoor (condenser) fan motor (OFM) runs continuously while unit is cooling.
CONTROLS (cont) Heating, Units Without Economizer — Upon a call for heating through terminal W1, indoor (evaporator) fan contactor (IFC) and heater contactor no. 1 (HC1) are energized. On units equipped for 2 stages of heat, when additional heat is needed, HC2 is energized through W2. Heating, Units With Economizer — When the room thermostat calls for heat through terminal W1, the indoor (evaporator) fan contactor (IFC) and heater contactor no. 1 (HC1) are energized.
CONTROLS (cont) As the refrigerant leaves the evaporator, the refrigerant passes a subcooler control low-pressure switch (S-LPS1 for circuit 1 or S-LPS2 for circuit 2) in the suction line. This low-pressure switch will deactivate the Perfect Humidity™ package when the suction pressure reaches 60 psig. The subcooler control lowpressure switch is an added safety device to protect against evaporator coil freeze-up during low ambient operation.
TYPICAL WIRING SCHEMATIC (Single Fan Units, Sizes 036-073) 14
BLK Y2 G AO COM 50DK508234 OAT TAN COM VIO OAH WHT +15V RED RAT TAN COM VIO RAM WHT +15V RED OAT USED FORMOUTDOOR AIR ENTHALPY STATUS 60 80 MIN POS (X) 40 0 C 100 D 30º 40º 1200 50º YEL Y1 CO SP MECH CLG ECON (PPM) LOCKOUT SP BLU 1400 B1 B CL02 20º A ORN 1000 OFF CL01 800 GND GRY 20 GRN 10º BRN 50DK509044 EconoMi$er ACTUATOR STEPPER DRIVE 24VAC 24COM 50DK508232 RED AD-DME1711-1 CONFIG TYPICAL WIRING SCHEMATIC (Two-Fan Units, Size 090-150) RED 2 BLK VIO
TYPICAL WIRING SCHEMATIC (Sizes 155-300) 16
TYPICAL WIRING SCHEMATIC (Sizes 155-300) LEGEND Adjustable Heat Anticipator American Wire Gage Breaks with Amp Turns Contactor, Compressor Capacitor Circuit Breaker Cooling Compensator Crankcase Heater Compressor Lockout Compressor Motor Control Relay Current Transformer Discharge Air Thermistor Damper Motor Dummy Terminal Enthalpy Control Equipment EconoMi$er Relay Emergency Power Supply (9 volt) — Fuse Link — Full Load Amps — Freeze Protection Thermostat AHA — AWG — BRK W/AT — C — CAP — CB — CC — CH — C
TYPICAL WIRING SCHEMATIC (cont) LEGEND OAT — Outdoor-Air Thermostat EconoMi$er Wiring NOTES: 1. If the Non-Fused Disconnect Option is ordered, the Non-Fused Disconnect will be factory-installed. 2. The Disconnect takes the place of TB-1 as shown on the unit wiring diagram label and the component arrangement label.
TYPICAL PIPING AND WIRING — SIZES 036-150 Vertical Discharge Ducting LEGEND NEC — National Electrical Code *Factory-supplied, internally mounted disconnect available as an option.
TYPICAL PIPING AND WIRING — SIZES 155-300 LEGEND NEC — National Electrical Code NOTES: 1. Illustration shown is a general guide only and is not intended to include all details for any specific installation. 2. Installation must comply with all applicable codes. 3. A 90-degree elbow must be installed on the supply duct connection for units equipped with electric heat.
APPLICATION DATA 1. CONDENSATE DRAIN PAN — A sloped condensate drain pan is supplied on all units. The condensate drain pan must be externally trapped. Condensate drains are located on both the bottom and end of the unit. The bottom drain can be used for thru-the-curb connections. 2. DUCTWORK — All ductwork must be attached to flanges. If no flanges are present, they must be field supplied. Secure vertical discharge ductwork to roof curb. For horizontal discharge applications, attach ductwork to flanges.
APPLICATION DATA (cont) c. HUMIDITY DAMAGE — Humidity causes property damage, such as stained wallpaper and ceiling tiles. Humidity can also damage books and artwork, and create strong odors in carpets. In addition, humidity can contribute to unacceptable product quality in industrial processes. d. IMPROPER VENTILATION — Buildings in hot and humid geographical areas cannot be properly ventilated due to high humidity levels outdoors, resulting in poor indoor-air quality. e.
APPLICATION DATA (cont) • Improved humidity control allows increased outdoor-air ventilation in hot and humid geographical areas. Humidity control also helps to improve the indoor-air quality of the building. • The Perfect Humidity dehumidification package is factory installed. There are no additional field installation costs.
Pressure Enthalpy Curve NOTE: Numbers 1 through 4 indicate point numbers referred to in Perfect Humidity™ Dehumidification Package Design Effects section.
LEGEND db — Dry Bulb wb — Wet Bulb Point 1 — Entering Air (F) 80 db/67 wb Point 2 — Leaving Air (F) 58.9 db/56.4 wb (Without Subcooler) Point 3 — Leaving Air (F) 63.0 db/56.
0TFQ004-012 558F036-150 MODEL NUMBER NOMENCLATURE — 558F 558F E X 090 000 KB 558F – Packaged Rooftop Standard Efficiency Electric Cooling Unit Factory-Installed Option Codes Voltage Designation J – 208/230-1-60 P – 208/230-3-60 E – 460-3-60 T – 575-3-60 Electric Heaters 000 – No factory-installed electric hea X – No Heat Installed (Field-installed electric heaters available) Nominal Tons 036 – 3 091 048 – 4 102 060 – 5 120 072 – 6 121 073 – 6* 150 090 – 7 1/2 – – – – – 7 1/2* 8 1/2 10 10* 12 1/
UNIT SIZE 558F NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Unit Al/Al* Al/Cu* Cu/Cu* EconoMi$er Roof Curb† COMPRESSOR Quantity No. Cylinders (per circuit) Oil (oz) REFRIGERANT TYPE Operating Charge (lb-oz) Circuit 1 Circuit 2 036 3 048 4 060 5 072 6 073 6 365 370 373 47 115 Reciprocating 1 2 50 375 381 387 47 115 RReciprocating 1 2 50 395 402 410 47 115 Reciprocating 1 2 50 R-22 470 479 490 47 115 Scroll 1 2 54 520 530 540 47 115 Scroll 1 2 54 4-4 — CONDENSER COIL Rows...Fins/in.
0TFQ004-012 558F036-150 PHYSICAL DATA — 558F090-150 UNIT SIZE 558F NOMINAL CAPACITY (tons) 090 71/2 091 71/2 102 81/2 120 10 121 150 121/2 OPERATING WEIGHT (lb) Unit Al/Al* Al/Cu* Cu/Cu* EconoMi$er Roof Curb† COMPRESSOR Quantity No.
0TFQ004-012 558F036-150 BASE UNIT DIMENSIONS — 558F036-072
0TFQ004-012 558F036-150 BASE UNIT DIMENSIONS — 558F073 30
0TFQ004-012 558F036-150 BASE UNIT DIMENSIONS — 558F090,102,120,150
0TFQ004-012 558F036-150 BASE UNIT DIMENSIONS — 558F091,121 32
ROOF CURB ACCESSORY CRRFCURB001A00 CRRFCURB002A00 “A” UNIT SIZE 558F 1′-2″ [356] 2′-0″ [610] 036-073 B C D ALT DRAIN HOLE 1′-911/16″ [551] 1′-4″ [406] 13/4″ [44.5] “E” “F” GAS POWER 3/ ″ [19] NPT 3/ ″ 4 4 [19] NPT 11/4″ [31.7] NPT 1/ ″ 2 3/ ″ [19] NPT 4 [12.7] NPT 3/ ″ 4 1 1 /4″ [31.7] NPT [19] NPT NOTES: 1. Roof curb accessory is shipped disassembled. 2. Insulated panels. 3. Dimensions in [ ] are in millimeters. 4. Roof curb: galvanized steel. 5.
0TFQ004-012 558F036-150 ACCESSORY DIMENSIONS (cont) ROOF CURB ACCESSORY CRRFCURB003A00 CRRFCURB004A00 “A” UNIT SIZE 558F 1′-2″ [356] 2′-0″ [610] 090-150 “B” 2′-87/16″ [827] “C” 1′-1015/16″ [583] “D” ALT DRAIN HOLE 13/4″ [44.5] “E” GAS “F” POWER 3/ ″ 4 [19] NPT 3/ ″ [19] NPT 4 11/4″ [31.7] NPT 1/ ″ 2 [12.7] NPT 3/ ″ 4 [19] NPT 3/ ″ 4 11/4″ [31.7] NPT NOTES: 1. Roof curb accessory is shipped disassembled. 2. Insulated panels, 1″ thick polyurethane foam, 13/4 lb density. 3.
I DETERMINE COOLING AND HEATING REQUIREMENTS AT DESIGN CONDITIONS: Given: Cooling Capacity Required . . . . . . . . . . . . . . 44,000 Btuh Sensible Heat Capacity . . . . . . . . . . . . . . . . . 32,000 Btuh Required Heating Load . . . . . . . . . . . . . . . . . 50,000 Btuh Condenser Entering-Air Temperature . . . . . . . . . . . . . . . . . . .95 F Edb/78 F Ewb Evaporator Entering-Air Temperature . . . . . . . . . . . . . . . . . . .80 F Edb/67 F Ewb Evaporator Air Quantity . . . . . . . . . . . . . . .
0TFQ004-012 558F036-150 PERFORMANCE DATA COOLING CAPACITIES Standard Ratings 558F036 (3 TONS) Temp (F) Air Entering Condenser (Edb) 75 85 95 105 115 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 72 42.8 20.0 2.91 40.8 19.4 3.14 38.7 18.6 3.35 36.5 17.8 3.55 34.3 17.0 3.76 Air Entering Evaporator — Cfm/BF 900/0.11 1200/0.14 1500/0.17 Air Entering Evaporator — Ewb (F) 67 62 72 67 62 72 67 62 38.9 35.0 44.8 40.8 37.0 45.8 41.9 38.2 24.5 28.7 21.8 27.5 32.8 23.0 30.0 36.0 2.81 2.70 2.99 2.88 2.
COOLING CAPACITIES (cont) 558F072 (6 TONS) Temp (F) Air Entering Condenser (Edb) 75 85 95 105 115 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 72 87.8 43.0 5.69 84.0 41.7 6.21 81.0 40.8 6.78 76.8 39.4 7.30 72.5 37.9 7.81 Air Entering Evaporator — Cfm/BF 2100/0.08 2400/0.09 Air Entering Evaporator — Ewb (F) 67 62 72 67 80.3 73.2 90.8 84.1 53.9 65.5 46.5 59.6 5.50 5.32 5.59 5.44 77.2 69.5 87.8 81.2 53.1 64.0 45.5 58.6 6.04 5.83 6.27 6.11 73.5 66.3 84.8 78.2 51.8 62.8 44.6 57.6 6.54 6.33 6.95 6.
0TFQ004-012 558F036-150 PERFORMANCE DATA (cont COOLING CAPACITIES (cont)) 558F091 (71/2 TONS) Temp (F) Air Entering Condenser (Edb) 75 85 95 105 115 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 72 107.8 53.6 6.46 103.8 52.6 6.94 98.9 51.2 7.42 92.8 49.1 7.81 86.8 47.3 8.25 Air Entering Evaporator — Cfm/BF 2800/0.11 3000/0.11 Air Entering Evaporator — Ewb (F) 67 62 72 67 100.1 91.7 108.4 100.9 69.1 83.2 54.6 71.1 6.19 5.93 6.5 6.25 95.4 86.8 104.6 96.2 67.7 81.1 53.8 69.9 6.66 6.37 6.98 6.69 90.
COOLING CAPACITIES (cont) 558F121 (10 TONS) Temp (F) Air Entering Condenser (Edb) 75 85 95 105 115 3000/0.095 72 136.6 67.2 8.12 130.8 64.7 8.66 124.8 62.6 9.26 118.8 60.8 9.93 115.7 59.7 10.2 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 67 125.5 83.1 7.83 120.3 81 8.38 114.4 78.9 8.97 105.2 75.3 9.59 98.6 72.8 9.84 62 112.7 98 7.57 104.6 94.4 8.1 97.3 90.5 8.65 88.4 85.7 9.24 84.7 83.9 9.49 Air Entering Evaporator — Cfm/BF 4000/0.125 Air Entering Evaporator — Ewb (F) 72 67 62 143.2 131.4 120.
0TFQ004-012 558F036-150 PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS 558F036 (3 TONS) — STANDARD MOTOR (DIRECT DRIVE) Low Speed Airflow 208 v (Cfm) ESP Bhp Watts ESP 0.67 0.21 253 0.68 900 0.60 0.23 270 0.61 1000 0.55 0.24 287 0.56 1100 0.51 0.26 304 0.51 1200 0.45 0.27 321 0.46 1300 0.38 0.29 338 0.41 1400 0.34 0.30 355 0.36 1500 High Speed 230, 460, 575 v Bhp 0.23 0.25 0.26 0.27 0.29 0.30 0.31 Watts 277 292 307 323 338 354 369 208 v Bhp 0.26 0.27 0.28 0.29 0.31 0.32 0.33 ESP 0.
FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 558F048 (4 TONS) — STANDARD MOTOR (DIRECT DRIVE) Low Speed Airflow 208 v (Cfm) ESP Bhp Watts ESP 0.93 0.41 458 0.94 1200 0.86 0.42 471 0.87 1300 0.78 0.45 503 0.79 1400 0.70 0.47 536 0.73 1500 0.61 0.49 557 0.64 1600 0.51 0.52 584 0.54 1700 0.40 0.54 610 0.44 1800 0.29 0.56 629 0.37 1900 0.25 0.58 651 0.30 2000 High Speed 230, 460, 575 v Bhp 0.45 0.46 0.49 0.52 0.54 0.57 0.60 0.62 0.64 Watts 506 521 556 593 616 646 674 696 720 208 v Bhp 0.51 0.52 0.54 0.
0TFQ004-012 558F036-150 PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 558F060 (5 TONS) — STANDARD MOTOR (DIRECT DRIVE) Low Speed Airflow 208 v 230, 460, 575 v (Cfm) ESP Bhp Watts ESP Bhp Watts 0.88 0.67 750 1.20 0.71 791 1500 0.68 0.70 780 1.04 0.74 824 1600 0.51 0.73 810 0.89 0.77 857 1700 0.35 0.75 839 0.73 0.80 891 1800 0.26 0.78 873 0.58 0.83 924 1900 0.18 0.81 905 0.42 0.86 957 2000 0.08 0.84 940 0.27 0.89 990 2100 — — — 0.19 0.92 1023 2200 — — — 0.11 0.
FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 558F072,073 (6 TONS)* — STANDARD MOTOR (BELT DRIVE) Airflow (Cfm) 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 3000 Rpm 852 894 936 978 1021 1064 1107 1150 1193 1237 1280 1324 1368 0.1 Bhp 0.55 0.64 0.74 0.85 0.97 1.10 1.24 1.39 1.56 1.74 1.94 2.15 2.37 Watts 562 630 708 795 891 998 1114 1241 1387 1543 1718 1901 2093 Rpm 905 945 984 1024 1064 1104 1145 1186 1228 1269 1311 1354 1396 0.2 Bhp 0.62 0.72 0.82 0.93 1.05 1.18 1.32 1.48 1.65 1.
0TFQ004-012 558F036-150 PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 558F090,091 (71/2 TONS)* — STANDARD MOTOR AND DRIVE AND ALTERNATE DRIVE (BELT DRIVE) Airflow (Cfm) 2250 2300 2400 2500 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750 Rpm 511 518 534 549 557 565 581 597 613 629 646 662 679 696 712 729 746 755 0.2 Bhp 0.52 0.55 0.61 0.67 0.71 0.74 0.81 0.89 0.97 1.06 1.15 1.25 1.35 1.46 1.57 1.69 1.85 1.
FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 558F090,091 (71/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* Airflow (Cfm) Rpm 514 521 536 551 559 567 582 598 614 630 646 662 679 695 712 729 745 754 2250 2300 2400 2500 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750 0.2 Bhp 0.55 0.57 0.63 0.69 0.72 0.75 0.83 0.90 0.98 1.07 1.16 1.28 1.36 1.47 1.59 1.71 1.84 1.
0TFQ004-012 558F036-150 PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 558F102 (8 TONS)* — STANDARD MOTOR (BELT DRIVE) Airflow (Cfm) 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750 3800 3900 4000 4100 4200 4250 Rpm 557 565 581 597 613 629 646 662 679 696 712 729 746 755 763 780 796 813 830 839 0.2 Bhp 0.71 0.74 0.81 0.89 0.97 1.06 1.15 1.25 1.35 1.46 1.57 1.69 1.82 1.89 1.95 2.09 2.23 2.39 2.55 2.
FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 558F102 (81/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* Airflow (Cfm) 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750 3800 3900 4000 4100 4200 4250 Rpm 559 567 582 598 614 630 646 662 679 695 712 729 745 754 762 779 796 813 830 839 0.2 Bhp 0.72 0.76 0.83 0.90 0.98 1.07 1.16 1.26 1.36 1.47 1.59 1.71 1.84 1.91 1.98 2.12 2.27 2.42 2.59 2.
0TFQ004-012 558F036-150 PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 558F120,121 (10 TONS)* Airflow (Cfm 3000 3100 3200 3300 3400 3500 3600 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000 Rpm 532 544 557 570 583 596 609 622 635 649 662 675 689 702 715 729 742 756 770 783 797 0.2 Bhp 0.64 0.70 0.75 0.81 0.88 0.94 1.01 1.09 1.16 1.25 1.33 1.42 1.52 1.61 1.72 1.83 1.94 2.06 2.18 2.31 2.
FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 558F150 (12 TONS)* Airflow (Cfm) 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000 5100 5200 5300 5400 5500 5600 5700 5800 5900 6000 6100 6200 6300 Rpm 654 668 683 697 711 726 741 755 770 784 799 814 829 843 858 873 888 903 918 933 948 963 978 993 1008 1023 1038 0.2 Bhp 1.12 1.20 1.28 1.37 1.46 1.56 1.66 1.77 1.89 2.00 2.13 2.25 2.39 2.52 2.67 2.82 2.97 3.13 3.30 3.47 3.65 3.83 4.00 4.22 4.42 4.63 4.
0TFQ004-012 558F036-150 PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS 558F036 (3 TONS) — STANDARD MOTOR (DIRECT DRIVE) Low Speed Airflow 208 v (Cfm) ESP Bhp Watts ESP 0.72 0.21 253 0.75 900 0.67 0.23 270 0.69 1000 0.61 0.24 287 0.63 1100 0.57 0.26 304 0.58 1200 0.51 0.27 321 0.53 1300 0.44 0.29 338 0.46 1400 0.39 0.30 355 0.41 1500 High Speed 230, 460, 575 v Bhp 0.23 0.25 0.26 0.27 0.29 0.30 0.31 Watts 277 292 307 323 338 354 369 ESP 0.73 0.70 0.64 0.56 0.53 0.47 0.
FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 558F048 (4 TONS) — STANDARD MOTOR (DIRECT DRIVE) Low Speed Airflow 208 v (Cfm) ESP Bhp Watts ESP 0.93 0.41 458 0.97 1200 0.86 0.42 471 0.90 1300 0.78 0.45 503 0.84 1400 0.73 0.47 536 0.76 1500 0.67 0.49 557 0.70 1600 0.60 0.52 584 0.63 1700 0.51 0.54 610 0.54 1800 0.40 0.56 629 0.45 1900 0.32 0.58 661 0.33 2000 Bhp — ESP — Watts — High Speed 230, 460, 575 v Bhp 0.45 0.46 0.49 0.52 0.54 0.57 0.60 0.62 0.
0TFQ004-012 558F036-150 PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 558F060 (5 TONS) — STANDARD MOTOR (DIRECT DRIVE) Low Speed Airflow 208 v 230, 460, 575 v (Cfm) ESP Bhp Watts ESP Bhp Watts 1.01 0.67 750 1.25 0.71 791 1500 0.82 0.70 780 1.09 0.74 824 1600 0.64 0.73 810 0.97 0.77 857 1700 0.44 0.75 839 0.81 0.80 891 1800 0.32 0.78 869 0.66 0.83 924 1900 0.21 0.81 899 0.47 0.86 957 2000 0.13 0.83 929 0.32 0.89 990 2100 0.05 0.86 959 0.19 0.92 1023 2200 — — — 0.08 0.
FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 558F072,073 (6 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 3000 Rpm 765 802 840 878 916 954 993 1031 1070 1109 1148 1188 1227 0.1 Bhp 0.45 0.45 0.60 0.69 0.78 0.89 1.00 1.13 1.26 1.41 1.57 1.74 1.92 Watts 487 539 600 669 739 827 916 1022 1131 1258 1396 1543 1700 Rpm 821 854 888 923 958 993 1029 1066 1103 1140 1177 1215 1253 0.2 Bhp 0.51 0.58 0.66 0.75 0.85 0.96 1.07 1.20 1.34 1.48 1.
0TFQ004-012 558F036-150 PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)) 558F072,073 (6 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* Airflow (Cfm) 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 3000 Rpm 942 982 1022 1063 1104 1130 1174 1201 1246 1285 1304 1345 1378 0.2 Bhp 0.73 0.83 0.94 1.10 1.20 1.27 1.37 1.50 1.67 1.80 1.85 2.05 2.
FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 558F090,091 (71/2 TONS) — STANDARD MOTOR AND DRIVE AND ALTERNATE DRIVE (BELT DRIVE)* Airflow (Cfm) 2250 2300 2400 2500 2550 2660 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750 Rpm 465 471 482 494 501 507 520 533 546 559 572 585 598 610 623 636 649 655 0.2 Bhp 0.43 0.45 0.50 0.54 0.57 0.59 0.65 0.71 0.77 0.83 0.90 0.96 1.03 1.10 1.17 1.25 1.33 1.
0TFQ004-012 558F036-150 PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 558F090,091 (71/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* Airflow (Cfm) 2250 2300 2400 2500 2550 2660 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750 Rpm 507 513 528 542 550 557 573 588 604 620 636 652 668 684 701 717 733 742 0.2 Bhp 0.53 0.55 0.60 0.68 0.69 0.72 0.79 0.86 0.94 1.02 1.11 1.21 1.31 1.41 1.53 1.65 1.77 1.
FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 558F102 (81/2 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) 2550 2660 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750 3800 3900 4000 4100 4200 4250 Rpm 501 507 520 533 546 559 572 585 598 610 623 636 649 655 661 674 687 699 712 719 0.2 Bhp 0.57 0.59 0.65 0.71 0.77 0.83 0.90 0.96 1.03 1.10 1.17 1.25 1.33 1.37 1.41 1.49 1.57 1.60 1.75 1.
0TFQ004-012 558F036-150 PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 558F102 (81/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* Airflow (Cfm) 2550 2660 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750 3800 3900 4000 4100 4200 4250 Rpm 550 557 573 588 604 620 636 652 668 684 701 717 733 742 750 767 783 800 817 826 0.2 Bhp 0.69 0.72 0.79 0.86 0.94 1.02 1.11 1.21 1.31 1.41 1.53 1.65 1.77 1.84 1.90 2.04 2.18 2.34 2.49 2.
FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 558F120,121 (10 TONS)* Airflow (Cfm) 3000 3100 3200 3300 3400 3500 3600 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000 Rpm 484 495 505 516 527 537 548 560 571 582 593 605 616 628 639 651 662 674 686 698 710 0.2 Bhp 0.55 0.61 0.66 0.72 0.78 0.85 0.92 1.00 1.08 1.16 1.25 1.35 1.45 1.56 1.67 1.78 1.91 2.03 2.17 2.31 2.
0TFQ004-012 558F036-150 PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 558F150 (121/2 TONS)* Airflow (Cfm) 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000 5100 5200 5300 5400 5500 5600 5700 5800 5900 6000 6100 6200 6300 Rpm 607 621 636 650 665 680 696 711 727 742 758 773 789 805 821 837 853 869 885 901 917 933 949 965 981 997 1014 0.2 Bhp 0.97 1.05 1.13 1.21 1.30 1.39 1.49 1.60 1.70 1.82 1.94 2.06 2.19 2.32 2.47 2.61 2.76 2.92 3.09 3.26 3.44 3.62 3.81 4.
ACCESSORY/FIOP STATIC PRESSURE (in. wg) — 558F036-073 CFM COMPONENT 900 0.05 0.15 0.05 1 Heater Module 2 Heater Modules EconoMi$er 1200 0.07 0.16 0.09 1400 0.09 0.16 0.13 1600 0.09 0.16 0.17 1800 0.10 0.17 0.22 2000 0.11 0.17 0.27 2200 0.11 0.17 0.32 2400 0.12 0.18 0.39 2600 0.13 0.18 0.45 3000 0.15 0.19 0.53 5500 0.14 0.19 — 6000 0.16 0.21 — 6250 0.17 0.20 — LEGEND FIOP — Factory-Installed Option *The static pressure must be added to external static pressure.
0TFQ004-012 558F036-150 PERFORMANCE DATA (cont) OUTDOOR SOUND DATA (Total Unit) UNIT 558F SOUND RATING (dB) A-WEIGHTED (dB) 036-073 090-102 120,121 150 81 87 88 87 80.5 86.4 87.6 86.4 63 56.8 83.2 97.6 83.7 125 75.8 87.4 90.4 87.2 250 72.4 83.5 85.7 83.4 SOUND POWER Octave Bands 500 1000 72.9 74.8 82.8 83.0 84.8 83.9 82.8 83.0 2000 75.4 77.7 77.5 77.7 4000 71.3 71.8 71.3 71.8 8000 69.1 67.0 65.8 67.
EVAPORATOR-FAN MOTOR PERFORMANCE UNIT 558F EVAPORATOR-FAN MOTOR Standard 036 Alternate High Static Standard 048 Alternate High Static Standard 060 Alternate High Static Standard 072,073 High Static Standard, Alternate 090,091 High Static Standard 102 High Static Standard 120,121 Alternate High Static Standard 150 Alternate UNIT VOLTAGE 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 4
0TFQ004-012 558F036-150 PERFORMANCE DATA (cont) ELECTRIC HEATING CAPACITIES UNIT 558F VOLTAGE (60 Hz) 208/230 (single phase) 036 208/230 (3 phase) 460 (3 phase) 208/230 (single phase) 048 208/230 (3 phase) 460 (3 phase) 208/230 (single phase) 060 208/230 (3 phase) 460 (3 phase) 208/230 (3 phase) 072 460 (3 phase) ACCESSORY kW 4.4 6.5 8.7 10.5 13.0* 4.4 6.5 8.7 10.5 16.0 6.0 8.8 11.5 14.0 4.4 8.7 13.0* 17.4* 21.0* 6.5 8.7 16.0 21.0* 6.0 11.5 14.0 23.0* 6.5 8.7 13.0* 17.4* 21.0* 6.5 10.5 16.0 21.
UNIT 558F NOMINAL V-Ph-Hz IFM TYPE VOLTAGE RANGE Min Max COMPRESSOR (ea) RLA LRA OFM (ea) Qty Hp FLA Std 208/230-1-60 208/230-3-60 IFM FLA 3.5 187 254 16.2 96.0 1 1/ 4 1.4 Alt 4.9 Std 3.5 Alt 187 254 10.2 75.0 1 1/ 4 1.4 4.9 036 460-3-60 High 5.2 Std 1.3 Alt 414 508 4.4 40.0 1 1/ 4 0.8 High 575-3-60 Std Alt High 2.6 518 632 3.7 31.0 1 1/ 4 0.8 Std 208/230-1-60 2.1 1.3 2.1 2.6 3.5 187 254 23.3 118.0 1 1/ 4 1.4 Alt 4.9 Std 3.
0TFQ004-012 558F036-150 ELECTRICAL DATA — 558F036-073 (cont) UNIT 558F NOMINAL V-Ph-Hz IFM TYPE VOLTAGE RANGE Min Max COMPRESSOR (ea) RLA LRA OFM (ea) Qty Hp FLA Std 460-3-60 Alt IFM FLA 1.8 414 508 8.3 45.0 1 1/ 4 0.8 2.1 048 High 575-3-60 Std Alt High 2.6 518 632 6.4 36.0 1 1/ 4 0.8 Std 208/230-1-60 208/230-3-60 1.8 2.1 2.6 5.9 187 254 28.8 147 1 1/ 4 1.4 Alt 6.6 Std 5.9 Alt 187 254 16.0 114 1 1/ 4 1.4 5.2 060 460-3-60 High 7.5 Std 3.
UNIT 558F NOMINAL V-Ph-Hz IFM TYPE VOLTAGE RANGE Min Max COMPRESSOR (ea) RLA LRA OFM (ea) Qty Hp FLA Std 208/230-3-60 IFM FLA 5.2 187 254 20.6 146 1 1/ 4 1.4 High 7.5 Std 2.6 072, 073 460-3-60 414 508 9.5 73 1 1/ 4 0.9 High 575-3-60 Std High 3.4 518 632 7.6 58.4 1 1/ 4 0.9 See Legend and Notes on page 70. 67 2.6 3.4 ELECTRIC HEAT* Nominal FLA kW** — — 4.9/ 6.5 13.6/15.6 7.9/10.5 21.9/25.3 12.0/16.0 33.4/38.5 15.8/21.0 43.8/50.5 19.9/26.5 55.2/63.8 — — 4.9/ 6.
0TFQ004-012 558F036-150 ELECTRICAL DATA — 558F090-150 UNIT 558F NOMINAL V-Ph-Hz IFM TYPE VOLTAGE RANGE Min Max COMPRESSOR (ea) RLA LRA Std and Alt 187 208/230-3-60 254 14.0 91.0 High Std and Alt 090,091 460-3-60 414 508 6.4 42.0 High 575-3-60 Std and Alt 518 632 5.2 39.0 High Std 208/230-3-60 187 254 16.0 137.0 High Std 102 460-3-60 414 508 8.3 69.0 High Std 575-3-60 518 632 6.4 58.0 High Std 120,121 208/230-3-60 Alt 187 High 254 15.8 130.
UNIT 558F NOMINAL V-Ph-Hz IFM TYPE VOLTAGE RANGE Min Max COMPRESSOR (ea) RLA LRA OFM (ea) Qty Hp FLA IFM FLA 2.6 Std 460-3-60 120,121 575-3-60 Alt 414 508 7.9 64.0 2 1/ 4 3.4 0.7 High 7.4 Std 2.6 Alt 518 632 6.6 52.0 2 1/ 4 0.7 3.4 High 7.4 Std 10.6 208/230-3-60 187 254 23.0 146.0 2 1/ 4 1.4 Alt 15.0 Std 4.8 150 460-3-60 414 508 10.4 73.0 2 1/ 4 0.7 Alt 7.4 Std 4.8 575-3-60 518 632 8.3 58.4 2 1/ 4 0.7 Alt 7.
0TFQ004-012 558F036-150 LEGEND AND NOTES FOR ELECTRICAL DATA TABLES PAGES 65-69 FLA — HACR — IFM — LRA — MCA — MOCP— NEC — OFM — RLA — Example: Supply voltage is 460-3-60.
MODEL NUMBER NOMENCLATURE — 551B 551B E X 090 000 DA Factory-Installed Option Code Voltage Designation J – 208/230-1-60 P – 208/230-3-60 E – 460-3-60 T – 575-3-60 Electric Heaters 000 – No factory-installed electric heaters X – No Heat Installed (Field-installed electric heaters available) Nominal Tons 036 – 3 048 – 4 060 – 5 072 – 6 090 – 7 1/2 102 – 8 1/2 120 – 10 150 – 12 1/2 NOTE: The example model number 551BEX090000DA designates a 71/2 ton 460-3-60 volt electric cooling rooftop unit with an
0TFQ004-012 551B036-150 PHYSICAL DATA — 551B036-072 UNIT 551B NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Unit EconoMi$er Perfect Humidity™ Dehumidification Package Roof Curb COMPRESSOR Quantity Oil (oz) REFRIGERANT TYPE Operating Charge (lb-oz) Standard Unit Unit With Perfect Humidity Dehumidification Package CONDENSER FAN Quantity...Diameter (in.) Nominal Cfm Motor Hp...Rpm Watts Input (Total) CONDENSER COIL Standard Unit Rows...Fins/in.
PHYSICAL DATA — 551B090-150 UNIT 551B NOMINAL CAPACITY (tons) Rows...Fins/in. Total Face Area (sq ft) HIGH-PRESSURE SWITCH (psig) Standard Compressor Internal Relief (Differential) Cutout Reset (Auto.) LOSS-OF-CHARGE/LOW-PRESSURE SWITCH (Liquid Line) (psig) Cutout Reset (Auto.
0TFQ004-012 551B036-150 BASE UNIT DIMENSIONS — 551B036-072 74
BASE UNIT DIMENSIONS — 551B090-150 0TFQ004-012 551B036-150 75
ACCESSORY DIMENSIONS — 551B036-072 0TFQ004-012 551B036-150 ROOF CURB ACCESSORY CRRFCURB001A00 CRRFCURB002A00 “A” UNIT SIZE 551B 1′-2″ [356] 2′-0″ [610] 036-072 B C D ALT DRAIN HOLE 1′-911/16″ [551] 1′-4″ [406] 13/4″ [44.5] “E” “F” GAS POWER 3/ ″ [19] NPT 3/ ″ 4 4 [19] NPT 11/4″ [31.7] NPT 1/ ″ 2 3/ ″ [19] NPT 4 [12.7] NPT 3/ ″ 4 1 1 /4″ [31.7] NPT [19] NPT NOTES: 1. Roof curb accessory is shipped disassembled. 2. Insulated panels. 3. Dimensions in [ ] are in millimeters. 4.
ACCESSORY DIMENSIONS — 551B090-150 ROOF CURB ACCESSORY CRRFCURB003A00 CRRFCURB004A00 “A” UNIT SIZE 551B 1′-2″ [356] 2′-0″ [610] 090-150 “B” 2′-87/16″ [827] “C” 1′-1015/16″ [583] “D” ALT DRAIN HOLE 13/4″ [44.5] “E” GAS “F” POWER 3/ ″ 4 [19] NPT 3/ ″ [19] NPT 4 11/4″ [31.7] NPT 3/ ″ 4 11/4″ [31.7] NPT NOTES: 1. Roof curb accessory is shipped disassembled. 2. Insulated panels, 1″ thick polyurethane foam, 13/4 lb density. 3. Dimensions in [ ] are in millimeters. 4. Roof curb: 16 gage steel. 5.
0TFQ004-012 551B036-150 SELECTION PROCEDURE (With 551B048 Example) I DETERMINE COOLING AND HEATING REQUIREMENTS AT DESIGN CONDITIONS. Given: Required Cooling Capacity (TC). . . . . . . . . . . 44,000 Btuh Sensible Heat Capacity (SHC) . . . . . . . . . . . . 32,000 Btuh Required Heating Capacity. . . . . . . . . . . . . . . 50,000 Btuh Condenser Entering-Air Temperature . . . . . . . . . . . . .95 F Evaporator Entering-Air Temperature . . . . . . . . . 82 F edb, 67 F ewb Evaporator Air Quantity . . . . . .
PERFORMANCE DATA COOLING CAPACITIES, STANDARD UNITS 551B036 (3 TONS) Temp (F) Air Ent Condenser (Edb) 75 95 105 115 125 78 45.6 14.5 2.24 44.4 14.1 2.51 42.9 13.6 2.80 41.3 13.0 3.11 72 41.9 20.4 2.19 40.7 19.9 2.46 39.3 19.5 2.75 37.7 18.8 3.06 36.0 18.3 3.41 34.2 17.6 3.78 67 38.7 25.2 2.16 37.5 24.7 2.42 36.1 24.1 2.71 34.6 23.5 3.02 33.0 22.9 3.36 31.3 22.2 3.73 62 35.7 29.7 2.12 34.5 29.2 2.39 33.1 28.4 2.66 31.7 27.8 2.98 29.7 26.7 3.31 27.8 25.8 3.
PERFORMANCE DATA (cont) COOLING CAPACITIES, STANDARD UNITS (cont) 551B080 (6 TONS) Temp (F) Air Ent Condenser (Edb) 0TFQ004-012 551B036-150 75 85 95 105 115 125 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 1800/0.05 78 93.5 29.9 4.73 91.3 29.2 5.29 89.0 28.4 5.85 72 86.7 43.0 4.58 84.1 42.0 5.10 81.3 41.0 5.65 77.9 39.7 6.22 74.7 38.7 6.84 70.3 37.2 7.43 67 80.7 53.7 4.46 78.2 52.6 4.97 75.3 51.4 5.52 72.0 50.2 6.08 68.4 48.8 6.68 63.6 47.0 7.25 62 74.4 63.8 4.33 72.0 62.7 4.
PERFORMANCE DATA (cont) COOLING CAPACITIES, STANDARD UNITS (cont) 551B120 (10 TONS) Temp (F) Air Ent Condenser (Edb) 75 95 105 115 125 78 152.7 46.7 7.34 150.5 44.7 8.28 147.7 43.9 9.33 72 140.3 65.6 7.35 137.7 65.0 8.29 133.8 63.9 9.33 128.7 62.3 10.46 123.2 60.4 11.66 117.5 58.5 12.99 67 129.4 82.2 7.21 125.3 81.2 8.13 120.7 79.6 9.16 115.4 77.6 10.28 109.1 75.1 11.47 101.8 72.5 12.77 62 115.0 97.4 7.12 110.0 95.2 8.02 103.0 92.2 8.98 96.5 89.4 10.00 90.8 86.6 11.20 86.2 84.5 12.50 78 153.1 47.
PERFORMANCE DATA (cont) COOLING CAPACITIES, UNITS WITH PERFECT HUMIDITY™ OPTION 551B036 (3 TONS) Temp (F) Air Entering Condenser (Edb) 0TFQ004-012 551B036-150 75 85 95 105 115 125 TC SHC kW TC SHC kw TC SHC kW TC SHC kW TC SHC kW TC SHC kW 900/0.14 78 44.9 12.5 2.26 42.1 10.8 2.53 39.2 9.1 2.82 37.1 7.5 3.13 72 41.3 17.5 2.19 38.6 15.2 2.46 35.9 13.0 2.74 33.8 10.9 3.05 31.8 9.0 3.40 28.7 6.9 3.78 67 37.3 22.4 2.14 34.4 20.1 2.40 31.4 17.9 2.68 29.7 15.8 3.00 28.0 13.7 3.36 26.3 12.2 3.73 62 34.
PERFORMANCE DATA (cont) COOLING CAPACITIES, UNITS WITH PERFECT HUMIDITY™ OPTION (cont) 551B072 (6 TONS) Temp (F) Air Entering Condenser (Edb) 75 85 95 105 115 125 78 89.0 25.0 4.80 84.9 21.8 5.40 80.7 18.7 6.01 72 82.6 36.0 4.60 78.2 31.4 5.16 73.8 27.0 5.75 68.4 22.3 6.37 63.4 18.1 7.04 55.5 15.3 7.80 67 75.6 44.8 4.52 71.6 41.2 5.03 67.4 37.6 5.60 62.6 33.5 6.22 57.8 29.5 6.89 49.6 24.0 7.61 62 68.5 55.4 4.36 64.5 41.7 4.89 60.2 47.9 5.44 55.9 43.5 6.06 50.7 38.9 6.68 45.8 35.2 7.38 78 91.1 25.
PERFORMANCE DATA (CONT) COOLING CAPACITIES, UNITS WITH PERFECT HUMIDITY™ OPTION (cont) 551B120 (10 TONS) Temp (F) Air Entering Condenser (Edb) 0TFQ004-012 551B036-150 75 85 95 105 115 125 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 3000/0.025 78 146.2 42.7 7.09 139.5 35.4 8.03 133.5 29.5 8.97 72 134.3 60.0 7.03 127.6 51.5 7.96 120.9 43.0 8.88 112.0 36.1 10.04 103.0 29.2 11.19 94.1 22.3 12.35 67 122.5 76.1 6.84 115.4 68.8 7.86 108.3 61.5 8.87 99.9 54.1 9.96 91.5 46.7 11.06 83.1 39.
PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS 551B036 (3 TONS) — STANDARD MOTOR (BELT DRIVE) Airflow (Cfm) 0.1 900 1000 1100 1200 1300 1400 1500 Bhp 0.12 0.19 0.22 0.26 0.29 0.35 0.42 Rpm 673 709 746 785 826 868 911 Bhp 0.18 0.22 0.26 0.32 0.38 0.45 0.53 Rpm 736 782 806 843 891 937 985 Bhp 0.25 0.30 0.35 0.41 0.48 0.57 0.66 Rpm 865 900 929 960 991 1032 1073 Rpm 1039 1061 1090 1109 1152 1181 1225 External Static Pressure (in. wg) 0.9 1.0 Bhp Rpm 0.45 1061 0.51 1086 0.58 1109 0.
PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 551B048 (4 TONS) — HIGH-STATIC MOTOR (BELT DRIVE) 0TFQ004-012 551B036-150 Airflow (Cfm) 0.2 Rpm 618 644 673 704 736 768 801 836 870 1200 1300 1400 1500 1600 1700 1800 1900 2000 Bhp 0.32 0.37 0.42 0.48 0.54 0.81 0.69 0.77 0.86 External Static Pressure (in. wg) 0.6 Rpm Bhp 842 0.44 867 0.50 889 0.55 912 0.61 920 0.68 965 0.76 892 0.84 1019 0.93 1046 1.03 Rpm 928 952 976 1001 1023 1045 1071 1097 1124 Bhp 0.89 1.01 1.09 1.20 1.
PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 551B072 (6 TONS) — STANDARD MOTOR (BELT DRIVE) Airflow (Cfm) Rpm 852 894 936 978 1021 1064 1107 1150 1193 1237 1280 1324 1368 0.2 Bhp 0.55 0.64 0.74 0.85 0.97 1.10 1.24 1.39 1.56 1.74 1.94 2.15 2.37 Rpm 905 945 984 1024 1064 1104 1145 1186 1228 1269 1311 1354 1396 0.4 Bhp 0.62 0.72 0.82 0.93 1.05 1.18 1.32 1.48 1.65 1.83 2.03 2.24 2.46 Rpm 1002 1037 1072 1108 1145 1183 1222 1262 1301 1341 1381 1420 1460 0.6 Bhp 0.78 0.88 0.98 1.
PERFORMANCE DATA (cont) FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 551B120 (10 TONS) — STANDARD AND HIGH-STATIC MOTOR (BELT DRIVE) 0TFQ004-012 551B036-150 Airflow (Cfm) Rpm 459 478 500 519 537 561 592 654 668 683 697 711 726 741 755 770 784 799 814 829 843 3000 3100 3200 3300 3400 3500 3600 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000 Bhp FIOP 0.2 — — 0.4 Bhp 0.46 0.57 0.62 0.69 0.77 0.86 0.98 1.12 1.20 1.28 1.37 1.46 1.56 1.66 1.77 1.89 2.00 2.13 2.25 2.39 2.
PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS 551B036 (3 TONS) — STANDARD MOTOR (BELT DRIVE) Airflow (Cfm) Rpm 526 570 614 658 703 725 755 Bhp 0.08 0.13 0.16 0.23 0.27 0.31 0.38 External Static Pressure (in. wg) 0.3 0.4 Rpm Bhp Rpm 656 0.12 734 800 738 0.19 812 758 0.23 780 0.28 840 808 0.32 868 845 0.38 891 870 0.43 924 Bhp 0.22 0.26 0.29 0.32 0.37 0.42 0.48 Rpm 818 848 863 889 916 937 969 Bhp 0.35 0.39 0.43 0.50 0.56 0.60 0.68 External Static Pressure (in. wg) 0.9 1.
PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 551B048 (4 TONS) — HIGH-STATIC MOTOR (BELT DRIVE) 0TFQ004-012 551B036-150 Airflow (Cfm) 1200 1300 1400 1500 1600 1700 1800 1900 2000 Bhp 0.2 Rpm 590 615 642 670 699 728 759 790 836 0.4 Bhp 0.20 0.23 0.27 0.31 0.36 0.42 0.48 0.55 0.62 Rpm 723 744 766 788 811 836 860 886 913 0.6 Bhp 0.30 0.35 0.39 0.44 0.49 0.55 0.62 0.69 0.77 Rpm 828 849 870 892 913 935 957 980 1004 0.8 Bhp 0.42 0.47 0.52 0.58 0.64 0.71 0.78 0.86 0.
PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 551B072 (6 TONS) STANDARD MOTOR (BELT DRIVE) Airflow (Cfm) Rpm 765 802 840 878 916 954 993 1031 1070 1109 1148 1188 1227 0.2 Bhp 0.45 0.45 0.60 0.69 0.78 0.89 1.00 1.13 1.26 1.41 1.57 1.74 1.92 Rpm 821 854 888 923 958 993 1029 1066 1103 1140 1177 1215 1253 0.4 Bhp 0.51 0.58 0.66 0.75 0.85 0.96 1.07 1.20 1.34 1.48 1.64 1.81 2.00 Rpm 923 953 984 1015 1046 1079 1112 1145 1179 1212 1246 1281 1316 Bhp 0.65 0.73 0.82 0.91 1.01 1.
PERFORMANCE DATA (cont) FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 551B102 (81/2 TONS) — STANDARD AND HIGH-STATIC MOTOR (BELT DRIVE) 0TFQ004-012 551B036-150 Airflow (Cfm) 2550 2660 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750 3800 3900 4000 4100 4200 4250 Bhp — 0.2 Rpm 501 507 520 533 546 559 572 585 598 610 623 636 649 655 661 674 687 699 712 719 0.4 Bhp 0.57 0.59 0.65 0.71 0.77 0.83 0.90 0.96 1.03 1.10 1.17 1.25 1.33 1.37 1.41 1.49 1.57 1.60 1.75 1.
PERFORMANCE DATA (cont) GENERAL FAN PERFORMANCE NOTES motor failure. Unit warranty will not be affected. See Evaporator-Fan Motor Performance tables on pages 93 and 94 for additional information. 3. Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative for details. 4. Interpolation is permissible. Do not extrapolate. NOTES: 1. Values include losses for filters, unit casing, and wet coils. See page 94 for accessory/factory-installed option static pressure information. 2.
PERFORMANCE DATA (cont) 0TFQ004-012 551B036-150 EVAPORATOR-FAN MOTOR PERFORMANCE — HIGH-STATIC MOTORS UNIT 551B UNIT PHASE MAXIMUM CONTINUOUS BHP* MAXIMUM OPERATING WATTS* 036 Three 2.40 2120 048 Three 2.40 2120 060 Three 2.90 2615 072 Three 2.90 2615 090,102 Three 4.20 3775 120 Three 5.25 4400 MAXIMUM AMP DRAW 6.7 3.0 3.0 6.7 3.0 3.0 8.6 3.9 3.9 8.6 3.9 3.9 12.2 5.5 5.5 17.3 8.5 8.
PERFORMANCE DATA (cont) 0.25 STATIC PRESSURE (in. wg) 0.20 0.15 0.10 0.05 0.20 0.15 0.10 0.05 0.00 0.
PERFORMANCE DATA (cont) 50 STATIC PRESSURE (in. wg) 0.35 FLOW (CFM) 30 20 10 0 0 0.5 0.75 0.25 3 TO 6 TON STATIC PRESSURE (in. wg) 7 1/2 TO 12 1/2 TON 0.30 0.25 0.20 0.15 0.10 0.05 0.00 1200 2000 3 TO 6 TON 7 1/2 TO 12 1/2 TON 1 80 3600 4400 STATIC PRESSURE (in. wg) 0.40 60 40 20 0.35 0.30 0.25 0.20 0.15 0.10 0.05 0.00 0 0.00 2800 FLOW (CFM) Vertical EconoMi$er Return-Air Pressure Drop Vertical EconoMi$er Outdoor-Air Leakage FLOW (CFM) 0TFQ004-012 551B036-150 40 0.
PERFORMANCE DATA (cont) ELECTRIC HEATING CAPACITIES UNIT 551B VOLTAGE (60 Hz) 036 208/230 (3 phase) 460 (3 phase) 208/230 (single phase) 048 208/230 (3 phase) 460 (3 phase) 208/230 (single phase) 060 208/230 (3 phase) 460 (3 phase) 208/230 (3 phase) 072 460 (3 phase) 4.4 6.5 8.7 10.5 13.0* 4.4 6.5 8.7 10.5 16.0 6.0 8.8 11.5 14.0 4.4 8.7 13.0* 17.4* 21.0* 6.5 8.7 16.0 21.0* 6.0 11.5 14.0 23.0* 6.5 8.7 13.0* 17.4* 21.0* 6.5 10.5 16.0 21.0* 26.5* 6.0 11.5 14.0 23.0* 25.5* 6.5 10.5 16.0 21.0* 26.5* 6.
ELECTRICAL DATA STANDARD MOTOR UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET 0TFQ004-012 551B036-150 UNIT 551B036 (3 Tons) 551B048 (4 Tons) 551B060 (5 Tons) NOMINAL VOLTAGE (V-Ph-Hz) VOLTAGE RANGE COMPRESSOR OFM IFM Min Max RLA LRA FLA FLA 208/230-1-60 187 254 16.0 88.0 0.7 4.9 208/230-3-60 187 254 10.3 77.0 0.7 4.9 460-3-60 414 508 5.1 39.0 0.4 2.2 575-3-60 518 632 4.2 31.0 0.4 2.2 208/230-1-60 187 254 23.7 129.0 0.7 4.9 208/230-3-60 187 254 13.5 99.
ELECTRICAL DATA (cont) STANDARD MOTOR UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET (cont) UNIT 551B102†† (81/2 Tons) 551B120†† (10 Tons) 551B150†† (121/2 Tons) VOLTAGE COMPRESSOR OFM RANGE (each) (each) IFM Min Max RLA LRA FLA 208/230-3-60 187 254 12.4 88.0 1.4 460-3-60 414 508 6.4 44.0 0.7 575-3-60 518 632 4.8 34.0 0.7 208/230-3-60 187 254 15.0 99.0 1.4 460-3-60 414 508 8.2 49.5 0.7 575-3-60 518 632 5.8 40.0 0.7 208/230-3-60 187 254 17.3 123.0 1.
ELECTRICAL DATA (cont) STANDARD MOTOR UNITS WITH ELECTRICAL CONVENIENCE OUTLET 0TFQ004-012 551B036-150 UNIT 551B036 (3 Tons) 551B048 (4 Tons) 551B060 (5 Tons) NOMINAL VOLTAGE (V-Ph-Hz) VOLTAGE RANGE COMPRESSOR OFM IFM Min Max RLA LRA FLA FLA 208/230-1-60 187 254 16.0 88.0 0.7 4.9 208/230-3-60 187 254 10.3 77.0 0.7 4.9 460-3-60 414 508 5.1 39.0 0.4 2.2 575-3-60 518 632 4.2 31.0 0.4 2.2 208/230-1-60 187 254 23.7 129.0 0.7 4.9 208/230-3-60 187 254 13.
ELECTRICAL DATA (cont) STANDARD MOTOR UNITS WITH ELECTRICAL CONVENIENCE OUTLET (cont) UNIT 551B102†† (81/2 Tons) 551B120†† (10 Tons) 551B150†† (121/2 Tons) VOLTAGE RANGE COMPRESSOR OFM (each) (each) IFM Min Max RLA LRA FLA FLA 208/230-3-60 187 254 12.4 88.0 1.4 7.5 460-3-60 414 508 6.4 44.0 0.7 3.4 575-3-60 518 632 4.8 34.0 0.7 3.4 208/230-3-60 187 254 15.0 99.0 1.4 7.5 460-3-60 414 508 8.2 49.5 0.7 3.4 575-3-60 518 632 5.8 40.0 0.7 3.
ELECTRICAL DATA (cont) HIGH-STATIC MOTOR UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET 0TFQ004-012 551B036-150 UNIT NOMINAL VOLTAGE (V-Ph-Hz) VOLTAGE RANGE Min COMPRESSOR (each) Max RLA LRA OFM IFM FLA FLA 208/230-3-60 187 254 10.3 77.0 0.7 5.8 460-3-60 414 508 5.1 39.0 0.4 2.6 575-3-60 518 632 4.2 31.0 0.4 2.6 208/230-3-60 187 254 13.5 99.0 0.7 5.8 460-3-60 414 508 7.4 49.5 0.4 2.6 575-3-60 518 632 5.8 40.0 0.4 2.6 208/230-3-60 187 254 17.3 123.0 1.
ELECTRICAL DATA (cont) HIGH-STATIC MOTOR UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET (cont) UNIT NOMINAL VOLTAGE (V-Ph-Hz) VOLTAGE RANGE Min RLA LRA FLA IFM FLA 254 12.4 88.0 1.4 10.6 551B090†† 460-3-60 414 508 6.4 44.0 0.7 4.8 575-3-60 518 632 4.8 34.0 0.7 4.8 208/230-3-60 187 254 15.0 99.0 1.4 10.6 551B102†† 460-3-60 414 508 8.2 49.5 0.7 4.8 575-3-60 518 632 5.8 40.0 0.7 4.8 208/230-3-60 187 254 17.3 125.0 1.4 15.0 551B120†† 460-3-60 414 508 9.0 62.
ELECTRICAL DATA (cont) HIGH-STATIC MOTOR UNITS WITH ELECTRICAL CONVENIENCE OUTLET 0TFQ004-012 551B036-150 UNIT NOMINAL VOLTAGE (V-Ph-Hz) VOLTAGE RANGE Min COMPRESSOR Max RLA LRA OFM IFM FLA FLA 208/230-3-60 187 254 10.3 77.0 0.7 5.8 460-3-60 414 508 5.1 39.0 0.4 2.6 575-3-60 518 632 4.2 31.0 0.4 2.6 208/230-3-60 187 254 13.5 99.0 0.7 5.8 460-3-60 414 508 7.4 49.5 0.4 2.6 575-3-60 518 632 5.8 40.0 0.4 2.6 208/230-3-60 187 254 17.3 123.0 1.5 7.
ELECTRICAL DATA (cont) HIGH-STATIC MOTOR UNITS WITH ELECTRICAL CONVENIENCE OUTLET (cont) UNIT NOMINAL VOLTAGE (V-Ph-Hz) VOLTAGE RANGE Min RLA LRA FLA IFM FLA 254 12.4 88.0 1.4 10.6 551B090†† 460-3-60 414 508 6.4 44.0 0.7 4.8 575-3-60 518 632 4.8 34.0 0.7 4.8 208/230-3-60 187 254 15.0 99.0 1.4 10.6 551B102†† 460-3-60 414 508 8.2 49.5 0.7 4.8 575-3-60 518 632 5.8 40.0 0.7 4.8 208/230-3-60 187 254 17.3 125.0 1.4 15.0 551B120†† 460-3-60 414 508 9.0 62.
50TFQ004-012 558F/551B036-150 GUIDE SPECIFICATIONS — SIZES 036-150 PACKAGED ROOFTOP COOLING UNIT WITH ELECTRIC HEAT OPTION — CONSTANT VOLUME APPLICATION HVAC GUIDE SPECIFICATIONS SIZE RANGE: 3 to 121/2 TONS, NOMINAL COOLING BRYANT MODEL NUMBER: 558F, 551B PART 1 — GENERAL 1.01 SYSTEM DESCRIPTION Outdoor rooftop- or slab-mounted, electrically controlled cooling unit with optional heat utilizing either reciprocating (558F) or scroll compressors for cooling duty and electric resistance coils for heating duty.
GUIDE SPECIFICATIONS — SIZES 036-150 (cont) I. K. L. M. * 3. * 4. 5. 6. 7. 8. 9. 10. * 11. 12. 107 f. Designed to close damper during loss-of-power situations with spring return built into motor (EconoMi$er). g. Dry bulb outdoor-air thermostat protection shall be provided as standard. h. The EconoMi$er is a parallel blade design.
GUIDE SPECIFICATIONS — SIZES 036-150 (cont) * * 50TFQ004-012 558F/551B036-150 * * * 13. High-Static Motor and Drive (036-120 3-phase units only): High static motor and drive shall be factory-installed to provide additional performance range. 14. Condenser Coil Grille: The grille protects the condenser coil from damage by large objects without increasing unit clearances. 15. Compressor Cycle Delay: Unit shall be prevented from restarting for a minimum of 5 minutes after shutdown. 16.
MODEL NUMBER NOMENCLATURE — 559F 5 5 9 F E X 1 8 0 0 0 0 A H C 559F – Standard Efficiency Electric Cooling Unit B Fan Drive Position (Standard Motor) B – Standard Low-Medium Fan Drive Static Capability D – Alternate High Fan Drive Static Capability Voltage Designation E – 460-3-60 P – 208/230-3-60 Factory-Installed Outdoor Air and Other Upgrade Options C – EconoMi$er H – Manual Outdoor-Air Damper Heat Type X – No Heat Installed (Field-installed electric heaters available) Nominal Tons 180
ARI* CAPACITY RATINGS (cont) ELECTRIC RESISTANCE HEATER DATA — 559F180-300 UNIT 559F 208 26 42 56 26 42 56 26 42 56 26 42 56 180 216 240 300 HEATER kW Unit Voltages 230 34 56 75 34 56 75 34 56 75 34 56 75 460 32 55 80 32 55 80 32 55 80 32 55 80 HEATER STAGES HEAT PER STAGE MAXIMUM STAGES* 2 2 2 2 2 2 2 2 2 2 2 2 50/50 33/67 50/50 50/50 33/67 50/50 50/50 33/67 50/50 50/50 33/67 50/50 2 3 4 2 3 4 2 3 4 2 3 4 MINIMUM HEATING CFM Cfm L/s 4500 2124 5400 2549 6000 2832 7000 3304 *Maximum n
PHYSICAL DATA — 559F180-300 UNIT 559F NOMINAL CAPACITY (tons) OPERATING WEIGHT COMPRESSOR/MANUFACTURER Quantity...Model (Ckt 1, Ckt 2) 180 15 2...ZR94KC Number of Refrigerant Circuits Oil (oz) (Ckt 1, Ckt 2) Stages of Capacity Control (%) REFRIGERANT TYPE Expansion Device Operating Charge (lb-oz) Circuit 1* Circuit 2 CONDENSER COIL 2 81, 81 50/50 Rows...Fins/in. Total Face Area (sq ft) CONDENSER FAN Nominal Cfm Quantity...Diameter (in.) Motor Hp...Rpm Watts Input (Total) EVAPORATOR COIL 2...17 21.
PHYSICAL DATA — 559F180-300 (cont) OPERATING AND RIGGING WEIGHTS UNIT 559F BASE UNIT OPERATING WEIGHTS* 216 240 lb kg lb 1650 748 1700 180 lb 1550 kg 703 300 kg 771 lb 1850 kg 839 *Base unit weight does not include electric heaters, copper coils, economizer, power exhaust, barometric relief or crating. See Options and Accessories table below for more information. NOTE: For 180 and 216 unit sizes add 75 lb (34 kg) for crating. For 240 and 300 unit sizes add 135 lb (61 kg).
STD UNIT WEIGHT Lb Kg 1550 703 1650 748 ECONOMI$ER WEIGHT Lb Kg 80 36.3 80 36.3 0TFQ004-012 559F180-300 180 216 UNIT 559F CORNER A Lb Kg 391 177 399 181 CORNER C Lb Kg 384 174 402 182 CORNER D Lb Kg 410 186 439 199 mm 1041 1016 DIM A ft-in. 3-5 3-4 Direction of airflow. Center of Gravity. mm 559 508 DIM C ft-in. 1-10 1- 8 5. Ductwork to be attached to accessory roof curb only. 6. Minimum clearance: • Rear: 7′-0″ (2134) for coil removal.
240 300 UNIT 559F STD UNIT WEIGHT Lb Kg 1700 771 1850 839 0TFQ004-012 559F180-300 ECONOMI$ER WEIGHT Lb Kg 80 36.3 80 36.3 CORNER A Lb Kg 419 190 428 194 CORNER B Lb Kg 394 179 412 187 CORNER C Lb Kg 425 193 511 232 CORNER D Lb Kg 463 210 499 226 mm 1016 965 DIM A ft-in. 3-4 3-2 mm 1041 1092 DIM B ft-in. 3-5 3-7 mm 508 508 DIM C ft-in.
ACCESSORY DIMENSIONS 0TFQ004-012 559F180-300 NOTES: 1. Roof curb accessory is shipped unassembled. 2. Insulated panels, 1″ thick neoprene coated, 11/2 lb density. 3. Dimensions in ( ) are in millimeters. 4. Direction of airflow. NOTE: To prevent the hazard of stagnant water build-up in the drain pan of the indoor section, unit can only be pitched as shown. 5. Roof curb: 16 ga. (VA03-56) steel. 6.
ACCESSORY DIMENSIONS (cont) NOTE: CRRFCURB013A00 is a fully factory preassembled horizontal adapter and includes an insulated high static regain transition duct which substantially improves fan static performance. The Barometric Relief Damper and Power Exhaust accessories must be installed in the Return Air Duct and are not available with the horizontal adapter. For Horizontal return applications: The power exhaust relief must be installed in the return air duct. ACCESSORY PACKAGE NO.
ACCESSORY DIMENSIONS (cont) LEGEND K.O.
0TFQ004-012 559F180-300 SELECTION PROCEDURE (with 559F180 example) From the given and the Accessory/FIOP Static Pressure table on page 125 find: External static pressure 0.60 in. wg Economizer static pressure 0.04 in. wg Total static pressure 0.64 in. wg Enter the Fan Performance table 559F180 (page 123) at 4,500 cfm and 0.64 in. wg external static pressure. By interpolation, find that the rpm is 905 and the watts are 1503. IV DETERMINE NET COOLING CAPACITY.
PERFORMANCE DATA COOLING CAPACITIES 559F180 (15 TONS) Temp (F) Air Entering Condenser (Edb) 75 85 95 105 115 118 120 BF — Edb — Ewb — kW — ldb — lwb — SHC — TC — TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 4500/0.10 57 164 164 13.6 159 159 14.8 154 153 16.1 148 147 17.5 142 142 18.9 140 140 19.3 139 139 19.6 62 177 146 14.0 170 142 15.2 163 139 16.4 155 135 17.6 148 131 19.0 145 130 19.4 144 129 19.6 67 193 124 14.4 186 120 15.6 178 117 16.9 170 114 18.2 162 111 19.
PERFORMANCE DATA (cont) COOLING CAPACITIES (cont) 559F240 (20 TONS) Temp (F) Air Entering Condenser (Edb) TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 75 85 95 105 115 125 BF — Edb — Ewb — kW — ldb — lwb — SHC — TC — 6,000/0.075 57 209 209 15.7 203 203 17.0 197 197 18.5 190 190 20.1 183 183 21.8 175 175 23.6 62 222 190 16.0 214 186 17.3 207 182 18.7 197 178 20.1 188 173 21.7 178 168 23.2 67 246 160 16.6 237 157 17.9 228 153 19.3 218 149 20.6 207 145 22.1 196 141 23.7 7,000/0.
PERFORMANCE DATA (cont) COOLING CAPACITIES (cont) 559F180 (15 TONS) — UNITS WITH PERFECT HUMIDITY™ OPTION Temp (F) Air Entering Condenser (Edb) TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 75 85 95 105 115 118 120 125 4500/0.12 62 — — — — — — — — — — — — — — — — — — — — — — — — 67 183 106 14.0 174 98 15.2 164 90 16.2 153 82 17.2 142 73 18.3 138 70 18.7 136 68 18.9 — — — 72 207 87 14.8 196 78 15.9 185 69 16.8 174 60 18.1 161 50 19.0 156 47 19.
PERFORMANCE DATA (cont) COOLING CAPACITIES (cont) 559F240 (20 TONS) — UNITS WITH PERFECT HUMIDITY™ OPTION Temp (F) Air Entering Condenser (Edb) TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 75 85 95 105 115 125 6,000/0.07 62 — — — — — — — — — — — — — — — — — — 67 237 141 16.2 227 133 17.5 215 125 18.7 205 117 20.2 190 108 21.2 176 97 22.8 72 269 118 17.1 257 110 18.3 246 102 19.6 230 92 20.3 217 82 22.2 198 70 22.9 Evaporator Air Quantity — Cfm/BF 8,000/0.
PERFORMANCE DATA (cont) GLYCOL HEATING PERFORMANCE GLYCOL COIL (559F180-300) Air Entering Evaporator — Cfm Temperature Entering Condenser Edb 4400 70 80 7200 Cap 310 255 200 274 218 164 249 194 140 25 Gpm 33 27 21 29 23 17 26 21 15 Ldb 120 108 97 127 116 104 132 121 109 Cap 293 237 181 257 201 146 233 177 123 50 Gpm 33 27 21 29 23 17 27 20 14 Ldb 116 105 93 124 112 100 129 117 106 Cap 347 285 223 306 244 183 279 217 156 25 Gpm 37 30 24 32 26 19 30 23 16 Ldb 115 104 94 123 112 101 128 117 107 C
PERFORMANCE DATA (cont) FAN PERFORMANCE — 559F180-300 UNITS (cont) 559F216, 240 (18 and 20 TONS)* Airflow (Cfm) 5,500 6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 0.2 Bhp 1.99 2.38 2.82 3.31 3.84 4.42 5.05 5.73 6.46 7.25 Rpm 682 730 778 828 878 928 979 1030 1082 1134 Watts 1675 2005 2373 2780 3227 3715 4245 4817 5433 6093 Available External Static Pressure (in. wg) 0.6 0.8 Rpm Bhp Watts Rpm Bhp Watts 832 2.59 2177 901 2.90 2441 871 2.99 2516 935 3.31 2783 911 3.44 2893 972 3.76 3164 953 3.
PERFORMANCE DATA (cont) OUTDOOR SOUND POWER SOUND RATING dB (60 Hz) 88 88 95 95 UNIT 559F 180 216 240 300 OCTAVE BANDS A-WEIGHTED (dB) 63 125 250 500 1000 2000 4000 8000 87.8 87.8 94.1 94.1 90.8 90.8 98.7 98.7 88.7 88.7 92.3 92.3 86.4 86.4 93.8 93.8 84.3 84.3 90.9 90.9 83.5 83.5 89.6 89.6 78.4 78.4 85.9 85.9 75.6 75.6 80.3 80.3 66.8 66.8 74.3 74.3 LEGEND Bels — Sound Levels (1 bel = 10 decibels) ACCESSORY/FIOP STATIC PRESSURE (in.
PERFORMANCE DATA (cont) EVAPORATOR-FAN MOTOR PERFORMANCE UNIT 559F UNIT VOLTAGE 208/230 460 208/230 460 208/230 460 208/230 460 180 216 240 300 MAXIMUM ACCEPTABLE CONTINUOUS BHP* 4.25 4.25 MAXIMUM ACCEPTABLE CONTINUOUS BkW* 3.17 3.17 MAXIMUM ACCEPTABLE OPERATING WATTS 3,775 3,775 5.90 4.40 5,180 8.70 9.50 10.20 11.80 6.49 7.08 7.61 8.80 7,915 8,640 9,510 11,000 MAXIMUM AMP DRAW 10.5 4.8 15.8 7.9 22.0 13.0 28.0 14.
ELECTRICAL DATA UNIT 559F Max 208/230 187 253 28.8 195 28.8 460 414 508 14.7 95 208/230 187 253 30.1 460 414 508 208/230 187 460 VOLTAGE RANGE OFM IFM Qty Hp FLA (ea) Hp FLA 195 3 0.5 1.7 3.7 10.5/11.0 14.7 95 3 0.5 0.8 3.7 4.8 225 28.8 195 3 0.5 1.7 5.0 15.8/15.8 15.5 114 14.7 95 3 0.5 0.8 5.0 7.9 253 37.8 239 30.1 225 2 1 6.6 7.5 25.0/25.0 414 508 17.2 125 15.5 114 2 1 3.3 7.5 13.0 208/230 187 253 41.0 350 37.
ELECTRICAL DATA (cont) FLA HACR IFM LRA MCA MOCP NEC OFM RLA — — — — — — — — — Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine percent voltage imbalance. LEGEND Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code Outdoor (Condenser) Fan Motor Rated Load Amps 7 457 = 1.
MODEL NUMBER NOMENCLATURE — 558F180-300 5 5 8 F E X 2 1 0 0 0 0 A A A 558F – Medium Efficiency Electric Cooling Unit A Fan Drive Position (Standard Motor)* B – Standard Low-Medium Fan Drive Static Capability D – Alternate High Fan Drive Static Capability Voltage Designation E – 460-3-60 P – 208/230-3-60 Heat Type X – No Heat Installed (Field-installed electric heaters available) Factory-Installed Outdoor Air and Other Upgrade Options C – EconoMi$er H – Manual Outdoor-Air Damper Nominal T
ARI* CAPACITY RATINGS (cont) ELECTRIC RESISTANCE HEATER DATA — 558F180-300 UNIT 558F 208 26 42 56 26 42 56 26 42 56 26 42 56 180 210 240 300 HEATER kW Unit Voltages 230 460 31 30 52 50 69 73 34 32 56 55 75 80 31 30 52 50 69 73 34 32 56 55 75 80 575 — — — — — — — — — — — — HEATER STAGES HEAT PER STAGE MAXIMUM STAGES* 2 2 2 2 2 2 2 2 2 2 2 2 50/50 33/67 50/50 50/50 33/67 50/50 50/50 33/67 50/50 50/50 33/67 50/50 2 3 4 2 3 4 2 3 4 2 3 4 MINIMUM HEATING CFM Cfm L/s 3750 1770 5400 2549 5000
PHYSICAL DATA — 558F180-300 UNIT 558F NOMINAL CAPACITY (tons) OPERATING WEIGHT COMPRESSOR/MANUFACTURER Quantity...Model (Ckt 1, Ckt 2) 180 15 1...ZR94KC, 1...ZR72KC 60/100 2 85,60 Stages of Capacity Control (%) Number of Refrigerant Circuits Oil (oz) (Ckt 1, Ckt 2) REFRIGERANT TYPE Expansion Device Operating Charge (lb-oz) Circuit 1† Circuit 2 CONDENSER COIL 19-6 13-4 4...15 21.7 Rows...Fins/in. Total Face Area (sq ft) CONDENSER FAN Nominal Cfm Quantity...Diameter (in.) Motor Hp...
PHYSICAL DATA — 558F180-300 (cont) OPERATING AND RIGGING WEIGHTS UNIT 558F 180 lb 1650 kg 748 lb 1710 BASE UNIT OPERATING WEIGHTS* 210 240 kg lb 776 1770 300 kg 803 lb 2120 kg 962 *Base unit weight does not include electric heaters, copper coils, economizer, power exhaust, barometric relief or crating. See Options and Accessories table below for more information. NOTE: For 180, 210 units add 75 lb (34 kg) for domestic crating. For 240 and 300 unit sizes add 135 lb (61 kg).
BASE UNIT DIMENSIONS — 558F180, 210 0TFQ004-012 558F180-300 133
0TFQ004-012 558F180-300 BASE UNIT DIMENSIONS — 558F240 134
BASE UNIT DIMENSIONS — 558F300 0TFQ004-012 558F180-300 135
0TFQ004-012 558F180-300 ACCESSORY DIMENSIONS NOTES: 1. Roof curb accessory is shipped unassembled. 2. Insulated panels, 1″ thick neoprene coated, 11/2 lb density. 3. Dimensions in ( ) are in millimeters. 4. Direction of airflow. NOTE: To prevent the hazard of stagnant water build-up in the drain pan of the indoor section, unit can only be pitched as shown. 5. Roof curb: 16 ga. (VA03-56) steel. 6.
ACCESSORY DIMENSIONS (cont) NOTE: CRRFCURB013A00 is a fully factory preassembled horizontal adapter and includes an insulated high static regain transition duct which substantially improves fan static performance. The Barometric Relief Damper and Power Exhaust accessories are not available with the horizontal adapter. ACCESSORY PACKAGE NO.
ACCESSORY DIMENSIONS (cont) LEGEND K.O.
SELECTION PROCEDURE (with 558F240 Example) I DETERMINE COOLING AND HEATING REQUIREMENTS AT DESIGN CONDITIONS. Given: Required Cooling Capacity . . . . . . . . . . . . . 230,000 Btuh Sensible Heat Capacity . . . . . . . . . . . . . . . . 170,000 Btuh Required Heating Capacity . . . . . . . . . . . . . . . . . . . 75 kW Condenser Entering Air Temp . . . . . . . . . . 95 F (Summer) Evaporator Entering Air Temp . . . . . . . . . . . . . . .80 F edb, 67 F ewb Evaporator Air Quantity . . . . . . . . . . . . . . .
PERFORMANCE DATA (cont) COOLING CAPACITIES 558F180 (15 TONS) Temp (F) Air Entering Condenser (Edb) 75 85 95 105 115 118 120 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 4,500/0.010 62 175.7 145.5 14.0 168.8 141.7 15.2 161.8 138.7 16.4 154.6 133.9 17.6 147.1 130.1 19.0 144.7 129.0 19.4 142.9 128.0 19.6 67 191.8 123.0 14.4 185.1 119.8 15.6 177.5 116.8 16.9 169.3 113.6 18.2 160.8 110.2 19.5 158.0 109.1 19.9 156.2 108.0 20.2 5,250/0.120 72 210.9 99.9 15.0 203.0 97.1 16.1 194.4 93.
PERFORMANCE DATA (cont) COOLING CAPACITIES (cont) 558F300 (25 TONS) Temp (F) Air Entering Condenser (Edb) TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 75 85 95 105 115 125 7,000/0.05 57 256 256 18.0 248 248 20.0 241 241 22.4 233 233 24.9 225 225 27.9 216 216 30.9 62 271 232 18.3 262 228 20.4 252 223 22.6 243 218 25.1 232 214 27.9 221 208 31.1 67 299 196 18.9 288 192 20.9 277 187 23.1 266 182 25.6 254 178 28.5 241 173 31.6 8,000/0.06 72 327 159 19.6 316 154 21.5 303 149 23.7 289 145 26.
PERFORMANCE DATA (cont) GLYCOL HEATING PERFORMANCE GLYCOL COIL Temperature Entering Condenser Edb Ewt 200 180 160 200 180 160 200 180 160 55 70 80 4400 Cap 310 255 200 274 218 164 249 194 140 25 Gpm 33 27 21 29 23 17 26 21 15 Ldb 120 108 97 127 116 104 132 121 109 Cap 293 237 181 257 201 146 233 177 123 50 Gpm 33 27 21 29 23 17 27 20 14 Ldb 116 105 93 124 112 100 129 117 106 Air Entering Evaporator — Cfm 5400 Percent Glycol 25 50 Cap Gpm Ldb Cap Gpm 347 37 115 327 37 285 30 104 264 30 223 24 94
PERFORMANCE DATA (cont) FAN PERFORMANCE — 558F180-300 UNITS 558F180* Cfm 4500 4800 5100 5700 6000 6300 6600 6900 7200 7500 Rpm 753 747 741 735 759 790 821 852 883 914 0.2 Watts 1307 1384 1465 1659 1854 2088 2340 2611 2903 3215 Rpm 993 1009 1026 1064 1083 1104 1125 1147 1170 1193 1.2 Watts 2133 2319 2521 2975 3228 3501 3791 4101 4431 4781 Bhp 1.53 1.62 1.72 1.95 2.18 2.45 2.74 3.06 3.40 3.77 Rpm 753 747 752 805 832 860 888 917 946 975 0.
PERFORMANCE DATA (cont) FAN PERFORMANCE — 558F180-300 UNITS (cont) 558F240* Cfm 6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 Rpm 753 793 844 895 947 999 1052 1105 1158 0.2 Watts 2385 2738 3151 3596 4073 4583 5125 5699 6306 Rpm 1069 1102 1136 1173 1211 1251 1292 1335 1378 1.2 Watts 3517 3891 4299 4739 5212 5718 6257 6830 7434 Rpm 1332 1356 1381 1409 1440 1471 1505 1540 — 2.2 Watts 4750 5122 5519 5951 6417 6916 7449 8016 — Bhp 2.83 3.25 3.74 4.27 4.83 5.44 6.08 6.76 7.
PERFORMANCE DATA (cont) FAN PERFORMANCE — 558F180-300 UNITS (cont) 558F300 (25 TONS)* Airflow (Cfm) 0.2 Bhp 3.26 3.82 4.43 5.11 5.85 6.65 7.52 8.45 9.45 9.97 Rpm 845 896 948 1001 1053 1106 1159 1213 1266 1293 7,000 7,500 8,000 8,500 9,000 9,500 10,000 10,500 11,000 11,250 Watts 2693 3156 3667 4226 4836 5498 6214 6984 7810 8245 Rpm 909 956 1005 1054 1104 1155 1206 1257 1309 1334 0.4 Bhp 3.60 4.17 4.80 5.49 6.23 7.04 7.92 8.86 9.87 10.
PERFORMANCE DATA (cont) FAN RPM AT MOTOR PULLEY SETTINGS* UNIT 558F 0 1/ 2 1 11/2 2 180† 180** 210† 210** 240† 240** 300† 300** †† †† †† †† †† †† †† †† †† †† †† †† †† †† †† †† †† †† 1095 1287 1225 1458 1283 — †† †† 1077 1265 1209 1434 1269 — 1021 1200 1058 1243 1187 1407 1247 1551 MOTOR PULLEY TURNS OPEN 21/2 3 31/2 4 1002 1178 1040 1222 1165 1381 1225 1524 984 1156 1021 1200 1143 1354 1203 1497 965 1134 1002 1178 1120 1328 1182 1470 947 1112 984 1156 1098 1301 1160 1443 41/2 5 51/2 6 92
PERFORMANCE DATA (cont) NOTE: The CRRFCURB013A00 horizontal supply/return adapter accessory improves 558F180-300 fan performance by increasing external static pressure by amount shown above. To convert from in. wg to Pa use the following formula: in. wg x 249.1 = Pa NOTE: The CRRFCURB013A00 high static regain adapter accessory may be used to provide horizontal supply/return.
ELECTRICAL DATA (cont) ELECTRICAL DATA — 558F180-300 (cont) NOMINAL VOLTAGE (3 Ph, 60 Hz) UNIT 558F VOLTAGE RANGE Min Max COMPRESSOR NO. 1 NO.2 RLA LRA RLA LRA OFM Qty Hp IFM FLA (ea) Hp FLA 208/230 187 253 42 239 33.6 225 2 1 6.6 7.5 25.0/25.0 460 414 508 19.2 125 17.3 114 2 1 3.3 7.5 13.0 208/230 187 253 41.4 312 47.1 245 6 0.5 1.7 10.0 28.0/28.0 460 414 508 20 150 19.6 125 6 0.5 0.8 10.0 14.
MODEL NUMBER NOMENCLATURE — 551A 551A E X 155 000 AJ C B 551A – High Efficiency Rooftop Units Electric Cooling Fan Drive Position (Standard Motor) B – Standard Low-Medium Fan Drive Static Capability D – Alternate High Fan Drive Static Capability Voltage Designation E – 460-3-60 P – 208/230-3-60 X – No Heat Installed Factory-Installed Outdoor Air Upgrade Options C – EconoMi$er H – 25% Manual Damper Nominal Tons 155 – 13 180 – 15 Electric Heaters 000 – No factory-installed electric heaters Access
ARI* CAPACITY RATINGS (cont) MULTIPLICATION FACTORS HEATER RATING VOLTAGE 200 0.694 — — 240 480 600 208 0.751 — — 230 0.918 — — ACTUAL HEATER VOLTAGE 380 440 460 — — — 0.626 0.840 0.918 — — — 240 1.000 — — 480 — 1.000 — 550 — — 0.840 575 — — 0.918 600 — — 1.000 NOTE: The following equation converts kW of heat energy to Btuh: kW x 3.413 = Btuh. EXAMPLE: 26.0 kW (at 240 v) heater on 208 v = 26.0 (.751 mult factor) = 19.5 kW capacity at 208 v.
PHYSICAL DATA — 551A155,180 UNIT 551A NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Unit Al/Al* Al/Cu* Cu/Cu* EconoMi$er Roof Curb† Perfect Humidity™ Dehumidification Package COMPRESSOR Quantity...Model (Ckt 1, Ckt 2) Number of Refrigerant Circuits Loading (% of full capacity) Oil (oz) (Ckt 1, Ckt 2) REFRIGERANT TYPE Expansion Device Operating Charge (lb)** Circuit 1 Circuit 2 CONDENSER COIL Motor Bearing Type Maximum Allowable Rpm Motor Pulley Pitch Dia. Nominal Motor Shaft Diameter (in.
PHYSICAL DATA (cont) OPERATING AND RIGGING WEIGHTS BASE UNIT OPERATING WEIGHTS* UNIT 155 lb 1575 551A 180 kg 714 lb 1650 kg 748 *Base unit weight does not include electric heaters, copper coils, economizer, power exhaust, barometric relief or crating. See Options and Accessories table below for more information. NOTE: For 155 and 180 unit sizes add 75 lb (34 kg) for domestic crating.
BASE UNIT DIMENSIONS — 551A155,180 0TFQ004-012 551A155-180 153
2′′-0″″ (610) 2′′-0″″ (610) 2′′-0″″ (610) CRRFCURB010A00 CRRFCURB011A00 CRRFCURB012A00 CRRFCURB013A00 PKG. NO. REF. CURB HEIGHT 1′′−2″″ (305) Standard Curb 14″″ High Standard Curb for Units Requiring High Installation Side Supply and Return Curb for High Installation Horizontal Adapter with High Static Transition Duct DESCRIPTION 0TFQ004-012 551A155-180 Direction of airflow. 154 551A UNIT in. .45 Deg. .28 A .28 Deg. B DIMENSIONS* (degrees and inches) .43 in. 5. Roof curb: 16 ga.
ACCESSORY DIMENSIONS (cont) NOTE: CRRFCURB013A00 is a fully factory preassembled horizontal adapter and includes an insulated high static regain transition duct which substantially improves fan static performance. The Barometric Relief Damper and Power Exhaust accessories are not available with the horizontal adapter. ACCESSORY PACKAGE NO.
ACCESSORY DIMENSIONS (cont) 0TFQ004-012 551A155-180 Factory-Installed Convenience Outlet Factory-Installed Non-Fused Disconnect 156
SELECTION PROCEDURE Enter the Accessory/FIOP Static Pressure — 551A155180 Units table at the selected unit size, cfm, and kW heater size to determine heater pressure drop. Calculate pressure drop: Design External Static Pressure 1.45 56 kW Heater Static Pressure +0.12 1.57 in. wg (ESP) Enter Fan Performance tables for 551A180 at 6,000 cfm and 1.57 in. wg. The rpm is 1184 and the Bhp is 4.43 (interpolation required).
PERFORMANCE DATA COOLING CAPACITIES 551A155 (13 TONS) Temp (F) Air Entering (Edb 75 85 95 105 115 117 120 125 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 3600/0.03 62 134 111 7.9 130 109 8.9 125 106 9.9 120 104 11.1 114 100 12.3 108 98 13.6 112 100 12.9 109 98 13.6 67 145 93 8.1 140 90 9.1 134 87 10.1 129 85 11.2 122 81 12.5 115 78 13.8 119 80 13.1 115 79 13.8 4375/0.04 72 153 72 8.2 147 68 9.2 141 66 10.2 134 63 11.3 127 60 12.6 118 57 13.9 123 59 13.
PERFORMANCE DATA (cont) COOLING CAPACITIES (cont) 551A155 (13 TONS) UNITS WITH PERFECT HUMIDITY™ OPTION Temp (F) Air Entering Condenser (Edb) 75 85 95 105 115 117 120 125 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 3600/0.03 62 — — — — — — — — — 105 80 10.6 90 66 11.7 86 64 12.8 90 67 12.3 83 61 12.8 67 139 81 8.0 133 75 8.9 126 70 9.9 119 65 10.9 108 57 12.1 100 52 13.2 102 52 12.6 95 47 13.1 4375/0.04 72 153 63 8.2 142 56 9.1 135 52 10.1 127 47 11.
PERFORMANCE DATA (cont) GLYCOL HEATING PERFORMANCE GLYCOL COIL (551A155,180) Temperature Entering Condenser Edb 4400 Ewt 200 180 160 200 180 160 200 180 160 55 70 80 25 Gpm 33 27 21 29 23 17 26 21 15 Cap 310 255 200 274 218 164 249 194 140 Ldb 120 108 97 127 116 104 132 121 109 Cap 293 237 181 257 201 146 233 177 123 50 Gpm 33 27 21 29 23 17 27 20 14 Ldb 116 105 93 124 112 100 129 117 106 GLYCOL COIL (551A155,180) (cont) Air Entering Evaporator — Cfm Temperature Entering 9000 Condenser 25 50 Edb
PERFORMANCE DATA (cont) FAN PERFORMANCE — 551A155,180 UNITS (cont) 551A155 WITH OPTIONAL MOTOR* Cfm Rpm 753 747 741 761 792 823 855 887 920 953 986 3750 4000 4250 4500 4750 5000 5250 5500 5750 6000 6250 0.2 Watts 942 1006 1073 1191 1339 1499 1671 1854 2050 2258 2480 Bhp 1.08 1.16 1.23 1.37 1.54 1.72 1.92 2.13 2.36 2.60 2.85 Rpm 786 810 835 861 887 915 943 972 1002 1031 1062 0.4 Watts 998 1118 1248 1389 1541 1705 1880 2068 2268 2480 2706 Available External Static Pressure (in. wg) 0.
PERFORMANCE DATA (cont) FAN PERFORMANCE — 551A155,180 UNITS (cont) 551A180* (cont) Cfm Rpm 1276 1287 1299 1325 1340 1356 — — — — 4500 4800 5100 5700 6000 6300 6600 6900 7200 7500 2.2 Watts 3509 3721 3949 4458 4741 5043 — — — — Bhp 4.12 4.36 4.63 5.23 5.56 5.91 — — — — Rpm 1326 1336 1347 1373 1387 — — — — — 2.4 Watts 3805 4020 4253 4772 5060 — — — — — Bhp 4.46 4.72 4.99 5.60 5.93 — — — — — Rpm 1375 1384 1395 1418 — — — — — — Available External Static Pressure (in. wg) 2.6 2.
PERFORMANCE DATA (cont) FAN RPM AT MOTOR PULLEY SETTINGS* 551A 0 1/ 2 1 11/2 2 21/2 3 31/2 4 41/2 5 51/2 6 155 (208/230, 460 v)† 155 (208/230, 460 v)** 180† 180** †† †† †† †† †† †† †† †† †† †† †† †† †† †† †† †† 1064 1426 1021 1200 1035 1393 1002 1178 1006 1360 984 1156 978 1327 965 1134 949 1294 947 1112 920 1261 928 1091 891 1227 910 1069 863 1194 891 1047 834 1161 873 1025 *Approximate fan rpm shown. †Indicates standard drive package. **Indicates alternate drive package.
ELECTRICAL DATA ELECTRICAL DATA — 551A155,180 UNIT 551A NOMINAL VOLTAGE (3 Ph, 60 Hz) Min Max COMPRESSOR No. 1 No. 2 RLA LRA RLA LRA 208/230 187 253 20.7 156 19.3 460 414 508 10 70 208/230 187 253 20.7 460 414 508 208/230 187 460 414 VOLTAGE RANGE OFM POWER EXHAUST IFM Qty Hp FLA (ea) Hp FLA 123 3 0.5 1.7 2.9 8.8/ 8.4 10 62 3 0.5 0.8 2.9 4.2 156 19.3 123 3 0.5 1.7 3.7 11.0/ 10.5 10 70 10 62 3 0.5 0.8 3.7 4.8 253 32.1 195 20.7 156 3 0.
GUIDE SPECIFICATIONS — SIZES 155-300 165 551A/558F/559F155-300 6. Unit shall contain a sloped drain pan, to prevent standing water from accumulating. Pan shall be fabricated of hot dipped zinc coated minimum spangle steel. Zinc coating shall be G90 designation according to ASTM Standard A653. Unit shall contain a factory-installed nonferrous main condensate drain connection. C. Fans: 1. Indoor blower (evaporator fan): a. Fan shall be belt driven. Belt drive shall include an adjustable pulley.
551A/558F/559F155-300 GUIDE SPECIFICTIONS — SIZES 155-300 (cont) 5. E-Coated aluminum-fin coils shall have a flexible epoxy polymer coating uniformly applied to all coil surface areas without material bridging between fins. Coating process shall ensure complete coil encapsulation. Color shall be high gloss black with gloss — 60 deg of 65 to 90% per ASTM D523-89. Uniform dry film thickness from 0.8 to 1.2 mil on all surface areas including fin edges.
GUIDE SPECIFICATIONS — SIZES 155-300 (cont) 4. 5. * 6. * 7. * * 8. 9. 10. * 11. 13. 14. 15. 16. 17. 167 positive superheat condition. If the operation of the subcooling coil is controlled by a field-installed wallmounted humidistat, the dehumidification circuit will then operate only when needed. Optional field connections for the humidistat are made in the low voltage compartment of the unit control box.
GUIDE SPECIFICATIONS — SIZES 155-300 (cont) 18. Glycol Coil: Coil shall be 2-row copper tube (1/2-in. OD) with aluminum plate fins (590 fins/m; 15 fins/in.) and (41.28 mm; 1.625 in. OD) copper headers. Input and output connections shall be (41.28 mm; 1.625 in. ODM) copper stubs for sweat connections. Coil shall be furnished with suitable support rails, end plates, and hardware for ready field installation in heater compartment. 19.
INDEX 551B036-150 section 71-108 551A155-180 section 149-168 558F036-150 section 26-70, 106-108 559F180-300 section 109-128, 165-168 558F180-300 section 129-148, 165-168 Airflow Configuration 21 Maximum 21 Minimum 21 Application data 21-25 ARI capacity ratings 551B036-150 71 551A155,180 149, 150 558F036-150 26 559F180-300 109, 110 558F180-300 129, 130 Changeover, heating to cooling 21 Coil guard grille 9 Concentric duct details 21 Condenser coil protection 6 Controls 11-13 Convenience outlet 8, 117, 138, 15
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Copyright 2002 Bryant Heating & Cooling Systems Printed in U.S.A. 1/02 Catalog No.