Product data

3
MODEL NUMBER NOMENCLATURE
704C N X 024
Model No.
704C – Single Pa ckaged
Air Conditioner
Electrical Supply
N – 208/230-1-60
N/A
Nominal Cooling Capacity
024 – 2.0 Tons
030 – 2.5 Tons
036 – 3.0 Tons
042 – 3.5 Tons
048 – 4.0 Tons
060 – 5.0 Tons
A A
N/A
Series
A – Original
Brand Name
A – Common Unit
000 BT
Options
BT - AL evap, vinyl condenser
CC - AL evap, CU condenser
CU - CU evap & condenser
TP - Base unit with tin plated indoor coil hairpins
TV - TP with vinyl coating on outdoor coil
TC - TP with AL indoor coil & CU/CU outdoor coil
Only used if ordering an option
LEGEND
AL Aluminum
CU Copper
P – 208/230-3-60
ARI* CAPACITIES
Cooling Capacities, Efficiencies and Sound Ratings
Unit 704C Nominal Tons Standard CFM
Net Cooling
Capacities (Btuh)
EER
@A**
SEER†
Sound Ratings‡
(dBA)
024 2 800 24,000 11 13.0 72
030 2--1/2 1000 28,800 11 13.0 72
036 3 1200 36,000 11 13.0 74
042 3--1/2 1400 41,000 11 13.0 74
048 4 1600 45,000 11 13.0 78
060 5 1750 57,000 11 13.0 78
* Air Conditioning & Refrigeration Institute.
** ”A condition s ---80°F indoor db/67°F indoor wb & 95°F outdoor db. { Rated in accordance with U.S. Government DOE (Department of Energy) test
procedures and/or ARI Standards 210/240---94.
} Tested in accordance with ARI Standard 270---95 (not listed in ARI).
NOTES
1. Ratings are net values, reflecting the effects of circulating fan heat. Ratings are based on:
Cooling Stan dard: 80°F db, 67°Fwb indoor entering --- air temperature and 95°F db outdoor entering---air temperature.
2. Before purchasing this appliance, read important energy cost and efficiency information available from your retailer.
LEGEND
dBA—Sound L evel s (decibels)
db—Dry Bulb
SEER—Seasonal Energy Efficiency Ratio
wb—Wet Bulb
704C