Instruction manual

23
Table 4 -- Dry Coil Air Delivery CFM* -- Downflow Discharge (Cont)
UNIT
MOTOR
SPEED
WIRE
COLOR
EXTERNAL STATIC PRESSURE (IN. W.C.)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.0
607C----A48
Low Blue
CFM 1491 1445 1403 1358 1306 1261 1199 1169 1122 1069
WATTS 232 239 254 262 278 293 303 316 323 335
BHP 0.25 0.26 0.27 0.28 0.30 0.31 0.32 0.34 0.35 0.36
MedLow Pink
CFM 1479 1436 1387 1346 1298 1253 1206 1160 1114 1061
WATTS 224 239 247 262 270 284 300 307 319 330
BHP 0.24 0.26 0.26 0.28 0.29 0.30 0.32 0.33 0.34 0.35
Medium
1
Red
CFM 1813 1785 1745 1709 1663 1632 1592 1548 1506 1450
WATTS 411 427 435 451 462 478 489 504 518 529
BHP 0.44 0.46 0.47 0.48 0.50 0.51 0.52 0.54 0.56 0.57
MedHigh Orange
CFM 2178 2148 2105 2073 2036 2002 1967 1919 1845 1751
WATTS 674 691 703 717 733 743 758 754 734 701
BHP 0.72 0.74 0.75 0.77 0.79 0.80 0.81 0.81 0.79 0.75
High Black
CFM 2480 2432 2375 2322 2236 2161 2085 2006 1917 1808
WATTS 1029 1012 995 975 941 908 869 836 796 751
BHP 1.10 1.09 1.07 1.05 1.01 0.97 0.93 0.90 0.85 0.81
607C----A60
Low Blue
CFM 1479 1436 1387 1346 1298 1253 1206 1160 1114 1061
WATTS 224 239 247 262 270 284 300 307 319 330
BHP 0.24 0.26 0.26 0.28 0.29 0.30 0.32 0.33 0.34 0.35
MedLow Pink
CFM 1841 1796 1761 1724 1690 1651 1616 1578 1527 1478
WATTS 425 434 453 460 476 485 501 508 525 542
BHP 0.46 0.47 0.49 0.49 0.51 0.52 0.54 0.54 0.56 0.58
Medium
1
Red
CFM 1944 1913 1872 1838 1801 1771 1731 1698 1655 1613
WATTS 486 501 511 529 537 554 565 578 595 603
BHP 0.52 0.54 0.55 0.57 0.58 0.59 0.61 0.62 0.64 0.65
MedHigh Orange
CFM 2178 2148 2105 2073 2036 2002 1967 1919 1845 1751
WATTS 674 691 703 717 733 743 758 754 734 701
BHP 0.72 0.74 0.75 0.77 0.79 0.80 0.81 0.81 0.79 0.75
High Black
CFM 2480 2432 2375 2322 2236 2161 2085 2006 1917 1808
WATTS 1029 1012 995 975 941 908 869 836 796 751
BHP 1.10 1.09 1.07 1.05 1.01 0.97 0.93 0.90 0.85 0.81
*Air delivery values are without air filter and are for dry coil (See 607C----A Wet Coil Pressure Drop table).
1
Factory--shipped cooling speed
NOTE: Deduct field--supplied air filter pressure drop and wet coil pressure drop to obtain external static pressure available for ducting.
Shaded areas indicate speed/static combinations that are not permitted.
607C-- -- A