Bryant Air Conditioning COMMERCIAL Model 579F/580D SINGLE PACKAGE ROOFTOP Sizes 036-300 GAS HEATING/ELECTRIC COOLING UNITS 3 to 25 Tons Model 580D036-072 Model 579F180,216 Model 580D090-150 Model 579F240,300 DESCRIPTION STANDARD FEATURES The 579/580 gas heating/electric cooling rooftop units are designed to deliver optimum performance and reliability in a commercial rooftop unit.
ADVANCED DESIGN of evaporator and condenser coils provides optimum heat transfer and cooling efficiency. Coils are computer-designed with advanced heat transfer surfaces, and are fabricated of copper tubing with aluminum fins. COMMERCIAL STRENGTH BASE RAILS (full-perimeter on 036-150 units) with built-in rigging capability permit easy rigging of unit. WEATHER-RESISTANT CABINET is built for durability in any climate.
FACTORY-INSTALLED OPTIONS DESCRIPTION AND USAGE when the evaporator fan is off to prevent cold backdrafts and wasted energy. • To reduce energy usage. Use whenever the number of hours of operation at below 55 F is significant. Manual Outdoor-Air Dampers — Package consists of a damper which can be set at 25% (180-300 only) or 50% (036150 only) outdoor air. The package includes a rainhood and birdscreen. SUGGESTED USE • To allow a fixed percentage of outdoor air for ventilation under all conditions.
FIELD-INSTALLED ACCESSORY DESCRIPTION AND USAGE (cont) LP (Liquid Propane) Kit (036-150) — Kit consists of gas orifices to convert the unit for use with LP gas. No gas valve modification is required. SUGGESTED USE: • When natural gas cannot be obtained for 036-150 units. Flue Hood Protector (036-150) — Consists of a sheet metal shield to go over the gas flue exhaust. SUGGESTED USE: • If additional protection from hot flue hood is required — for example, if 036-150 unit is slab mounted near a driveway.
MODEL DESCRIPTION (ODS Model Number) LEGEND ODS — Order Distribution System *Refer to Trade Price Sheets or contact your local representative for specific information regarding which options are available on which units.
CAPACITY RATINGS SEER* UNIT 580D NOMINAL TONS STANDARD CFM NET COOLING CAPACITY (Btuh) TOTAL kW Belt Drive Direct Drive 036 048 060 3 4 5 1200 1600 2000 35,000 47,000 57,000 4.0 5.5 6.7 10.0 10.0 10.0 9.7 9.7 9.7 UNIT 580D NOMINAL TONS STANDARD CFM NET COOLING CAPACITY (Btuh) TOTAL kW EER 072 090 102 120 150 6 7 1 ⁄2 81⁄2 10 121⁄2 2100 2800 3000 4000 4500 70,000 85,000 99,000 117,000 145,000 7.9 9.6 11.0 13.0 15.8 8.9 8.9 9.0 9.0 9.
DIMENSIONAL DRAWING — 580D036-072 UNIT 580D 036 048 060 072 A B C STANDARD UNIT WEIGHT Lb Kg 460 209 470 213 490 222 565 256 CORNER WEIGHT (A) Lb Kg 140 63.5 142 64.4 150 68.0 165 74.8 CONNECTION SIZES 11⁄169 Dia. [27] Field Power Supply Hole 3⁄49— 14 NPT Condensate Drain 1⁄29—14 NPT Gas Connection CORNER WEIGHT (B) Lb Kg 105 47.6 106 48.1 115 52.2 136 61.7 THREADED CONDUIT WIRE SIZE SIZE ⁄( ⁄( 34 2. 3. CORNER WEIGHT (D) Lb Kg 56 25.4 60 27.2 65 29.5 64 29.
DIMENSIONAL DRAWING — 580D090-150 UNIT 580D 090 102 120 150 STANDARD UNIT WEIGHT Lb Kg 870 395 880 399 1035 469 1050 476 CORNER CORNER CORNER CORNER WEIGHT WEIGHT WEIGHT WEIGHT ‘‘H’’ ‘‘J’’ ‘‘K’’ (A) (B) (C) (D) Lb Kg Lb Kg Lb Kg Lb Kg Ft-in. mm Ft-in. mm Ft-in.
DIMENSIONAL DRAWING — 579F180,216 UNIT 579F 180 231 180 270 216 270 UNIT 579F 180 231 180 270 216 270 A Lb 348 355 362 Kg 158 161 164 CORNER B Lb Kg 360 163 363 164 483 219 MAXIMUM SHIPPING WEIGHT Lb Kg 1800 816 1820 826 2131 967 WEIGHT* C Lb Kg 373 169 377 171 495 225 D Lb 523 530 511 Kg 237 240 232 *Weights are for unit only and do not include options or crating. NOTES: 1. Dimensions in ( ) are in millimeters. 2. 3. Center of gravity. Direction of airflow. 4.
DIMENSIONAL DRAWING — 579F240,300 UNIT 579F 240 240 300 300 270 485 270 485 A Lb 495 431 523 465 Kg 225 196 237 211 CORNER B Lb Kg 483 219 421 191 541 245 486 220 WEIGHT* C Lb Kg 362 164 494 224 574 260 725 329 D Lb 511 685 596 737 A Kg 232 311 270 334 Ft-in. 3-3 4-2 3-3 4-2 DIMENSIONS C D Ft-in. mm Ft-in. 0-3 76 6-111⁄2 0-41⁄2 114 8- 71⁄4 0-3 76 6-111⁄2 0-41⁄2 114 8- 71⁄4 B mm 991 1270 991 1270 Ft-in. 3-7 3-4 3-7 3-5 mm 1092 1016 1092 1041 mm 2121 2623 2121 2623 E Ft-in.
DIMENSIONAL DRAWING — ROOF CURB, 580D036-072 ROOF CURB ACCESSORY CRRFCURB001A00 CRRFCURB002A00 ‘‘A’’ UNIT SIZE 580D 18-29 [356] 28-09 [610] 036-072 UNIT SIZE 580D ‘‘B’’ ‘‘C’’ ‘‘D’’ ALT DRAIN HOLE 036-072 1-911⁄169 [551] 1-49 [406] 1-3⁄49 [45] ‘‘E’’ GAS ‘‘F’’ POWER ⁄ 9 NPT 34 ⁄ 9 NPT 34 34 34 ‘‘G’’ CONTROL ⁄ 9 NPT 34 ⁄ 9 NPT ⁄ 9 NPT 12 ⁄ 9 NPT CONNECTOR PACKAGE ACCESSORY 50DJ900791 (THRU-THE-CURB CONNECTIONS) CRBTMPWR001A00 (THRU-THE-BOTTOM CONNECTIONS) NOTES: 1.
DIMENSIONAL DRAWING — ROOF CURB, 580D090-150 ROOF CURB ACCESSORY ‘‘A’’ CRRFCURB003A00 18-29 [356] CRRFCURB004A00 28-09 [610] UNIT SIZE 580D UNIT SIZE 580D ‘‘B’’ ‘‘C’’ ‘‘D’’ ALT DRAIN HOLE 090-150 ‘‘E’’ GAS ‘‘F’’ POWER ⁄ 9 NPT 19 NPT 34 34 090-150 28-87⁄169 [827] 18-1015⁄169 [583] 13⁄49 [45] ‘‘G’’ CONTROL ⁄ 9 NPT ⁄ 9 NPT 34 ⁄ 9 NPT 12 ⁄ 9 NPT 11⁄49 NPT 12 34 34 ⁄ 9 NPT ⁄ 9 NPT CONNECTOR PACKAGE ACCESSORY 50DJ901551 (THRU-THE-CURB CONNECTIONS) CRBTMPWR001A00 (THRU-THE-BOTTOM CONN
DIMENSIONAL DRAWING — HORIZONTAL AND VERTICAL ROOF CURBS AND HORIZONTAL ADAPTER, 579F180-300 NOTE: To prevent the hazard of stagnant water build-up in the drain pan of the indoor-air section, unit can only be pitched as shown. LEGEND COMPR SECT. — Compressor Section NOTES: 1. Roof curb accessory is shipped unassembled. 2. Insulated panels, 1⁄2-in. thick neoprene-coated, 2 lb density. 3. Dimensions in ( ) are in millimeters. 4. Direction of airflow. 5. Roof curb: 18 gage steel. 6.
DIMENSIONAL DRAWING — HORIZONTAL ADAPTER INSTALLATION — 579F216-300 NOTE: 389210-201 and 389211-201 are fully factory preassembled horizontal adapters which include an insulated high static regain transition duct and substantially improve fan static performance.
SPECIFICATIONS — 580D036-072 UNIT SIZE NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Unit Al/Al* Economizer Varislide™ Parablade Roof Curb COMPRESSOR Quantity Oil (oz) REFRIGERANT TYPE Operating Charge (lb-oz) Circuit 1 Circuit 2 CONDENSER COIL Rows...Fins/in. Total Face Area (sq ft) CONDENSER FAN Nominal Cfm Quantity...Diameter (in.) Motor Hp...Rpm Watts Input (Total) EVAPORATOR COIL Rows...Fins/in. Total Face Area (sq ft) EVAPORATOR FAN Quantity...Size (in.
SPECIFICATIONS — 580D036-072 (cont) UNIT SIZE FURNACE SECTION Rollout Switch Cutout Temp (F)† Burner Orifice Diameter (in. ...drill size) Natural Gas Liquid Propane Pilot Orifice Diameter (in. ...drill size) Natural Gas Liquid Propane Thermostat Heat Anticipator Setting (amps) 208/230, 575 v Stage 1 Stage 2 460 v Stage 1 Stage 2 Gas Input (Btuh) Stage 1 Stage 2 Efficiency (Steady State) (%) Temperature Rise Range Manifold Pressure (in.
SPECIFICATIONS — 580D090-150 UNIT SIZE NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Unit Al/Al* Economizer Varislide™ Parablade Roof Curb†† COMPRESSOR Quantity Oil (oz) REFRIGERANT TYPE Operating Charge (lb-oz) Circuit 1 Circuit 2 CONDENSER COIL Rows...Fins/in. Total Face Area (sq ft) CONDENSER FAN Nominal Cfm Quantity...Diameter (in.) Motor Hp...Rpm Watts Input (Total) EVAPORATOR COIL Rows...Fins/in. Total Face Area (sq ft) EVAPORATOR FAN Quantity...Size (in.
SPECIFICATIONS — 580D090-150 (cont) UNIT SIZE FURNACE SECTION Rollout Switch Cutout Temp (F)† Burner Orifice Diameter (in. ...drill size) Natural Gas Liquid Propane Pilot Orifice Diameter (in. ...drill size) Natural Gas Liquid Propane Thermostat Heat Anticipator Setting (amps) 208/230, 575 v Stage 1 Stage 2 460 v Stage 1 Stage 2 Gas Input (Btuh) Stage 1 Stage 2 Efficiency (Steady State) (%) Temperature Rise Range Manifold Pressure (in.
SPECIFICATIONS — 579F180-300 UNIT SIZE NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Unit Al/Al* Economizer Roof Curb†† COMPRESSOR Quantity Oil (oz) REFRIGERANT TYPE Operating Charge (lb-oz)¶ Circuit 1 Circuit 2 CONDENSER COIL Rows...Fins/in. Total Face Area (sq ft) CONDENSER FAN Nominal Cfm Quantity...Diameter (in.) Motor Hp...Rpm Watts Input (Total) EVAPORATOR COIL Rows...Fins/in. Total Face Area (sq ft) EVAPORATOR FAN Quantity...Size (in.
SPECIFICATIONS — 579F180-300 (cont) UNIT SIZE FURNACE SECTION Rollout Switch Cutout Temp (F)† Burner Orifice Diameter (in. ...drill size) Natural Gas Liquid Propane Pilot Orifice Diameter (in. ...drill size) Natural Gas Low Heat 180 High Heat 216 Low Heat Low Heat High Heat Low Heat High Heat 190 190 190 190 190 190 190 Std Alt .113...33 — .113...33 — .113...33 — .113...33 — .113...33 — .113...33 — .113...33 — Std 0.55...54 — .055...54, .041...59 — .055...54, .041..59 — .055...
SELECTION PROCEDURE (with 579F180270 example) IV DETERMINE FAN SPEED AND POWER REQUIREMENTS AT DESIGN CONDITIONS: Before entering the Air Delivery tables on pages 30-48, calculate the total static pressure required based on unit components. From the given and the Pressure Drop table on page 50, find: External static pressure 0.80 in. wg Economizer 0.04 in. wg I DETERMINE COOLING AND HEATING REQUIREMENTS AT DESIGN CONDITIONS: Given: Total Cooling Capacity Required . . . . . . . .
GROSS COOLING CAPACITIES 580D036 (3 TON) Air Entering Evaporator Cfm BF 900 0.11 1200 0.14 1500 0.17 Ewb (F) 72 67 62 72 67 62 72 67 62 75 Capacity MBtuh Total Sensible 42.8 20.0 38.9 24.5 35.0 28.7 44.8 21.8 40.8 27.5 37.0 32.8 45.8 23.0 41.9 30.0 38.2 36.0 Compressor kW 2.91 2.81 2.70 2.99 2.88 2.78 3.02 2.92 2.82 Air Entering Condenser (F) 85 Capacity MBtuh Compressor kW Total Sensible 40.8 19.4 3.14 36.9 23.7 3.01 33.3 27.9 2.90 42.5 21.0 3.20 38.7 26.8 3.08 35.0 31.8 2.97 43.6 22.6 3.24 39.
GROSS COOLING CAPACITIES (cont) 580D060 (5 TON) Air Entering Evaporator Cfm BF 1500 0.07 2000 0.09 2500 0.12 Ewb (F) 72 67 62 72 67 62 72 67 62 75 Capacity MBtuh Total Sensible 71.0 33.9 63.8 41.5 55.4 47.9 74.5 37.4 67.2 47.4 59.2 55.8 76.5 40.6 69.7 52.8 62.1 61.8 Compressor kW 5.04 4.82 4.62 5.20 4.97 4.76 5.29 5.06 4.87 Air Entering Condenser (F) 85 Capacity MBtuh Compressor kW Total Sensible 69.2 61.0 54.2 72.9 65.6 57.2 75.2 68.1 61.5 33.4 40.5 47.3 37.0 46.9 54.9 40.1 52.3 61.3 5.50 5.
GROSS COOLING CAPACITIES (cont) 580D090 (71⁄2 TON) Air Entering Evaporator Cfm BF 2250 0.07 2800 0.09 3000 0.10 3750 0.12 Ewb (F) 72 67 62 72 67 62 72 67 62 72 67 62 75 Capacity MBtuh Total Sensible 102.8 49.4 94.8 61.8 86.2 73.2 105.8 52.6 98.2 67.8 90.0 81.6 106.4 53.6 99.0 69.8 90.8 84.0 109.2 58.2 101.6 77.4 93.6 92.2 Compressor kW 7.14 6.82 6.50 7.28 6.98 6.68 7.32 7.04 6.72 7.46 7.18 6.86 Air Entering Condenser (F) 85 Capacity MBtuh Compressor kW Total Sensible 98.6 48.0 7.66 90.2 60.2 7.
GROSS COOLING CAPACITIES (cont) 580D102 (81⁄2 TON) Air Entering Evaporator Cfm BF 2550 0.080 3000 0.10 3400 0.110 4250 0.135 Ewb (F) 72 67 62 72 67 62 72 67 62 72 67 62 75 Capacity MBtuh Total Sensible 116.6 71.9 108.4 61.9 99.0 75.9 119.2 75.2 111.3 65.1 101.8 81.4 120.1 80.5 112.8 68.0 103.6 85.6 122.3 32.7 114.8 73.9 106.3 94.4 Compressor kW 7.77 7.57 7.38 7.86 10.68 7.44 7.89 6.72 7.51 7.97 7.80 7.60 Air Entering Condenser (F) 85 Capacity MBtuh Compressor kW Total Sensible 113.3 104.2 94.
GROSS COOLING CAPACITIES (cont) 580D150 (121⁄2 TON) Air Entering Evaporator Cfm BF 3750 0.08 4500 0.09 5000 0.10 6250 0.12 Ewb (F) 72 67 62 72 67 62 72 67 62 72 67 62 75 Capacity MBtuh Total Sensible 175.6 85.7 162.2 107.3 149.2 128.0 181.0 91.4 167.5 116.2 154.2 140.3 182.9 94.2 170.2 122.2 156.4 146.5 187.2 102.1 174.7 135.3 161.8 160.7 Compressor kW 11.16 10.85 10.57 11.32 11.00 10.69 11.37 11.07 10.73 11.49 11.19 10.
GROSS COOLING CAPACITIES (cont) 579F180 (15 TON) Air Entering Evaporator Cfm BF 4500 0.08 5250 0.10 6000 0.11 6750 0.12 7500 0.14 Ewb (F) 72 67 62 72 67 62 72 67 62 72 67 62 72 67 62 75 Capacity MBtuh Total Sensible 212.0 101.0 195.0 126.0 179.0 148.0 216.0 105.0 200.0 133.0 183.0 161.0 219.0 109.0 204.0 141.0 187.0 170.0 223.0 115.0 205.0 152.0 189.0 179.0 224.0 118.0 207.0 157.0 193.0 187.0 Compressor kW 15.20 14.70 14.20 15.40 14.90 14.90 15.50 15.10 14.60 15.70 15.10 14.70 15.70 15.20 14.
GROSS COOLING CAPACITIES (cont) 579F216 (18 TON) Air Entering Condenser (F) Air Entering Evaporator Cfm BF 5400 0.035 6300 0.045 7200 0.055 8100 0.065 9000 0.075 Ewb (F) 72 67 62 72 67 62 72 67 62 72 67 62 72 67 62 75 Capacity MBtuh Total Sensible 233.0 116.7 215.0 148.3 198.8 178.0 237.0 123.8 221.0 159.2 204.5 193.0 240.0 132.9 223.0 170.1 209.6 206.1 239.0 141.6 227.0 180.3 214.6 214.4 241.0 148.1 227.0 191.2 217.0 217.0 Compressor kW 15.42 14.99 14.54 15.57 15.15 14.73 15.66 15.26 14.
AIR DELIVERY — VERTICAL DISCHARGE UNITS 580D036 (3 TON) Standard Direct Drive Motor Low Speed Airflow (Cfm) Esp 0.49 0.42 0.37 0.33 0.27 0.20 0.16 900 1000 1100 1200 1300 1400 1500 208 V Bhp 0.21 0.23 0.24 0.26 0.27 0.29 0.30 Watts 253 270 287 304 321 338 355 Esp 0.50 0.43 0.38 0.33 0.28 0.23 0.18 High Speed 230, 460, 575 V Bhp Watts 0.23 277 0.25 292 0.26 307 0.27 323 0.29 338 0.30 354 0.31 369 Esp 0.51 0.43 0.39 0.34 0.28 0.25 0.20 208 V Bhp 0.26 0.27 0.28 0.29 0.31 0.32 0.
AIR DELIVERY — VERTICAL DISCHARGE UNITS (cont) 580D048 (4 TON) Standard Direct Drive Motor Low Speed Airflow (Cfm) 208 V Bhp 0.41 0.42 0.45 0.47 0.49 0.52 0.54 0.56 — Esp 0.68 0.61 0.53 0.45 0.36 0.26 0.15 0.04 — 1200 1300 1400 1500 1600 1700 1800 1900 2000 Watts 458 471 503 536 557 584 610 629 — Esp 0.74 0.67 0.59 0.51 0.42 0.32 0.22 0.11 — High Speed 230, 460, 575 V Bhp Watts 0.45 506 0.46 521 0.49 556 0.52 593 0.54 616 0.57 646 0.60 674 0.62 696 — — Esp 0.74 0.66 0.59 0.52 0.45 0.37 0.30 0.23 0.
AIR DELIVERY — VERTICAL DISCHARGE UNITS (cont) 580D060 (5 TON) Airflow (Cfm) 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 Esp 0.69 0.49 0.29 0.09 — — — — — — — Low Speed 208 V 230, Bhp Watts Esp 0.67 750 1.01 0.70 780 0.85 0.73 810 0.70 0.75 839 0.54 — — 0.39 — — 0.23 — — 0.08 — — — — — — — — — — — — 460, 575 V Bhp Watts 0.71 791 0.74 824 0.77 857 0.80 891 0.83 924 0.86 957 0.89 990 — — — — — — — — Esp 1.00 0.85 0.70 0.55 0.40 0.25 0.
AIR DELIVERY — VERTICAL DISCHARGE UNITS (cont) 580D072 (6 TON) Airflow (Cfm) 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 3000 Rpm 942 982 1022 1063 1104 1130 1174 1201 1246 1285 1304 1345 1378 0.1 Bhp 0.70 0.80 0.91 0.99 1.13 1.26 1.37 1.48 1.62 1.75 1.87 2.07 2.26 Watts 646 739 835 916 1039 1156 1258 1361 1491 1613 1726 1910 2084 Rpm 978 1023 1068 1115 1159 1202 1237 1272 1320 1361 1402 1446 1489 0.2 Bhp 0.66 0.78 0.90 1.00 1.15 1.29 1.41 1.53 1.68 1.82 1.95 2.16 2.
AIR DELIVERY — VERTICAL DISCHARGE UNITS (cont) 580D090 (71⁄2 TON) Airflow (Cfm) 2200 2250 2300 2400 2500 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750 Rpm 506 514 521 536 551 559 567 582 598 614 630 646 662 679 695 712 729 745 754 0.2 Bhp 0.52 0.55 0.57 0.63 0.69 0.72 0.75 0.83 0.90 0.98 1.07 1.16 1.26 1.36 1.47 1.59 1.71 1.84 1.
AIR DELIVERY — VERTICAL DISCHARGE UNITS (cont) 580D102 (81⁄2 TON) Airflow (Cfm) 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750 3800 3900 4000 4100 4200 4250 4300 Rpm 559 567 582 598 614 630 646 662 679 695 712 729 745 754 762 779 796 813 830 839 847 0.2 Bhp 0.72 0.75 0.83 0.90 0.98 1.07 1.16 1.26 1.36 1.47 1.59 1.71 1.84 1.91 1.98 2.12 2.27 2.42 2.59 2.68 2.
AIR DELIVERY — VERTICAL DISCHARGE UNITS (cont) 580D120 (10 TON) Airflow (Cfm) 3000 3100 3200 3300 3400 3500 3600 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000 Rpm 592 607 622 638 653 669 684 700 715 731 747 763 778 794 810 826 842 858 874 890 906 0.2 Bhp 0.76 0.83 0.90 0.98 1.06 1.15 1.24 1.33 1.43 1.54 1.64 1.76 1.88 2.00 2.13 2.27 2.41 2.55 2.70 2.86 3.03 0.4 Bhp 0.93 1.01 1.09 1.17 1.26 1.35 1.44 1.54 1.64 1.74 1.85 1.97 2.10 2.23 2.37 2.52 2.67 2.83 2.99 3.16 3.
AIR DELIVERY — VERTICAL DISCHARGE UNITS (cont) 580D150 (121⁄2 TON) Airflow (Cfm) 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000 5100 5200 5300 5400 5500 5600 5700 5800 5900 6000 6100 6200 Rpm 729 745 761 777 793 810 826 842 859 876 892 909 926 942 959 976 993 1010 1027 1043 1060 1077 1094 1111 1128 1145 0.2 Bhp 1.36 1.46 1.56 1.67 1.79 1.91 2.04 2.17 2.31 2.45 2.60 2.77 2.93 3.11 3.29 3.47 3.67 3.87 4.07 4.29 4.51 4.74 4.98 5.22 5.48 5.
AIR DELIVERY — HORIZONTAL DISCHARGE UNITS 580D036 (3 TON) Standard Direct Drive Motor Low Speed Airflow (Cfm) Esp 0.54 0.49 0.43 0.39 0.33 0.26 0.21 900 1000 1100 1200 1300 1400 1500 208 v Bhp 0.21 0.23 0.24 0.26 0.27 0.29 0.30 Watts 253 270 287 304 321 338 355 Esp 0.57 0.51 0.45 0.40 0.35 0.28 0.23 High Speed 230, 460, 575 v Bhp Watts 0.23 277 0.25 292 0.26 307 0.27 323 0.29 338 0.30 354 0.31 369 Esp 0.55 0.52 0.46 0.38 0.35 0.29 0.24 208 v Bhp 0.26 0.27 0.28 0.29 0.31 0.32 0.
AIR DELIVERY — HORIZONTAL DISCHARGE UNITS (cont) 580D048 (4 TON) Standard Direct Drive Motor Low Speed Airflow (Cfm) 208 v Bhp 0.41 0.42 0.45 0.47 0.49 0.52 0.54 0.56 — Esp 0.75 0.68 0.60 0.51 0.42 0.32 0.21 0.09 — 1200 1300 1400 1500 1600 1700 1800 1900 2000 Watts 458 471 503 536 557 584 610 629 — Esp 0.81 0.74 0.66 0.58 0.49 0.39 0.29 0.18 0.06 High Speed 230, 460, 575 v Bhp Watts 0.45 506 0.46 521 0.49 556 0.52 593 0.54 616 0.57 646 0.60 674 0.62 696 0.65 731 Esp 0.87 0.79 0.71 0.64 0.56 0.48 0.
AIR DELIVERY — HORIZONTAL DISCHARGE UNITS (cont) 580D060 (5 TON) Airflow (Cfm) 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 Esp 0.74 0.54 0.34 0.14 — — — — — — — Low Speed 208 V 230, Bhp Watts Esp 0.67 750 1.06 0.70 780 0.90 0.73 810 0.75 0.75 839 0.59 — — 0.44 — — 0.28 — — 0.13 — — — — — — — — — — — — 460, 575 V Bhp Watts 0.71 791 0.74 824 0.77 857 0.80 891 0.83 924 0.86 957 0.89 990 — — — — — — — — Esp 1.07 0.92 0.77 0.62 0.47 0.32 0.17 0.
AIR DELIVERY — HORIZONTAL DISCHARGE UNITS (cont) 580D072 (6 TON) Airflow (Cfm) 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 3000 Rpm 885 928 971 1015 1060 1104 1138 1183 1210 1254 1274 1318 1362 0.1 Bhp 0.63 0.73 0.84 0.97 1.10 1.25 1.30 1.43 1.58 1.76 1.82 1.95 2.20 Watts 623 700 787 891 998 1123 1165 1275 1404 1560 1613 1726 1945 Rpm 942 982 1022 1063 1104 1130 1174 1201 1246 1285 1304 1345 1378 0.2 Bhp 0.73 0.83 0.94 1.10 1.20 1.27 1.37 1.50 1.67 1.80 1.85 2.05 2.
AIR DELIVERY — HORIZONTAL DISCHARGE UNITS (cont) 580D090 (71⁄2 TON) Airflow (Cfm) 2200 2250 2300 2400 2500 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750 Rpm 499 507 513 528 542 550 557 573 588 604 620 636 652 668 684 701 717 733 742 0.2 Bhp 0.50 0.53 0.55 0.60 0.66 0.69 0.72 0.79 0.86 0.94 1.02 1.11 1.21 1.31 1.41 1.53 1.65 1.77 1.
AIR DELIVERY — HORIZONTAL DISCHARGE UNITS (cont) 580D102 (81⁄2 TON) Airflow (Cfm) 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750 3800 3900 4000 4100 4200 4250 4300 Rpm 550 557 573 588 604 620 636 652 668 684 701 717 733 742 750 767 783 800 817 826 834 0.2 Bhp 0.69 0.72 0.79 0.86 0.94 1.02 1.11 1.21 1.31 1.41 1.53 1.65 1.77 1.84 1.90 2.04 2.18 2.34 2.49 2.58 2.
AIR DELIVERY — HORIZONTAL DISCHARGE UNITS (cont) 580D120 (10 TON) Airflow (Cfm) 3000 3100 3200 3300 3400 3500 3600 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000 Rpm 552 565 578 591 605 619 633 648 662 677 692 707 722 737 752 768 783 799 814 — — 0.2 Bhp 0.68 0.74 0.81 0.88 0.96 1.04 1.13 1.23 1.33 1.44 1.55 1.67 1.80 1.94 2.08 2.24 2.40 2.56 2.74 — — 0.4 Bhp 0.87 0.93 1.00 1.08 1.16 1.23 1.31 1.39 1.51 1.61 1.73 1.84 1.97 2.09 2.21 2.35 2.50 2.64 2.80 2.90 3.
AIR DELIVERY — HORIZONTAL DISCHARGE UNITS (cont) 580D150 (121⁄2 TON) Airflow (Cfm) 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000 5100 5200 5300 5400 5500 5600 5700 5800 5900 6000 6100 6200 Rpm 677 691 705 720 734 749 764 779 793 808 822 837 852 867 882 896 911 926 940 955 970 985 1000 1015 1030 1046 0.2 Bhp 1.20 1.28 1.37 1.47 1.56 1.66 1.77 1.88 1.99 2.11 2.24 2.37 2.51 2.65 2.79 2.95 3.11 3.27 3.44 3.62 3.80 3.99 4.18 4.39 4.59 4.
AIR DELIVERY — 579F180-300 UNITS 579F180 (15 TON) Airflow (Cfm) 4500 4800 5100 5400 5700 6000 6300 6600 6900 7200 7500 Rpm 801 843 885 927 971 1016 1059 1104 1150 1194 1238 0.2 Bhp 1.05 1.25 1.47 1.71 1.98 2.28 2.60 2.96 3.35 3.77 4.23 Watts 933 1110 1306 1519 1758 2025 2309 2629 2975 3348 3758 Rpm 890 928 968 1008 1049 1091 1133 1174 1218 1260 — 0.4 Bhp 1.26 1.47 1.70 1.95 2.24 2.55 2.89 3.26 3.67 4.10 — Standard Belt-Drive Motor; 208/230-V and 460 V Units External Static Pressure (in. wg) 0.6 0.
AIR DELIVERY — 579F180-300 UNITS (cont) 579F216 (18 TON) Airflow (Cfm) 5000 5500 6000 6500 7000 7200 7500 8000 8500 9000 Rpm 669 717 767 817 869 889 920 973 1026 1079 0.2 Bhp 1.10 1.40 1.80 2.20 2.70 2.94 3.30 3.90 4.60 5.40 Watts 1019 1292 1617 1992 2427 2624 2919 3476 4102 4800 Rpm 772 813 858 903 950 969 998 1047 1097 — 0.4 Bhp 1.40 1.80 2.20 2.60 3.10 3.34 3.70 4.30 5.
AIR DELIVERY — 579F180-300 UNITS (cont) 579F300 (25 TON) Airflow (Cfm) 7,500 8,000 8,500 9,000 9,500 10,000 10,500 11,000 11,250 Rpm 962 1017 1072 1128 1185 1241 1298 1355 1384 0.2 Bhp 3.39 4.04 4.76 5.57 6.47 7.45 8.54 9.72 10.36 Watts 3123 3717 4385 5129 5955 6865 7865 8956 9540 Rpm 1039 1091 1143 1196 1250 1304 1359 1414 1441 0.4 Bhp 3.81 4.48 5.23 6.07 6.99 8.00 9.12 10.33 10.
579F180-300 HORIZONTAL SUPPLY/RETURN FAN PERFORMANCE WITH 389210-201 OR 389211-201 HIGH STATIC REGAIN ADAPTER NOTE: The 389210-201 or 389211-201 horizontal supply/return adapter accessory improves 579F180-300 fan performance by increasing external static pressure by amount shown above. NOTE: The 389210-201 or 389211-201 high static regain adapter accessory may be used to provide horizontal supply/return.
ACCESSORY/FIOP ECONOMIZER STATIC PRESSURE DROP (in. wg) CFM VARISLIDE™ ECONOMIZER PRESSURE DROP 900 1,200 1,400 1,600 1,800 2,000 2,200 2,400 2,600 2,200 2,500 3,000 3,500 4,000 4,500 5,000 5,500 6,000 4,000 5,000 6,000 7,500 6,000 7,200 9,000 10,000 11,250 .05 .05 .05 .05 .05 .05 .05 .05 .05 .02 .02 .03 .04 .05 .06 .07 .08 .09 .03 .05 .07 .10 .07 .09 .11 .12 .13 UNIT VOLTAGE UNIT 580D036-072 All 580D090-150 All 579F180 All 579F216-300 All PARABLADE ECONOMIZER PRESSURE DROP .08 .10 .17 .26 .
ELECTRICAL DATA — 580D036-150 UNIT 580D 036 (3 Tons) NOMINAL VOLTAGE (60 Hz) IFM TYPE 208/230 (single phase) Std Alt Std Alt Std Alt Std Alt Std Alt Std Alt Std Alt Std Alt Std Alt Std Alt Std Alt Std Alt 208/230 (3 phase) 460 (3 phase) 575 (3 phase) 208/230 (single phase) 048 (4 Tons) 208/230 (3 phase) 460 (3 phase) 575 (3 phase) 208/230 (single phase) 060 (5 Tons) 208/230 (3 phase) 460 (3 phase) 575 (3 phase) 072 (6 Tons) 090 (71⁄2 Tons) 102 (81⁄2 Tons) 208/230 (3 phase) 460 (3 phase) 575 (3
ELECTRICAL DATA — 579F180-300 UNIT 579F VOLTAGE RANGE COMPRESSOR NO. 1 NO. 2 OFM NOMINAL VOLTAGE (60 Hz) Min Max RLA LRA RLA LRA Qty 208/230 (3 phase) 187 254 61.0 266 — — 3 460 (3 phase) 414 508 28.0 120 — — 3 575 (3 phase) 518 632 23.0 96 — — 3 208/230 (3 phase) 187 254 28.3 205 25.0 185 3 460 (3 phase) 414 508 14.4 104 12.4 89 3 575 (3 phase) 518 632 11.4 78 10.4 78 3 208/230 (3 phase) 187 254 34.5 239 28.
OPERATING SEQUENCE (cont) When first-stage thermostat calls for heat, time-delay relay for evaporator fan begins timer sequence. Induced-draft relay closes, and induced-draft motor starts. Pressure switch closes and pilot valve no. 1 opens, allowing gas to flow to the first-stage pilot. Spark ignitor ignites pilot flame. Sensor detects flame and the main gas valve no. 1 opens. Gas flows to main burners and first-stage burners ignite. Spark ignitor turns off.
TYPICAL WIRING SCHEMATIC — 580D036-150 See Legend on page 57.
TYPICAL WIRING SCHEMATIC — 579F180-300 See Legend on page 57.
TYPICAL INSTALLATION — 580D090-150 Vertical Discharge Ducting NEC — National Electrical Code Horizontal Discharge Ducting 56
TYPICAL INSTALLATION — 579F180-300 NEC — National Electrical Code NOTES: 1. Illustration shown is a general guide only and is not intended to include all details for any specific installation. 2. Installation must comply with all applicable codes.
APPLICATION DATA 1. Ductwork (580D036-150) — Secure vertical discharge ductwork to roof curb. For horizontal discharge applications, attach ductwork to unit, or field-supplied flanges can be attached to horizontal discharge openings and all ductwork attached to flanges. 14. High Altitude — A change to the gas orifice may be required at high altitudes. Refer to Altitude Compensation charts on page 61. 2. Ductwork (579F180-300) — Ductwork should be attached to the curb on all units.
APPLICATION DATA (cont) NOTE: Dimensions A, A8 and B, B8 are obtained from fieldsupplied ceiling diffuser. NOTE: Do not drill in this area; damage to basepan may result in water leak. Shaded area indicates block-off panels.
APPLICATION DATA (cont) EVAPORATOR-FAN MOTOR PERFORMANCE UNIT EVAPORATOR-FAN MOTOR Standard 580D036 Alternate Standard 580D048 Alternate Standard 580D060 Alternate 580D072 Standard 580D090 Standard 580D102 Standard Standard 580D120 Alternate Standard 580D150 Alternate 579F180 Standard 579F216 Standard 579F240 Standard 579F300 Standard UNIT VOLTAGE 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 5
APPLICATION DATA (cont) Varislide™ Economizer Barometric Relief Damper Characteristics — 580D036-150 Parablade Economizer Barometric Relief Damper Characteristics — 580D090-150 ALTITUDE COMPENSATION* — 036-072 UNITS ELEVATION (Ft) 0-2,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 13,000 14,000 72,000 AND 115,000 BTUH NOMINAL INPUT Natural Liquid Gas Propane Orifice Orifice Size† Size† 33 43 34 43 35 44 36 44 36 44 37 45 37 45 38 46 39 47 41 48 43 48 44 49 44 49 45 50 150,000
APPLICATION DATA (cont) ALTITUDE COMPENSATION* — 180-300 UNITS ALTITUDE COMPENSATION* — 090-150 UNITS ELEVATION (Ft) 0-2,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 13,000 14,000 125,000, 180,000, AND 224,000 BTUH NOMINAL INPUT Natural Liquid Gas Propane Orifice Orifice Size† Size† 31 41 32 42 32 42 32 42 33 43 34 43 35 44 36 44 37 45 38 46 39 47 40 47 41 48 42 48 ELEVATION (Ft) 250,000 BTUH NOMINAL INPUT Natural Gas Orifice Size† 30 30 31 32 33 34 35 36 37 38 39 40 41 42
ENGINEERS’ SPECIFICATION GUIDE — MODELS 580D036-150 (3 TO 121⁄2 TONS) FILTER SECTION: Filter section shall consist of factoryinstalled low velocity, 2-in. thick fiberglass throwaway filters of commercially available sizes. Filter access panel shall be easy, tool-less access. CONTROLS: Unit shall be complete with self-contained lowvoltage control circuit. Safeties shall include compressor overtemperature and overcurrent.
ENGINEERS’ SPECIFICATION GUIDE — MODELS 579F180-300 (15 TO 25 TONS) GENERAL: Furnish and install single-package, outdoor rooftopmounted, electrically controlled, heating and cooling unit utilizing reciprocating compressor(s) for cooling and gas combustion for heating duty. Unit shall discharge supply air vertically or horizontally as shown on the contract drawings. Nominal unit electrical characteristics shall be v, 3 ph, 60 Hz.