Typical Piping and Wiring
A09230
A09231
Application Data
Condensate trap A 2-in. (50.8 mm) condensate trap must be field
supplied.
Ductwork Secure downflow discharge ductwork to roof curb. For
horizontal discharge applications, attach ductwork to unit with flanges.
To convert a unit to downflow discharge Units are equipped with
factory-installed inserts in the down-flow openings. Removal of the
inserts is similar to removing an electrical knock-out. Use the duct cover
to seal the horizontal discharge openings in the unit. Units installed in
horizontal discharge orientation do not require duct covers.
Airflow — Units are draw-thru in the cooling mode and blow-thru in the
heating mode.
Maximum cooling airflow To minimize the possibility of
condensate blow-off from the evaporator, airflow through the units
should not exceed 450 CFM per ton.
Minimum cooling airflow — Minimum cooling airflow is 350 cfm per
ton.
Minimum ambient cooling operation temperature All standard
units have a minimum ambient operating temperature of 40_F (4_C).
With accessory low ambient temperature kit, units can operate at
temperatures down to 0_F (-17_C).
Minimum temperature Air entering the heat exchanger in heating
mode must be a minimum of 50_F (10_C) continuous and/or 45_F (7_C)
intermittent.
ROOF
RETURN-AIR
FLEXIBLE DUCT
CEILING
CONCENTRIC DIFFUSER BOX
(FIELD-SUPPLIED)
SUPPLY-AIR
FLEXIBLE DUCT
ROOF-MOUNTING
CURB
INDOOR
THERMOSTAT
DISCONNECT
PER NEC*
FROM
POWER
SOURCE
RETURN
AIR
TOP COVER
FROM
GAS LINE
*NEC - NATIONAL ELECTRICAL CODE