COMMERCIAL AIR-COOLED CONDENSING UNITS WITH 524A AIR-HANDLING UNITS Models 566D, 566E, 569D, 569F, 576C with 524A 6 to 20 Tons 569D072-120 576C120 569F120 524A072-300 566D150-240 566E150-240 FEATURES/BENEFITS These dependable split systems match Bryant’s indoor-air handlers and direct-expansion coils with outdoor condensing units for a wide selection of commercial cooling solutions.
Thermal insulation contains an EPA-registered immobilized anti-microbial agent to inhibit the growth of bacteria and fungi. The pitched, non-corroding drain pan can be adjusted for a right- or left-hand connection to suit many applications and provide positive drainage and to prevent standing condensate. The 524A accessory economizer can provide ventilation air to improve indoor air quality by using demand control ventilation.
ARI* CAPACITY RATINGS CONDENSING UNIT SYSTEM† AIR HANDLER/ INDOOR COIL Net Cap.
OPTIONS AND ACCESSORIES 566D, 566E, 569D, 569F, 576C FACTORY-INSTALLED OPTIONS Dura-Shield Condenser Coils offer several options to match coil protection to site conditions for optimum durability. See table below. Consult your Bryant representative for further information. E-Coated Aluminum-Fin Coils have a flexible and durable epoxy coating uniformly applied to all coil surfaces.
OPTIONS AND ACCESSORIES (cont) 524A-B, C FACTORY-INSTALLED OPTIONS Alternate Fan Motors and Drives are available to provide the widest possible range of performance. High-Capacity 4-Row Coils are available to provide increased latent and sensible capacities (524A-C). Prepainted Steel Units are available from the factory for applications that require painted units. Units are painted with American Sterling Gray color.
OPTIONS AND ACCESSORIES (cont) HOT WATER OR STEAM COIL DISCHARGE PLENUM RETURN-AIR GRILLE SUBBASE FAN COIL UNIT FAN COIL UNIT 524A with Discharge Plenum, Return Grille, and Subbase 524A with Hot Water or Steam Coil ECONOMIZER FAN COIL UNIT 524A with Economizer 524A with Condensate Trap 6
SELECTION PROCEDURE To determine combination ratings for 569D/F, 576C and 566D/E units matched with 524A Series air handlers, follow these steps: I DETERMINE COOLING LOAD, EVAPORATOR-AIR TEMPERATURE, AND QUANTITY. Given: Total Cooling Capacity Required (TC). . . . . . . . . . . . . . . . . . . . . . 127,000 Btuh Sensible Heat Capacity Required (SHC) . . . . . . . . . . . . . . . . . . . . . 95,000 Btuh Compressor Type . . . . . . . . . . . . . . . . . . . . . . . . . . .
CONTROLS OPERATING SEQUENCES 569D072-120, 576C120 — At start-up, the thermostat calls for cooling. With all safety devices satisfied, the compressor contactor and fan contactor energize, causing the compressor and outdoor-fan motor to operate. Thermostat contacts energize, allowing the field-supplied and field-installed indoorfan contactor to function. A field-supplied and field-installed liquid line valve also opens, allowing the system to function in Cooling mode.
TYPICAL WIRING SCHEMATICS NOTES: 1. If any of the original wire furnished must be replaced, it must be replaced with type 90° C wire or its equivalent. 2. Thermostat: HH07AT170, 172, 174 & P2722783 Subbase: HH93AZ176, 178 & P272-1882, 1883 or HH93AZ177 & 179. 3. Sealed VA for IFC and LLSV is not to exceed 22. 4. Use copper conductors only. 5. TRAN is wired for 230 v unit. If unit is to be run with 200 v power supply, disconnect BLK wire from 230 v tap and connect to 200 v tap. 6.
TYPICAL WIRING SCHEMATICS (cont) LEGEND AHA — Adjustable Heat Anticipator C — Contactor, Compressor CAP — Capacitor CB — Circuit Breaker CC — Cooling Compensator CH — Crankcase Heater COMP — Compressor Motor COTP — Compressor Over Temperature Protection EQUIP — Equipment GND — Ground HPS — High-Pressure Switch IFC — Indoor-Fan Contactor LLSV — Liquid Line Solenoid Valve LPS — Low-Pressure Switch NEC — National Electrical Code OFM — Outdoor-Fan Motor OL — Overload Relay R — Relay TB — Terminal Block TC — T
MODEL NUMBER NOMENCLATURE P X 072 000 –– 569D — Commercial Air-Cooled Condensing Unit With Scroll Compressor 569F — Dual Circuit Commercial Air-Cooled Condensing Unit With Scroll Compressor Factory-Installed Options* Voltage Designation E — 460-3-60 P — 208/230-3-60 T — 575-3-60 Heating X — None Nominal Tons Cooling 072 — 6 (569D Only) 090 — 7-1/2 (569D Only) 120 — 10 (569D, 569F) Heating Capacity 000 — No Heat 576C P X 120 000 –– 576C — Commercial Air-Cooled Condensing Unit With Semi-Hermeti
50TFQ004-012 569D072-120, 576C120, 569F120 PHYSICAL DATA 569D072-120, 576C120, 569F120 UNITS UNIT NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Aluminum Coils (Standard) Copper Coils (Optional) RREFRIGERANT TYPE* Operating Charge, Typical (lb)† Shipping Charge (lb) COMPRESSOR Type Qty...Model Oil Charge (oz) No. Cylinders Speed (rpm) CONDENSER FAN Qty...Rpm Motor HP (rpm) Diameter Nominal Airflow (Cfm Total) Watts (Total) CONDENSER COIL (Qty) Face Area (sq ft total) Rows...Fins/in.
DIMENSIONS 569D072 569D090 569D120 576C120 Standard Unit Weight lb kg 300 136 383 174 430 195 575 261 Corner W lb kg 62 28 86 39 84 38 55 25 ALUMINUM COIL Corner X Corner Y Corner Z lb kg lb kg lb kg 103 47 62 28 72 33 123 56 85 39 89 40 166 75 66 30 114 52 265 120 88 40 167 76 Center of Gravity X mm [in.] Y mm [in.] 831.9 [32.75] 641.4 [25.25] 822.3 [32.38] 635.0 [25.00] 812.8 [32.00] 676.3 [26.63] 927.1 [36.50] 647.7 [25.
50TFQ004-012 569D072-120, 576C120, 569F120 DIMENSIONS (cont) OUTDOOR COIL CORNER “A” CORNER “B” 1162.7 [45.78] Y OUTDOOR COIL O 34.5 [1.36] POWER ENTRY WITH 50.0/58.0/65.0 K.O. CORNER “C” X CORNER “D” ACCESS PANEL TOP VIEW ELECTRICAL DISCONNECT LOCATION LIQUID CONNECTION (SEE CHART FOR SIZE) CONTROL BOX ACCESS PANEL CONVENIENCE OUTLET LOCATION OUTDOOR COIL SUCTION CONNECTION (SEE CHART FOR SIZE) OUTDOOR COIL 582.5 [22.93] 167.5 [6.59] BOTTOM OF UNIT 111.7 116.7 FORK TRUCK SLOTS [4.40] [4.
PERFORMANCE DATA 569D072 576C120 SST (F) 25 30 35 40 45 50 TC kW SDT TC kW SDT TC kW SDT TC kW SDT TC kW SDT TC kW SDT 80 53.6 4.24 101.0 59.1 4.33 102.0 64.9 4.42 104.0 71.0 4.53 106.0 77.4 4.65 107.0 84.2 4.78 109.0 Air Temperature Entering Condenser (F) 85 95 100 105 52.3 49.4 48.0 46.5 4.49 5.02 5.31 5.60 106.0 115.0 120.0 125.0 57.6 54.6 53.0 51.5 4.57 5.10 5.39 5.69 107.0 117.0 122.0 126.0 63.3 60.1 58.4 56.7 4.67 5.20 5.49 5.79 109.0 118.0 123.0 128.0 69.3 65.8 64.1 62.3 4.77 5.31 5.60 5.90 110.
50TFQ004-012 569D072-120, 576C120, 569F120 PERFORMANCE DATA (cont) COMBINATION RATINGS* UNIT 569D072 569D072/524A-C072 WITH HIGH-CAPACITY 4-ROW COIL Temp (F) Air Entering Condenser (Edb) 80 85 95 100 105 115 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 72 80.7 40.8 4.71 79.3 40.3 4.99 76.7 39.3 5.53 75.2 38.8 5.84 73.8 38.2 6.15 70.9 37.2 6.77 Evaporator Air — Cfm 2400 Evaporator Air — Ewb (F) 57 62 67 72 72.0 72.6 77.7 84.1 72.0 70.5 58.6 45.5 4.55 4.57 4.66 4.78 71.0 71.4 76.3 82.6 71.
PERFORMANCE DATA (cont) UNIT 569D072 (cont) 569D072/524A-C090 WITH HIGH-CAPACITY 4-ROW COIL* Temp (F) Air Entering Condenser (Edb) 80 85 95 100 105 115 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 72 84.8 45.1 4.79 83.3 44.6 5.07 80.4 43.5 5.61 78.8 43.0 5.92 77.3 42.5 6.23 74.2 41.4 6.85 Evaporator Air — Cfm 3000 Evaporator Air — Ewb (F) 57 62 67 72 77.7 77.7 81.3 87.6 77.7 77.7 67.0 50.9 4.66 4.66 4.73 4.85 76.5 76.5 79.8 86.1 76.5 76.5 66.4 50.3 4.93 4.93 5.00 5.12 74.1 74.1 76.9 82.
50TFQ004-012 569D072-120, 576C120, 569F120 PERFORMANCE DATA (cont) COMBINATION RATINGS (cont) UNIT 569D090 569D090/524A-C072 WITH HIGH-CAPACITY 4-ROW COIL* Temp (F) Air Entering Condenser (Edb) 80 85 95 100 105 115 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 1800 57 78.9 77.9 5.75 77.6 77.0 6.10 75.1 75.1 6.80 73.9 73.8 7.20 72.6 72.6 7.59 70.1 70.1 8.38 62 85.1 69.0 5.78 83.6 68.3 6.13 80.8 66.8 6.82 79.2 66.0 7.21 77.6 65.3 7.60 74.5 63.7 8.38 67 92.8 59.0 5.85 91.3 58.3 6.20 88.3 56.
PERFORMANCE DATA (cont) UNIT 569D090 (cont) 569D090/524A-C090 WITH HIGH-CAPACITY 4-ROW COIL* Temp (F) Air Entering Condenser (Edb) 80 85 95 100 105 115 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 2205 57 86.0 86.0 5.78 84.8 84.8 6.14 82.3 82.3 6.85 81.0 81.0 7.24 79.6 79.6 7.63 77.0 77.0 8.41 62 90.4 78.0 5.83 88.9 77.3 6.18 85.8 75.8 6.88 84.2 75.0 7.26 82.5 74.1 7.65 79.2 72.5 8.42 67 98.0 65.6 5.91 96.4 64.9 6.26 93.1 63.5 6.96 91.3 62.8 7.36 89.6 62.1 7.75 86.0 60.6 8.53 72 106.
50TFQ004-012 569D072-120, 576C120, 569F120 PERFORMANCE DATA (cont) COMBINATION RATINGS (cont) UNIT 569D120 569D120/524A-C120 WITH HIGH-CAPACITY 4-ROW COIL Temp (F) Air Entering Condenser (Edb) 80 85 95 100 105 115 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 3000 57 117.0 117.0 8.34 115.0 115.0 8.72 112.0 112.0 9.49 110.0 110.0 9.90 108.0 108.0 10.30 104.0 104.0 11.10 62 122.0 106.0 8.48 120.0 104.0 8.85 116.0 102.0 9.60 113.0 101.0 10.00 111.0 100.0 10.40 106.0 97.7 11.20 67 132.0 88.
PERFORMANCE DATA (cont) UNIT 569D120 (cont) 569D120/524A-C150 WITH HIGH-CAPACITY 4-ROW COIL Temp (F) Air Entering Condenser (Edb) 80 85 95 100 105 115 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 3750 57 126.0 126.0 8.60 124.0 124.0 8.98 120.0 120.0 9.74 118.0 118.0 10.20 116.0 116.0 10.60 112.0 112.0 11.40 62 129.0 119.0 8.68 127.0 118.0 9.05 122.0 116.0 9.80 120.0 114.0 10.20 117.0 113.0 10.60 112.0 110.0 11.40 67 138.0 98.7 8.94 136.0 97.7 9.31 131.0 95.7 10.10 128.0 94.6 10.50 126.
50TFQ004-012 569D072-120, 576C120, 569F120 PERFORMANCE DATA (cont) COMBINATION RATINGS (cont) UNIT 576C120 576C120/524A-C120 WITH HIGH-CAPACITY 4-ROW COIL Temp (F) Air Entering Condenser (Edb) 80 85 95 100 105 115 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 3000 57 113.0 113.0 8.00 111.0 111.0 8.39 106.0 106.0 9.17 104.0 104.0 9.55 102.0 102.0 9.93 97.2 97.2 10.70 62 118.0 104.0 8.12 115.0 102.0 8.51 110.0 99.8 9.28 107.0 98.4 9.65 104.0 97.0 10.00 98.6 94.2 10.80 67 129.0 87.4 8.
PERFORMANCE DATA (cont) UNIT 576C120 (cont) 576C120/524A-C150 WITH HIGH-CAPACITY 4-ROW COIL Temp (F) Air Entering Condenser (Edb) 80 85 95 100 105 115 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 3750 57 122.0 122.0 8.23 120.0 120.0 8.64 115.0 115.0 9.46 113.0 113.0 9.86 110.0 110.0 10.30 105.0 105.0 11.10 62 125.0 117.0 8.28 122.0 116.0 8.69 116.0 113.0 9.50 113.0 111.0 9.89 111.0 109.0 10.30 105.0 105.0 11.10 67 135.0 97.7 8.51 132.0 96.5 8.94 126.0 93.9 9.78 123.0 92.6 10.20 119.0 91.
50TFQ004-012 569D072-120, 576C120, 569F120 PERFORMANCE DATA (cont) COMBINATION RATINGS (cont) UNIT 569F120 569F120/524A-C120 WITH HIGH-CAPACITY 4-ROW COIL Temp (F) Air Entering Condenser (Edb) 80 85 95 100 105 115 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 3000 57 112.0 112.0 7.90 110.0 110.0 8.35 107.0 107.0 9.24 105.0 105.0 9.74 103.0 103.0 10.20 99.7 99.7 11.20 62 116.0 102.0 7.94 114.0 102.0 8.39 110.0 99.6 9.28 108.0 98.6 9.78 106.0 97.5 10.30 102.0 95.5 11.30 67 126.0 85.9 8.
PERFORMANCE DATA (cont) UNIT 569F120 (cont) 569F120/524A-C150 WITH HIGH-CAPACITY 4-ROW COIL Temp (F) Air Entering Condenser (Edb) 80 85 95 100 105 115 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 3750 57 121.0 121.0 8.00 119.0 119.0 8.45 115.0 115.0 9.35 113.0 113.0 9.86 112.0 112.0 10.40 108.0 108.0 11.40 62 123.0 116.0 8.03 121.0 115.0 8.48 117.0 112.0 9.37 115.0 111.0 9.87 113.0 110.0 10.40 108.0 107.0 11.40 67 132.0 96.4 8.14 130.0 95.5 8.59 125.0 93.7 9.50 123.0 92.8 10.0 121.0 91.
50TFQ004-012 569D072-120, 576C120, 569F120 ELECTRICAL DATA 569D072-120, 576C120, 569F120 UNITS FACTORYINSTALLED OPTION UNIT SIZE 072 090 569D 120 576C 120 569F FLA LRA MCA MOCP NEC RLA 120 — — — — — — NONE OR DISCONNECT CONVENIENCE OUTLET NONE OR DISCONNECT CONVENIENCE OUTLET NONE OR DISCONNECT CONVENIENCE OUTLET NONE OR DISCONNECT CONVENIENCE OUTLET NONE OR DISCONNECT CONVENIENCE OUTLET NONE OR DISCONNECT CONVENIENCE OUTLET NONE OR DISCONNECT CONVENIENCE OUTLET NONE OR DISCONNECT CONVENIENCE O
APPLICATION DATA — 569D072-120, 576C090-120, 569F120 Maximum Cooling Outdoor MINIMUM OUTDOOR-AIR OPERATING TEMPERATURE 115 F See Minimum Outdoor-Air Operating Temperature table at right.
50TFQ004-012 569D072-120, 576C120, 569F120 TYPICAL PIPING AND WIRING WEATHERPROOF FUSED DISCONNECT* PER NEC CONDENSING UNIT FIELD SUPPLIED POWER MOISTURE INDICATOR SIGHT GLASS* ELECTRIC HEATER ACCESSORY POWER WIRES LLSV* PIT CH FILTER DRIER* INSULATED VAPOR LINE LIQUID LINE CONTROL WIRES 524A UNIT CONDENSATE DRAIN POWER WIRES INDOOR THERMOSTAT† FUSED DISCONNECT PER NEC TO OPEN SIGHT DRAIN LEGEND LLSV — Liquid Line Solenoid Valve NEC — National Electrical Code TXV — Thermostatic Expansion Valve
GUIDE SPECIFICATIONS — 569D072-120, 576C120 D. Compressor: 1. Compressor shall be of the scroll type (569D) or semi-hermetic reciprocating type (576C). 2. Compressors shall be mounted on vibration isolators. 3. Compressors shall include overload protection. 4. Compressors shall be equipped with a crankcase heater. 5. Compressor shall be equipped with internal high discharge temperature protection (569D072 and 120 only). 6. Compressor shall unload using suction cutoff unloading (576C120 only).
50TFQ004-012 569D072-120, 576C120, 569F120 GUIDE SPECIFICATIONS — 569D072-120, 576C120 (cont) J. Special Features: 1. Low-Ambient Temperature Control Accessory: Low-ambient control shall be available as a factoryinstalled option or a field-installed accessory and shall regulate speed of condenser-fan motor in response to the saturated condensing temperature of the unit.
GUIDE SPECIFICATIONS — 569F120 E. F. G. H. I. J. 31 4. Compressors shall be equipped with a crankcase heater. 5. Compressors shall be equipped with high discharge temperature protection. Condenser Coil: 1. Condenser coil shall be air-cooled and circuited for integral subcooler. 2. Coil shall be constructed of aluminum fins (copper fins optional) mechanically bonded to internally grooved seamless copper tubes which are then cleaned, dehydrated, and sealed.
50TFQ004-012 569D072-120, 576C120, 569F120 GUIDE SPECIFICATIONS — 569F120 (cont) 3. Optional Condenser Coil Materials: a. Pre-Coated Aluminum-Fin Coils: Shall have a durable epoxy-phenolic coating to provide protection in mildly corrosive coastal environments. Coating shall be applied to the aluminum fin stock prior to the fin stamping process to create an inert barrier between the aluminum fin and copper tube. Epoxy-phenolic barrier shall minimize galvanic action between dissimilar metals. b.
MODEL NUMBER NOMENCLATURE 566D E X 150 000 –– Factory-Installed Options* 566D — Commercial Air-Cooled Condensing Unit With Semi-Hermetic Compressor 566E — Dual Circuit Commercial Air-Cooled Condensing Unit With Scroll Compressors Heating Capacity 000 — No Heat Voltage Designation E — 460-3-60 P — 208/230-3-60 T — 575-3-60 Nominal Tons Cooling 150 — 12-1/2 180 — 15 240 — 20 Heating X — None *Contact your local representative for more details.
PHYSICAL DATA 566D/E150-240 50TFQ004-012 566D150-240 UNITS UNIT NOMINAL CAPACITY (tons) OPERATING WEIGHTS (lb) Aluminum-Fin Coil (Standard) Copper-Fin Coil (Optional) REFRIGERANT TYPE* Operating Charge, Typical (lb)† Shipping Charge (lb) COMPRESSOR Qty...Model No. Cylinders Speed (rpm) Oil Charge (pt) Capacity Steps Accessory Standard Unloader Setting (psig) Load Unload Crankcase Heater Watts CONDENSER FANS Qty...Rpm Diameter (in.) Nominal Hp Nominal Airflow (cfm, total) Watts (total) CONDENSER COIL Rows.
PHYSICAL DATA (cont) 566E150-240 UNITS UNIT NOMINAL CAPACITY (tons) OPERATING WEIGHTS (lb) Aluminum-Fin Coil (Standard) Copper-Fin Coil (Optional) REFRIGERANT TYPE* Operating Charge, Typical (lb)† Shipping Charge (lb) COMPRESSOR Qty...Model Speed (rpm) Oil Charge (oz) Crankcase Heater Watts CONDENSER FANS Qty...Rpm Diameter (in.) Nominal Hp Nominal Airflow (cfm, total) Watts (total) CONDENSER COIL Rows...Fins/in.
DIMENSIONS 566D/E150-240 50TFQ004-012 NOTES: 1. Service clearances are as follows: Side (compressor) — 31/2 ft Side (opposite compressor) — 3 ft Ends — 2 ft Top — 5 ft 2. See page 38 for corner weights and unit center of gravity.
DIMENSIONS (cont) NOTES: 1. Service clearances are as follows: Side (compressor) — 31/2 ft (1067 mm) Side (opposite compressor) — 3 ft (914 mm) Ends — 2 ft (610 mm) Top — 5 ft (1524 mm) 2. See page 38 for corner weights and unit center of gravity.
DIMENSIONS (cont) 566D150-240 UNIT 566D 150 180 240 Standard Weight (lb) 779 789 900 UNIT 566D 566D/E150-240 50TFQ004-012 150 180 240 ALUMINUM COIL Operational Weight Points (lb) A B C D E F 70 70 84 177 180 234 68 69 82 100 101 108 261 265 310 103 104 111 CENTER OF GRAVITY (in.
PERFORMANCE DATA CONDENSING UNIT RATINGS 566D150 566E150 SST (F) TC kW SDT TC kW SDT TC kW SDT TC kW SDT TC kW SDT TC kW SDT 25 30 35 40 45 50 80 139.0 12.30 99.5 159.0 12.90 102.0 179.0 13.50 105.0 198.0 14.00 108.0 218.0 14.60 110.0 237.0 15.20 113.0 Air Temperature Entering Condenser (F) 85 95 100 105 134.0 126.0 121.0 117.0 12.70 13.60 14.00 14.40 104.0 114.0 118.0 123.0 154.0 144.0 139.0 134.0 13.40 14.30 14.70 15.20 107.0 116.0 121.0 125.0 173.0 163.0 157.0 152.0 14.00 15.00 15.50 16.00 109.
PERFORMANCE DATA (cont) COMBINATION RATINGS UNIT 566D150 566D150/524A-C150 WITH HIGH CAPACITY 4-ROW COIL Temp (F) Air Entering Condenser (Edb) 80 85 95 100 105 115 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 3750 57 133.0 133.0 9.00 131.0 131.0 9.44 126.0 126.0 10.40 123.0 123.0 10.80 121.0 121.0 11.30 116.0 116.0 12.20 62 139.0 123.0 9.07 136.0 122.0 9.54 130.0 119.0 10.50 127.0 117.0 10.90 124.0 116.0 11.40 118.0 113.0 12.30 67 151.0 103.0 9.27 148.0 102.0 9.75 142.0 99.5 10.70 138.
PERFORMANCE DATA (cont) COMBINATION RATINGS (cont) UNIT 566D150 (cont) 566D150/524A-C180 WITH HIGH CAPACITY 4-ROW COIL Temp (F) Air Entering Condenser (Edb) 80 85 95 100 105 115 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 4500 57 142.0 142.0 9.13 140.0 140.0 9.60 134.0 134.0 10.50 132.0 132.0 11.00 129.0 129.0 11.50 124.0 124.0 12.40 62 145.0 136.0 9.17 142.0 134.0 9.65 136.0 131.0 10.60 133.0 129.0 11.10 130.0 127.0 11.50 124.0 123.0 12.50 67 157.0 114.0 9.37 154.0 112.0 9.86 147.0 109.
PERFORMANCE DATA (cont) COMBINATION RATINGS (cont) UNIT 566D180 566D180/524A-C180 WITH HIGH-CAPACITY 4-ROW COIL Temp (F) Air Entering Condenser (Edb) 80 85 95 100 105 115 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 4500 57 167.0 167.0 13.10 165.0 165.0 13.70 160.0 160.0 14.90 157.0 157.0 15.50 154.0 154.0 16.00 148.0 148.0 17.30 62 177.0 152.0 13.40 174.0 150.0 14.00 167.0 147.0 15.20 164.0 145.0 15.80 160.0 144.0 16.30 153.0 140.0 17.50 67 192.0 128.0 13.90 189.0 127.0 14.50 182.0 123.
PERFORMANCE DATA (cont) COMBINATION RATINGS (cont) UNIT 566D180 (cont) 566D180/524A-C240 WITH HIGH-CAPACITY 4-ROW COIL Temp (F) Air Entering Condenser (Edb) 80 85 95 100 105 115 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 6,000 57 196.0 196.0 13.90 193.0 193.0 14.60 186.0 186.0 15.90 183.0 183.0 16.50 179.0 179.0 17.20 172.0 172.0 18.50 62 200.0 188.0 14.00 196.0 186.0 14.70 188.0 182.0 16.00 184.0 179.0 16.60 180.0 177.0 17.20 172.0 172.0 18.50 67 215.0 156.0 14.50 211.0 154.0 15.
PERFORMANCE DATA (cont) COMBINATION RATINGS (cont) UNIT 566D240 566D240/524A-C300 WITH HIGH-CAPACITY 4-ROW COIL Temp (F) Air Entering Condenser (Edb) 80 85 95 100 105 115 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 7,500 57 244.0 244.0 18.90 239.0 239.0 19.70 230.0 230.0 21.30 226.0 226.0 22.00 221.0 221.0 22.80 212.0 212.0 24.30 62 249.0 233.0 19.20 244.0 231.0 19.90 233.0 225.0 21.40 228.0 222.0 22.10 222.0 219.0 22.80 212.0 211.0 24.30 67 268.0 194.0 19.90 263.0 192.0 20.70 251.0 187.
PERFORMANCE DATA (cont) COMBINATION RATINGS (cont) UNIT 566E150 566E150/524A-C120 WITH HIGH-CAPACITY 4-ROW COIL Temp (F) Air Entering Condenser (Edb) 80 85 95 100 105 115 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 3000 57 126.0 126.0 9.13 125.0 125.0 9.68 121.0 121.0 10.90 119.0 119.0 11.60 118.0 118.0 12.30 114.0 114.0 13.70 62 135.0 112.0 9.18 133.0 111.0 9.72 129.0 109.0 11.00 127.0 108.0 11.60 124.0 107.0 12.30 120.0 104.0 13.80 67 148.0 95.4 9.22 146.0 94.5 9.79 141.0 92.4 11.
PERFORMANCE DATA (cont) COMBINATION RATINGS (cont) UNIT 566E150 (cont) 566E150/524A-C150 WITH HIGH-CAPACITY 4-ROW COIL Temp (F) Air Entering Condenser (Edb) 80 85 95 100 105 115 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 3750 57 139.0 139.0 9.18 137.0 137.0 9.74 133.0 133.0 11.00 131.0 131.0 11.60 129.0 129.0 12.30 125.0 125.0 13.80 62 145.0 127.0 9.21 143.0 126.0 9.76 138.0 124.0 11.00 136.0 123.0 11.60 133.0 121.0 12.30 128.0 119.0 13.80 67 158.0 107.0 9.27 155.0 106.0 9.84 150.0 104.
PERFORMANCE DATA (cont) COMBINATION RATINGS (cont) UNIT 566E150 (cont) 566E150/524A-C180 WITH HIGH-CAPACITY 4-ROW COIL Temp (F) Air Entering Condenser (Edb) 80 85 95 100 105 115 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 4500 57 152.0 152.0 9.24 150.0 150.0 9.80 146.0 146.0 11.00 144.0 144.0 11.70 141.0 141.0 12.40 137.0 137.0 13.90 62 156.0 145.0 9.26 154.0 144.0 9.82 148.0 141.0 11.10 146.0 140.0 11.70 143.0 138.0 12.40 138.0 135.0 13.90 67 169.0 121.0 9.35 166.0 120.0 9.92 161.0 117.
PERFORMANCE DATA (cont) COMBINATION RATINGS (cont) UNIT 566E180 566E180/524A-C150 WITH HIGH-CAPACITY 4-ROW COIL Temp (F) Air Entering Condenser (Edb) 80 85 95 100 105 115 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 3750 57 163.0 161.0 12.60 160.0 159.0 13.10 155.0 155.0 14.30 152.0 152.0 14.90 150.0 150.0 15.60 144.0 144.0 16.90 62 175.0 142.0 12.80 172.0 141.0 13.40 166.0 138.0 14.60 163.0 136.0 15.20 159.0 134.0 15.80 152.0 131.0 17.10 67 190.0 121.0 13.20 187.0 120.0 13.80 180.0 117.
PERFORMANCE DATA (cont) COMBINATION RATINGS (cont) UNIT 566E180 (cont) 566E180/524A-C180 WITH HIGH-CAPACITY 4-ROW COIL Temp (F) Air Entering Condenser (Edb) 80 85 95 100 105 115 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 4500 57 180.0 180.0 12.90 177.0 177.0 13.50 172.0 172.0 14.70 169.0 169.0 15.40 166.0 166.0 16.00 159.0 159.0 17.30 62 190.0 162.0 13.20 187.0 160.0 13.80 180.0 157.0 14.90 176.0 155.0 15.60 172.0 153.0 16.20 164.0 149.0 17.50 67 206.0 136.0 13.60 203.0 135.0 14.20 195.
PERFORMANCE DATA (cont) COMBINATION RATINGS (cont) UNIT 566E180 (cont) 566E180/524A-C240 WITH HIGH-CAPACITY 4-ROW COIL Temp (F) Air Entering Condenser (Edb) 80 85 95 100 105 115 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 6,000 57 201.0 201.0 13.40 198.0 198.0 14.00 191.0 191.0 15.30 188.0 188.0 15.90 184.0 184.0 16.50 176.0 176.0 17.90 62 205.0 191.0 13.50 202.0 190.0 14.10 194.0 186.0 15.30 190.0 183.0 15.90 185.0 181.0 16.60 177.0 176.0 17.90 67 220.0 159.0 13.90 216.0 157.0 14.
PERFORMANCE DATA (cont) COMBINATION RATINGS (cont) UNIT 566E240 566E240/524A-C240 WITH HIGH-CAPACITY 4-ROW COIL Temp (F) Air Entering Condenser (Edb) 80 85 95 100 105 115 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 6,000 57 228.0 228.0 17.60 225.0 225.0 18.40 218.0 218.0 20.00 214.0 214.0 20.90 211.0 211.0 21.70 203.0 203.0 23.50 62 239.0 207.0 18.00 235.0 205.0 18.70 227.0 201.0 20.30 222.0 199.0 21.10 217.0 196.0 22.00 207.0 192.0 23.70 67 258.0 174.0 18.70 254.0 172.0 19.40 244.0 168.
PERFORMANCE DATA (cont) COMBINATION RATINGS (cont) UNIT 566E240 (cont) 566E240/524A-C300 WITH HIGH-CAPACITY 4-ROW COIL Temp (F) Air Entering Condenser (Edb) 80 85 95 100 105 115 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 7,500 57 249.0 249.0 18.30 245.0 245.0 19.10 237.0 237.0 20.70 232.0 232.0 21.50 228.0 228.0 22.30 219.0 219.0 24.10 62 254.0 236.0 18.50 249.0 234.0 19.20 240.0 229.0 20.80 235.0 226.0 21.60 230.0 223.0 22.40 219.0 217.0 24.10 67 272.0 196.0 19.20 267.0 194.0 19.
ELECTRICAL DATA 566D150-240 NOMINAL VOLTAGE (3-Ph, 60 Hz) UNIT SIZE 150 566D 180 240 208/230 460 575 208/230 460 575 208/230 460 575 COMPRESSOR VOLTAGE RANGE* Min 187 414 518 187 414 518 187 414 518 Max 253 528 660 253 528 660 254 508 632 RLA LRA 49.3 22.1 17.9 63.6 29.3 23.8 67.9 34.7 28.
APPLICATION DATA — 566D150-240, 566E150-240 1. INSTALLATION — Select equipment to match or to be slightly less than peak load. This provides better humidity control, less unit cycling, and less part-load operation. When selecting vapor line sizes, oil return must be evaluated, particularly at part-load conditions. The indoor fan must always be operating when outdoor unit is operating. Ductwork should be sized according to unit size, not building load.
APPLICATION DATA — 566D150-240, 566E150-240 (cont) REFRIGERANT PIPING SIZES UNIT 566D 150 180 240 LINEAR LENGTH OF INTERCONNECTING PIPING (FT) 0-15 16-25 26-50 51-75 76-100 Line Size (in.
APPLICATION DATA — 566D150-240, 566E150-240 (cont) MULTIPLE CONDENSING UNIT ARRANGEMENTS* 566D, 566E150-240 566D, 566E150-240 566D, 566E150-240 Space for Service and Airflow *For clearances between controls and grounded surfaces, check local codes.
TYPICAL PIPING AND WIRING 566D/E150-240 50TFQ004-012 NOTES: 1. All piping must follow standard refrigerant piping techniques. 2. All wiring must comply with the applicable local and national codes. 3. Wiring and piping shown are general points-of-connection guides only and are not intended for, or to include all details for, a specific installation. 4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refrigerant migration to the compressor. 5.
566D/E150-240 50TFQ004-012 TYPICAL PIPING AND WIRING (cont) NOTES: 1. All piping must follow standard refrigerant piping techniques. 2. All wiring must comply with the applicable local and national codes. 3. Wiring and piping shown are general points-of-connection guides only and are not intended for, or to include all details for, a specific installation. 4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refrigerant migration to the compressor. 5.
GUIDE SPECIFICATIONS — 566D150-240, 566E150-240 b. Compressor shall be equipped with an automatically reversible oil pump, operating oil charge, suction and discharge shutoff valves, and an insert-type, factory-sized crankcase heater to control oil dilution. c. Compressor shall be mounted on spring vibration isolators with an isolation efficiency of no less than 95%. d. Compressor speed shall not exceed 1750 rpm. e.
566D/E150-240 50TFQ004-012 GUIDE SPECIFICATIONS — 566D150-240, 566E150-240 (cont) Manual reset at the unit Electrical overload protection through the use of definite-purpose contactors and calibrated, ambient compensated, magnetic trip circuit breakers. Circuit breakers shall open all 3 phases in the event of an overload in any one of the phases or a single-phase condition. H. Operating Characteristics: 1. The capacity of the condensing unit shall meet or exceed_____Btuh at a suction temperature of_____ F.
MODEL NUMBER NOMENCLATURE 524A P B 120 000 GC Factory-Installed Options GC — Unpainted, Standard Motor and Standard Drive HC — Unpainted, Standard Motor and Medium-Static Drive (not available for 300 sizes) TC — Unpainted, Alternate Motor and Medium-Static Drive (300 size only) YC — Unpainted, Alternate Motor and High-Static Drive* ED — Painted, Standard Motor and Standard Drive FD — Painted, Standard Motor and Medium-Static Drive (not available for 300 size) RD — Painted, Alternate Motor and Medium-St
PHYSICAL DATA 524A-B,C UNITS UNIT 524A NOMINAL CAPACITY (Tons) OPERATING WEIGHT (lb) Base Unit with TXV (3 Row/4 Row) Plenum Economizer Hot Water Coil Steam Coil FANS Qty...Diam. (in.) Nominal Airflow (cfm) Airflow Range (cfm) Nominal Motor Hp (Standard Motor)* 208/230-1-60 208/230-3-60 and 460-3-60 575-3-60 Motor Speed (rpm) 208/230-1-60 208/230-3-60 and 460-3-60 575-3-60 REFRIGERANT Operating charge (lb) (approx per circuit)† DIRECT-EXPANSION COIL Max Working Pressure (psig) Face Area (sq ft) No.
DIMENSIONS UNIT 524A-B072 524A-B090 524A-B120 524A-C072 524A-C090 524A-C120 UNIT WEIGHT (lb) 381 385 405 399 404 425 LEGEND TXV — Thermostatic Expansion Valve NOTES: 1. Dimensions in [ ] are in millimeters. 2. Direction of airflow. 524A-B,C072-120 63 524A072-300 50TFQ004-012 3. Recommended clearance: • Rear: 3″ (76.2 mm) (2′-6″ [762 mm] with electric heat accessory) • Front: 2′-6″ (762 mm) • Right Side: 2′-6″ (762 mm) • Left Side: 2′-6″ (762 mm) • Local codes or jurisdiction may prevail. 4.
DIMENSIONS (cont) . UNIT 524A B150 B180 B240 C150 C180 C240 UNIT WEIGHT (lb) 670 685 690 695 713 730 LEGEND TXV — Thermostatic Expansion Valve NOTES: 1. Dimensions in [ ] are in millimeters. 2. Direction of airflow. 524A072-300 50TFQ004-012 3. Recommended clearance: • Rear: 3″ (76.2 mm) (2′-6″ [762 mm] with electric heat accessory) • Front: 2′-6″ (762 mm) • Right Side: 2′-6″ (762 mm) • Left Side: 2′-6″ (762 mm) • Local codes or jurisdiction may prevail. 4. Liquid piping not supplied by Bryant. 5.
DIMENSIONS (cont) UNIT 524A CONTROL BOX B300 C300 ALTERNATE ACCESS FOR FILTERS UNIT WEIGHT (lb) 1020 1050 ALTERNATE ACCESS FOR MOTOR/BELT RETURN AIR OPENING CONTROL BOX LEGEND TXV — Thermostatic Expansion Valve NOTES: 1. Dimensions in [ ] are in millimeters. 2. Direction of airflow. 3. Recommended clearance: • Rear: 3″ (76.2 mm) (2′-6″ [762 mm] with electric heat accessory) • Front: 2′-6″ (762 mm) • Right Side: 2′-6″ (762 mm) • Left Side: 2′-6″ (762 mm) • Local codes or jurisdiction may prevail.
PERFORMANCE DATA 524A-B FAN PERFORMANCE DATA — 0.0-1.2 in. wg ESP UNIT 524A-B AIRFLOW (Cfm) 0.0 EXTERNAL STATIC PRESSURE (in. wg) 0.4 0.6 0.8 Rpm Bhp Rpm Bhp Rpm Bhp 0.60 548 0.35 634 0.47 713 583 0.46 660 0.59 733 0.73 622 0.60 693 0.74 760 0.89 663 0.78 730 0.93 792 1.09 707 0.99 770 1.15 828 1.32 072 1,800 2,100 2,400 2,700 3,000 Rpm 399 446 498 544 594 Bhp 0.19 0.28 0.40 0.55 0.73 0.2 Rpm Bhp 454 0.24 497 0.34 541 0.47 588 0.63 635 0.
PERFORMANCE DATA (cont) 524A-B FAN PERFORMANCE DATA — 1.4-2.4 in. wg ESP UNIT 524A-B AIRFLOW (Cfm) 1.4 1.6 EXTERNAL STATIC PRESSURE (in. wg) 1.8 2.0 Rpm Bhp Rpm Bhp 1180 1.36 1065 1.52 1035 1.56 1084 1.74 1052 1.78 1101 1.98 1069 2.03 1118 2.24 1089 2.31 1136 2.53 072 1,800 2,100 2,400 2,700 3,000 Rpm 910 927 944 964 989 Bhp 1.04 1.21 1.41 1.63 1.89 Rpm 965 983 999 1018 1039 Bhp 1.20 1.38 1.59 1.82 2.10 090 2,250 2,600 3,000 3,400 3,750 918 936 963 998 1360 1.26 1.48 1.79 2.18 2.
PERFORMANCE DATA (cont) FAN PERFORMANCE DATA — 524A-C WITH HIGH CAPACITY COIL — 0.0-1.2 in. wg ESP UNIT 524A-C (High-Capacity 4-Row Coil) AIRFLOW (Cfm) 0.0 EXTERNAL STATIC PRESSURE (in. wg) 0.4 0.6 0.8 0.2 1.0 1.2 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 072 1,800 2,100 2,400 2,700 3,000 419 471 524 578 633 0.21 0.31 0.44 0.61 0.81 471 519 568 619 671 0.26 0.37 0.51 0.69 0.90 564 602 645 690 738 0.37 0.49 0.64 0.84 1.07 649 679 715 755 799 0.49 0.62 0.79 0.99 1.
PERFORMANCE DATA (cont) FAN PERFORMANCE DATA — 524A-C WITH HIGH CAPACITY COIL — 1.4-2.4 in. wg ESP UNIT 524A-C (High-Capacity 4-Row Coil) AIRFLOW (Cfm) 1.4 EXTERNAL STATIC PRESSURE (in. wg) 1.8 2.0 1.6 2.2 2.4 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 072 1,800 2,100 2,400 2,700 3,000 921 942 963 987 1015 1.07 1.26 1.47 1.71 1.99 975 997 1017 1039 1065 1.23 1.43 1.66 1.91 2.20 1026 1048 1069 1090 1113 1.39 1.61 1.85 2.12 2.42 1074 1097 1118 1138 1161 1.55 1.79 2.05 2.33 2.
PERFORMANCE DATA (cont) FACTORY-SUPPLIED FILTER PRESSURE DROP UNIT 524A-B 524A-C 072 090 120 150 180 240 300 ACCESSORY PLENUM AIR THROW DATA AIRFLOW (Cfm) PRESSURE DROP (in. wg) UNIT 524A AIRFLOW (Cfm) 1,800 2,400 3,000 2,250 3,000 3,750 3,000 4,000 5,000 3,750 5,000 6,250 4,500 6,000 7,500 6,000 8,000 10,000 7,500 10,000 12,500 0.05 0.08 0.11 0.07 0.11 0.15 0.11 0.17 0.23 0.06 0.10 0.13 0.08 0.12 0.17 0.12 0.19 0.26 0.15 0.22 0.
PERFORMANCE DATA (cont) HYDRONIC HEATING CAPACITIES UNIT 524A-B 524A-C AIRFLOW (Cfm) 1,800 2,400 3,000 2,250 3,000 3,750 3,000 4,000 5,000 3,750 5,000 6,250 4,500 6,000 7,500 6,000 8,000 10,000 7,500 10,000 12,500 072 090 120 150 180 240 300 1-ROW STEAM* Cap. Ldb Cap. 146 173 209 168 209 240 209 243 279 370 425 465 402 458 479 458 487 499 511 575 626 134 126 123 129 123 117 123 115 111 150 137 128 141 129 118 129 115 105 122 112 106 156.0 183.0 206.0 174.0 206.0 238.0 299.0 275.0 316.0 362.0 409.
ELECTRICAL DATA 524A-B,C STANDARD MOTORS UNIT 524A-B 524A-C 072 090 120 150 180 240 300 FAN MOTOR V*-PH-Hz VOLTAGE LIMITS Hp (kW) FLA 208/230-1-60 208/230-3-60 460-3-60 575-3-60 208/230-1-60 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 187-253 187-253 414-506 518-632 187-253 187-253 414-506 518-632 187-253 414-506 518-632 187-253 414-506 518-632 187-253 4
ELECTRICAL DATA (cont) 524A-B,C ALTERNATE MOTORS UNIT 524A-B 524A-C 072 090 120 150 180 240 300 FAN MOTOR V*-PH-Hz VOLTAGE LIMITS Hp (kW) FLA 208/230-1-60 208/230-3-60 460-3-60 575-3-60 208/230-1-60 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 187-253 187-253 414-506 518-632 187-253 187-253 414-506 518-632 187-253 414-506 518-632 187-253 414-506 518-632 18
ELECTRICAL DATA (cont) ELECTRIC HEATER DATA HEATER PART NO. UNIT V-PH-Hz 208-3-60 CAELHEAT001A00 240-3-60 CAELHEAT002A00 480-3-60 CAELHEAT003A00 575-3-60 208-3-60 CAELHEAT004A00 524A-B072-120 524A-C072-120 240-3-60 CAELHEAT005A00 480-3-60 CAELHEAT006A00 575-3-60 208-3-60 CAELHEAT007A00 240-3-60 CAELHEAT008A00 480-3-60 CAELHEAT009A00 575-3-60 FAN MOTOR Hp 1.3† 2.4† 2.4 2.9 3.7 1.3† 2.4† 2.4 2.9 3.7 2.4 2.9 3.7 1.0 2.0 3.0 1.3† 2.4† 2.4 2.9 3.7 1.3† 2.4† 2.4 2.9 3.7 2.4 2.9 3.7 1.0 2.0 3.
ELECTRICAL DATA (cont) ELECTRIC HEATER DATA (cont) HEATER PART NO. UNIT V-PH-Hz 208-3-60 CAELHEAT010A00 240-3-60 CAELHEAT011A00 CAELHEAT012A00 480-3-60 524A-B072-120 524A-C072-120 575-3-60 208-3-60 CAELHEAT013A00 240-3-60 CAELHEAT014A00 480-3-60 CAELHEAT015A00 575-3-60 FLA Hp MCA MOCP — — — — FAN MOTOR Hp 1.3† 2.4† 2.4 2.9 3.7 1.3† 2.4† 2.4 2.9 3.7 2.4 2.9 3.7 1.0 2.0 3.0 2.4† 2.4 2.9 3.7 2.4† 2.4 2.9 3.7 2.4 2.9 3.7 2.0 3.0 kW 0.97 1.79 1.79 2.16 2.76 0.97 1.79 1.79 2.16 2.76 1.79 2.16 2.
ELECTRICAL DATA (cont) ELECTRIC HEATER DATA (cont) HEATER PART NO. UNIT V-PH-Hz 208-3-60 CAELHEAT016A00 240-3-60 CAELHEAT017A00 480-3-60 CAELHEAT018A00 575-3-60 208-3-60 CAELHEAT019A00 240-3-60 524A-B150-240 524A-C150-240 CAELHEAT020A00 480-3-60 CAELHEAT021A00 575-3-60 208-3-60 CAELHEAT022A00 240-3-60 CAELHEAT023A00 480-3-60 CAELHEAT024A00 575-3-60 FAN MOTOR Hp 2.9 3.7 5.0 7.5 2.9 3.7 5.0 7.5 2.9 3.7 5.0 7.5 3.0 5.0 7.5 2.9 3.7 5.0 7.5 2.9 3.7 5.0 7.5 2.9 3.7 5.0 7.5 3.0 5.0 7.5 2.9 3.7 5.
ELECTRICAL DATA (cont) ELECTRIC HEATER DATA (cont) HEATER PART NO. UNIT V-PH-Hz 208-3-60 CAELHEAT025A00 240-3-60 524A-B180,240 524A-C180,240 CAELHEAT026A00 480-3-60 CAELHEAT027A00 575-3-60 208-3-60 CAELHEAT028A00 240-3-60 CAELHEAT029A00 CAELHEAT030A00 480-3-60 524A-B300 524A-C300 575-3-60 208-3-60 CAELHEAT031A00 240-3-60 CAELHEAT032A00 480-3-60 CAELHEAT033A00 575-3-60 FLA — Hp — MCA — MOCP— FAN MOTOR Hp 3.7 5.0 7.5 3.7 5.0 7.5 3.7 5.0 7.5 3.0 5.0 7.5 7.5 10.0 7.5 10.0 7.5 10.0 7.5 10.0 7.
ELECTRICAL DATA (cont) ELECTRIC HEATER DATA (cont) HEATER PART NO. UNIT V-PH-Hz 208-3-60 CAELHEAT034A00 240-3-60 CAELHEAT035A00 CAELHEAT036A00 480-3-60 524A-B300 524A-C300 575-3-60 208-3-60 CAELHEAT037A00 240-3-60 CAELHEAT038A00 480-3-60 CAELHEAT039A00 575-3-60 FLA Hp MCA MOCP — — — — FAN MOTOR Hp 7.5 10.0 7.5 10.0 7.5 10.0 7.5 10.0 7.5 10.0 7.5 10.0 7.5 10.0 7.5 10.0 kW 5.59 7.46 5.59 7.46 5.59 7.46 5.59 7.46 5.59 7.46 5.59 7.46 5.59 7.46 5.59 7.46 FLA 19.8 28.0 19.4 26.8 9.7 13.4 7.8 10.
APPLICATION DATA — 524A 1. OPERATING LIMITS Maximum fan speed — 524A-B,C072-240 . . . . . . . .1200 rpm Maximum fan speed — 524A-B,C300 . . . 1100 rpm (18.3 r/s) 2. GENERAL — Select equipment to match or to be slightly less than peak load. This provides better humidity control, less unit cycling, and less part-load operation. Equipment should be selected to perform at no less than 300 cfm/ton. The air handler fan must always be operating when the condensing unit is operating.
APPLICATION DATA — 524A (cont) FAN MOTOR DATA (cont) ALTERNATE MOTOR UNIT SIZE 524A 208/230-1-60 Speed (rpm) Hp Frame (NEMA) Shaft Dia (in.) 230-3-60 and 460-3-60 Speed (rpm) Hp Frame (NEMA) Shaft Dia (in.) 575-3-60 Speed (rpm) Hp Frame (NEMA) Shaft Dia (in.) 072 090 120 150 180 240 300 1725 2.4 56Y 5/ 8 1725 2.4 56Y 5/ 8 — — — — — — — — — — — — — — — — — — — — 1725 2.9 56Y 7/ 8 1725 2.9 56Y 7/ 8 1725 3.7 Y56Y 7/8 1725 3.7 Y56Y 7/ 8 1725 5.0 S184T 11 / 8 1745 7.5 S213T 13 / 8 1745 10.
APPLICATION DATA — 524A (cont) MEDIUM-STATIC DRIVE DATA UNIT SIZE 524A MOTOR DRIVE Motor Pulley Pitch Diameter (in.) Pulley Factory Setting Full Turns Open FAN DRIVE Pulley Pitch Dia (in.) Pulley Bore (in.) Belt No. — Section Belt Pitch (in.) FAN SPEEDS (rpm) Factory Setting Range Max Allowable Speed (rpm) Change per 1/2 Turn of Moveable Motor Pulley Flange MAX FULL TURNS FROM CLOSED POSITION SHAFTS CENTER DISTANCE (in.) 072 090 120 150 180 240 300 3.4-4.4 3.4-4.4 3.4-4.4 3.4-4.4 3.7-4.7 4.3-5.
524A072-300 50TFQ004-012 GUIDE SPECIFICATIONS — 524A COMMERCIAL PACKAGED AIR-HANDLING UNIT HVAC GUIDE SPECIFICATIONS SIZE RANGE: 1,800 to 12,500 CFM, NOMINAL AIRFLOW 6 TO 25 TONS, NOMINAL COOLING BRYANT MODEL NUMBERS: 524A-B (DIRECT-EXPANSION COIL), 524A-C (HIGH-CAPACITY 4-ROW DIRECT-EXPANSION COIL) PART 1 — GENERAL 1.01 SYSTEM DESCRIPTION A. Indoor, packaged air-handling unit for use in commercial split systems.
GUIDE SPECIFICATIONS — 524A (cont) 5. Electric Heaters: Heaters for nominal 240, 480, or 575-volt, 3-phase, 60 Hz power supply shall be factory-supplied for field installation as shown on the equipment drawings. Electric heat assembly shall be ETL and ETL, Canada, agency approved, and shall have single-point power wiring. Heater assembly shall include contactors with 24-v coils, power wiring, 24-v control wiring terminal blocks, and a hinged access panel.
INDEX 569D/F072-120, 576C120 11-32 566D/E150-240 33-60 524A072-300 61-83 Alternate motors and drives 5, 73, 80, 81 Application data 569D/F072-120, 576C120 27 566D/E150-240 54-56 524A072-300 79-81 ARI capacity ratings 3 CO2 sensor 83 Combination ratings 566D150-240/524A 40-44 566E150-240/524A 45-52 569D072-120/524A 16-21 569F120/524A 24, 25 576C/524A 22, 23 Condenser coil grille 4 Condensing unit ratings 15, 39 Controls 8 Convenience outlet 4 Dimensions Base unit 569D/F072-120, 576C120 13, 14 566D/E150-240 3