Specifications

61
TYPICAL WIRING SCHEMATIC (cont)
APPLICATION DATA
1.
CONDENSATE DRAIN PAN
A sloped condensate drain
pan is supplied on all units. The condensate drain pan must
be externally trapped. Condensate drains are located on
both the bottom and end of the unit. The bottom drain can
be used for thru-the-curb connections.
2.
DUCTWORK
All ductwork must be attached to flanges. If
no flanges are present, they must be field supplied. Secure
vertical discharge ductwork to roof curb. For horizontal dis-
charge applications, attach ductwork to flanges. Field sup-
plied flanges can be attached to horizontal discharge
openings and all ductwork attached to flanges.
3.
TO CONVERT FROM
VERTICAL DISCHARGE TO HORI-
ZONTAL DISCHARGE (DURABLADE ECONOMIZER
ONLY):
a. Remove economizer or two-position damper to gain
access to return duct opening.
b. Move the horizontal-discharge duct opening covers to
the vertical discharge openings.
c. Rotate economizer or two-position damper 90 degrees
(until the motor faces the condenser section).
d. Rotate the barometric relief damper 90 degrees.
e. Install block-off plate over the opening on the access
panel.
4.
THRU-THE-BOTTOM SERVICE CONNECTIONS
Thru-
the-bottom connections allow field power wires and control
wires to enter through the basepan.
5.
THERMOSTAT
Use of 2-stage cooling thermostat is
recommended for all units equipped with economizer.
6.
HEATING-TO-COOLING CHANGEOVER
All units are
automatic changeover from heating to cooling when auto-
matic changeover thermostat and subbase are used.
7.
AIRFLOW
Units are draw-thru on cooling and blow-thru
on heating.
8.
MAXIMUM AIRFLOW
To minimize possibility of conden-
sate blow-off from evaporator, airflow through units should
not exceed 500 cfm/ton.
9.
MINIMUM AIRFLOW
Minimum airflow for cooling is
300 cfm/ton. For units with electric heating, required mini-
mum cfm is 900 for 551B036; 1200 for 551B048; 1500 for
551B060; 1800 for 551B072; 2250 for 551B090; 2500 for
551B102; 3000 for 551B120; and 4000 for the 551B150,
with the following exceptions:
10.
MINIMUM AMBIENT OPERATING TEMPERATURE
Min-
imum operating temperature for size 036-150 standard units
is 25 F. With accessory Motormaster® or Motormaster IV
control, units can operate at outdoor temperatures down to
20 F.
11.
MAXIMUM OPERATING OUTDOOR-AIR TEMPERATURE
Maximum outdoor-air operating temperature for cooling
is 125 F.
12.
MOTOR DATA
Due to Bryants internal unit design (draw-
thru over the motor), air path, and specially designed
motors, the full horsepower (maximum continuous bhp)
listed in the Physical Data table and in each Fan Perfor-
mance table can be utilized with extreme confidence.
Using Bryant motors to the values listed in the Physical
Data, Fan Performance, and Evaporator-Fan Motor Data
tables
will not
result in nuisance tripping or premature motor
failure. In addition, the unit warranty will not be affected.
UNIT
551B
UNIT
VO LTAGE
HEATER
kW
UNIT
CONFIGURATION
REQUIRED
MINIMUM CFM
120
208/230 42.4 Horizontal 3200
208/230 50.0 Horizontal 3200
460 50.0 Horizontal or Vertical 3200
090-150
575
17.0
Horizontal or Vertical
2800
34.0 2350
AHA
Adjustable Heat Anticipator
AWG
American Wire Gage
C
Contactor, Compressor
CAP
Capacitor
CB
Circuit Breaker
CC
Cooling Compensator
CLO
Compressor Lockout
COMP
Compressor Motor
D
Diode
EC
Enthalpy Control
ECON
Economizer
EPS
Emergency Power Supply
(9-v Battery)
EQUIP
Equipment
ER
Economizer Relay
FPT
Freeze Protection Thermostat
FSS
Filter Status Switch
FU
Fuse
GND
Ground
HC
Heater Contactor
HPS
High-Pressure Switch
IFC
Indoor (Evaporator) Fan Contactor
IFM
Indoor (Evaporator) Fan Motor
IFR
Indoor (Evaporator) Fan Relay
LPS
Low-Pressure Switch
LSM
Limit Switch (Manual Reset)
MTR
Motor
OAT
Outdoor-Air Thermostat
OFC
Outdoor (Condenser) Fan Contactor
OFM
Outdoor (Condenser) Fan Motor
OLR
Overload Relay
P
Plug
PL
Plug Assembly
QT
Quadruple Terminal
R
Relay
SAT
Supply-Air Thermostat
SW1
Switch Fully Open
SW2
Switch Fully Closed
SW3
Switch Minimum Vent Position
SW4
Switch Maximum Vent Position
TB
Terminal Block
TC
Thermostat-Cooling
TDR
Time-Delay Relay
TH
Thermostat-Heating
TRAN
Transformer
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
To indicate common potential only.
Not to represent wiring.
NOTES:
1. If any of the original wire furnished must be replaced, it
must be replaced with type 90° C wire or its equivalent.
2. Three-phase motors are protected under primary
single-phasing conditions.
3. Thermostat: HH07AT170,172
Subbase: HH93AZ176,177,178, and 179
4. Single-Fan Units
:
Set heat anticipator at .8 amp for first stage, and
.3 amp for second stage.
Two-Fan Units
:
Set heat anticipator at 1 amp.
5. Use copper conductors only.
6. Single-Fan Units
:
TRAN is wired for 230-v unit. If unit is to be run with
208-v power supply, disconnect BLK wire from 230-v
tap (ORN) and connect to 208-v tap (RED). Insulate
end of 230-v tap.
Two-Fan Units
:
Use copper, copper-clad aluminum, or aluminum
conductors.
7. Single-Fan Units
:
Use copper, copper-clad aluminum, or aluminum
conductors.
Two-Fan Units
:
TRAN is wired for 230-v unit. If unit is to be run with
208-v power supply, disconnect BLK wire from 230-v
tap (ORN) and connect to 208-v tap (RED). Insulate
end of 230-v tap.