Specifications
39
PERFORMANCE DATA (cont)
FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)
L
EGEND
NOTES:
1.
Boldface
indicates a field-supplied drive is required. (See Note 6.)
2. indicates a high-static motor and drive are required.
3. Maximum continuous bhp is 2.90 for standard motors; 4.20 for high-static
motors. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using your fan
motors up to the ratings shown will not result in nuisance tripping or prema-
ture motor failure. Unit warranty will not be affected. For additional informa-
tion on motor performance, refer to Evaporator-Fan Motor Data tables on
pages 42 and 43.
4. Values include losses for filters, unit casing, and wet coils. See page 43 for
accessory/FIOP static pressure information.
5. Use of a field-supplied motor may affect wire sizing. Contact Bryant repre-
sentative to verify.
6. Standard motor drive range: 840 to 1085 rpm. High-static motor drive range:
860 to 1060 rpm. All other rpms require field-supplied drive.
7. Interpolation is permissible. Do not extrapolate.
551B102 (8
1
/
2
TONS) — STANDARD AND HIGH-STATIC MOTOR (BELT DRIVE)
Airflow
(Cfm)
External Static Pressure (in. wg)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
2550 501 0.57 587 0.79 659 1.05 722 1.29 780 1.55
2660 507 0.59 592 0.82 663 1.08 727 1.32 784 1.58
2700 520 0.65 604 0.89 672 1.14 737 1.40 793 1.66
2800 533 0.71 615 0.95 683 1.20 747 1.49 802 1.75
2900 546 0.77 626 1.02 693 1.27 756 1.57 813 1.84
3000 559 0.83 637 1.09 704 1.35 765 1.66 823 1.94
3100 572 0.90 648 1.17 715 1.43 775 1.74 832 2.05
3200 585 0.96 660 1.24 727 1.52 785 1.83
841 2.15
3300 598 1.03 671 1.32 739 1.62 795 1.91
851 2.26
3400 610 1.10 682 1.41 750 1.72 806 2.01
860 2.36
3500 623 1.17 694 1.50 761 1.82 817 2.11
870 2.47
3600 636 1.25 707 1.60 772 1.93 828 2.23
880 2.57
3700 649 1.33 720 1.71 783 2.03
8402.358902.69
3750 655 1.37 727 1.77 789 2.09
8462.428962.75
3800 661 1.41 733 1.82 795 2.15
8522.489012.80
3900 674 1.49 746 1.93 806 2.26
863 2.61
912 2.93
4000 687 1.57 759 2.05 817 2.38
874 2.75
923 3.08
4100 699 1.60 772 2.17 828 2.50
885 2.88
935 3.23
4200 712 1.75 785 2.30
840 2.64
897 3.03 947 3.39
4250 719 1.80 792 2.37
846 2.71
903 3.10 ——
551B102 (8
1
/
2
TONS) — STANDARD AND HIGH-STATIC MOTOR (BELT DRIVE) (cont)
Airflow
(Cfm)
External Static Pressure (in. wg)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
2550 836 1.83
887 2.13 931 2.45 964 2.77
986 3.11
2660 839 1.87
891 2.17 936 2.49 973 2.82
999 3.16
2700
846 1.95 898 2.26 946 2.58
987 2.91 1019 3.26
2800
855 2.04 906 2.35 954 2.67
997 3.01 1034 3.36
2900
863 2.13 913 2.44 961 2.77
1006 3.12 ——
3000
872 2.22 921 2.54 969 2.88
1014 3.22 ——
3100
8822.339302.65
976 2.99 1021 3.34 ——
3200
8922.459392.76
984 3.10 ————
3300
9022.579482.88
993 3.21 ————
3400
912 2.69
958 3.01 1002 3.34 ————
3500
921 2.82
968 3.15 ——————
3600
930 2.95 978 3.29 ——————
3700
940 3.07 ————————
3750
945 3.14 ————————
3800
949 3.20 ————————
3900
959 3.33 ————————
4000
——————————
4100
——————————
4200
——————————
4250
——————————
Bhp —
Brake Horsepower Input to Fan
FIOP —
Factory-Installed Option