Specifications

26
PERFORMANCE DATA (cont)
FAN PERFORMANCE VERTICAL DISCHARGE UNITS (cont)
LEGEND
NOTES:
1.
Boldface
indicates a field-supplied drive is required. (See Note 6.)
2. indicates field-supplied motor and drive are required.
3. Maximum continuous bhp is 1.80 for single-phase standard motors; 2.40 for
3-phase standard motors; and 2.90 for high-static motors. Extensive motor
and electrical testing on these units ensures that the full range of the motor
can be utilized with confidence. Using your fan motors up to the ratings
shown will not result in nuisance tripping or premature motor failure. Unit
warranty will not be affected. For additional information on motor perfor-
mance, refer to Evaporator-Fan Motor Data tables on pages 42 and 43.
4. Values include losses for filters, unit casing, and wet coils. See page 43 for
accessory/FIOP static pressure information.
5. Use of a field-supplied motor may affect wire sizing. Contact Bryant repre-
sentative to verify.
6. Motor drive range: 1020 to 1460 rpm for single-phase standard motors;
1120 to 1585 for 3-phase standard motors; and 1300 to 1685 for high-static
motors. All other rpms require field-supplied drive.
7. Interpolation is permissible. Do not extrapolate.
551B060 (5 TONS) STANDARD MOTOR (BELT DRIVE) SINGLE-PHASE UNITS
Airflow
(Cfm)
External Static Pressure (in. wg)
0.1 0.2 0.4 0.6 0.8
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1500 711 0.33 769 0.39 878 0.51 971 0.64
1052 0.78
1600 751 0.39 806 0.45 906 0.53
1024 0.73 1087 0.88
1700 791 0.46 846 0.53 941 0.66
1030 0.80 1112 0.96
1800 852 0.55 905 0.62 1002 0.78
1084 0.93 1163 1.10
1900 894 0.64 945 0.72
1037 0.88 1119 1.04 1194 1.21
2000 936 0.74 984 0.82
1072 0.98 1154 1.16 1226 1.33
2100 978 0.85
1024 0.93 1108 1.10 1190 1.29 1259 1.47
2200
1021 0.97 1064 1.05 1145 1.22 1225 1.43 1294 1.62
2300
1064 1.10 1104 1.18 1183 1.36 1260 1.57 1330 1.78
2400
1107 1.24 1145 1.32 1222 1.52 1296 1.73
1365 1.94
2500
1150 1.39 1186 1.48 1262 1.68
1331 1.89 1400 2.12
551B060 (5 TONS) STANDARD MOTOR (BELT DRIVE) SINGLE-PHASE UNITS (cont)
Airflow
(Cfm)
External Static Pressure (in. wg)
1.0 1.2 1.4 1.6
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1500
1134 0.95 1213 1.11 1276 1.38 1331 1.49
1600
1159 1.02 1231 1.20 1311 1.39 1395 1.59
1700
1184 1.12 1258 1.30 1322 1.49 1403 1.69
1800
1235 1.29 1303 1.48 1371 1.69
1433 1.90
1900
1266 1.40 1330 1.59
1396 1.81 1460 2.03
2000
1297 1.53 1362 1.73
1422 1.94 1485 2.16
2100
1327 1.66
1393 1.87 1452 2.08 1510 2.31
2200
1359 1.81 1423 2.02 1483 2.24 1538 2.46
2300
1392 1.97 1454 2.18 1515 2.41 1569 2.64
2400
1426 2.15 1485 2.36 1544 2.59 1601 2.84
2500
1461 2.34 1518 2.55 1575 2.78 ——
551B060 (5 TONS) STANDARD MOTOR (BELT DRIVE) THREE-PHASE UNITS
Airflow
(Cfm)
External Static Pressure (in. wg)
0.1 0.2 0.4 0.6 0.8
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1500 711 0.33 769 0.39 878 0.51 971 0.64 1052 0.78
1600 751 0.39 806 0.45 906 0.53 1024 0.73 1087 0.88
1700 791 0.46 846 0.53 941 0.66 1030 0.80 1112 0.96
1800 852 0.55 905 0.62 1002 0.78 1084 0.93
1163 1.10
1900 894 0.64 945 0.72 1037 0.88 1119 1.04
1194 1.21
2000 936 0.74 984 0.82 1072 0.98
1154 1.16 1226 1.33
2100 9780.8510240.9311081.10
1190 1.29 1259 1.47
2200 1021 0.97 1064 1.05
1145 1.22 1225 1.43 1294 1.62
2300 1064 1.10 1104 1.18
1183 1.36 1260 1.57 1330 1.78
2400 1107 1.24
1145 1.32 1222 1.52 1296 1.73 1365 1.94
2500
1150 1.39 1186 1.48 1262 1.68 1331 1.89 1400 2.12
551B060 (5 TONS) STANDARD MOTOR (BELT DRIVE) THREE-PHASE UNITS (cont)
Airflow
(Cfm)
External Static Pressure (in. wg)
1.0 1.2 1.4 1.6
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1500
1134 0.95 1213 1.11 1276 1.38 1331 1.49
1600
1159 1.02 1231 1.20 1311 1.39 1395 1.59
1700
1184 1.12 1258 1.30 1322 1.49 1403 1.69
1800
1235 1.29 1303 1.48 1371 1.69 1433 1.90
1900
1266 1.40 1330 1.59 1396 1.81 1460 2.03
2000
1297 1.53 1362 1.73 1422 1.94 1485 2.16
2100
1327 1.66 1393 1.87 1452 2.08 1510 2.31
2200
1359 1.81 1423 2.02 1483 2.24
1538 2.46
2300
1392 1.97 1454 2.18
1515 2.41 1569 2.64
2400
1426 2.15 1485 2.36
1544 2.59 1601 2.84
2500
1461 2.34
1518 2.55 1575 2.78 ——
Bhp
Brake Horsepower Input to Fan
FIOP
Factory-Installed Option