Specifications

21
PERFORMANCE DATA (cont)
COOLING CAPACITIES, UNITS WITH PERFECT HUMIDITY OPTION (cont)
Do not operate at these conditions.
LEGEND
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
where h
ewb
= enthalpy of air entering indoor coil
3. The SHC is based on 80 F edb temperature of air entering evap-
orator coil.
Below 80 F db, subtract (corr factor x cfm) from SHC.
Above 80 F db, add (corr factor x cfm) to SHC
.
Correction Factor = 1.10 x (1 BF) x (db 80)
551B060 (5 TONS)
TEMP (F)
AIR ENT
CONDENSER
(Edb)
Temp (F) Air Entering Evaporator CFM/BF
1500/0.08 1750/0.09 2000/0.11 2500/0.13
Temp (F) Air Entering Evaporator Ewb
78 72 67 62 78 72 67 62 78 72 67 62 78 72 67 62
75
TC
79.4 69.9 62.7 56.2 85.0 74.7 67.3 61.0 90.0 78.5 71.2 64.8
81.7 75.5 69.3
SHC
21.8 29.0 36.9 43.9 23.2 31.7 40.5 51.2 24.7 34.5 44.2 55.4
37.8 52.0 62.8
kW
3.77 3.61 3.55 3.51 3.81 3.64 3.58 3.49 3.84 3.65 3.60 3.51
3.62 3.58 3.51
85
TC
75.1 65.9 59.1 51.7
70.6 63.2 56.3 75.5 66.8 60.7 78.1 70.8 65.1
SHC
18.9 25.3 34.0 41.9
27.5 37.6 48.0 30.7 41.6 52.0 33.8 47.4 58.0
kW
4.31 4.05 3.97 3.91
4.07 4.01 3.92 4.11 4.00 3.95 4.08 4.02 3.96
95
TC
75.6 61.9 55.2 47.7
66.5 58.8 51.3 70.4 61.9 55.7 74.2 65.9 60.6
SHC
24.1 21.6 31.1 40.0
23.5 34.5 44.6 26.0 38.6 47.9 30.0 42.8 52.6
kW
4.62 4.53 4.43 4.35
4.55 4.47 4.37 4.56 4.42 4.41 4.58 4.49 4.44
105
TC
57.7 51.1 44.9 61.8 54.5 47.7 65.1 57.2 50.8 68.4 60.3 56.1
SHC
18.1 27.8 35.7 20.0 31.2 40.1 22.1 34.3 43.5 26.1 38.9 48.5
kW
5.05 4.93 4.84 5.09 4.97 4.88 5.11 4.96 4.92 5.11 5.03 4.98
115
TC
53.4 47.2 42.0 56.6 50.0 44.2 59.6 52.5 46.2 62.6 54.9 51.6
SHC
14.7 24.6 31.5 16.5 27.8 35.7 18.2 30.0 39.0 22.1 34.9 44.3
kW
5.60 5.49 5.40 5.64 5.52 5.45 5.69 5.55 5.48 5.69 5.61 5.57
125
TC
48.7 42.0 36.9 51.3 45.0 39.0 54.1 46.8 40.9 56.9 49.2 45.9
SHC
10.9 19.6 28.0 12.5 22.2 31.5 13.5 24.0 34.0 16.5 28.0 38.8
kW
6.26 6.12 6.02 6.28 6.18 6.09 6.33 6.18 6.13 6.33 6.27 6.22
551B072 (6 TONS)
TEMP (F)
AIR ENT
CONDENSER
(Edb)
Temp (F) Air Entering Evaporator CFM/BF
1800/0.05 2100/0.06 2400/0.06 3000/0.08
Temp (F) Air Entering Evaporator Ewb
78 72 67 62 78 72 67 62 78 72 67 62 78 72 67 62
75
TC
89.0 82.6 75.6 68.5 91.1 84.9 78.0 70.9 92.4 85.9 79.5 73.5
89.1 82.7 77.0
SHC
25.0 36.0 44.8 55.4 25.1 37.5 49.1 59.7 25.2 38.8 51.1 64.0 41.8 58.1 70.2
kW
4.80 4.60 4.52 4.36 4.86 4.67 4.57 4.46 4.89 4.70 4.57 4.45
4.77 4.61 4.51
85
TC
84.9 78.2 71.6 64.5 87.0 80.9 73.4 65.8
82.0 74.4 67.9 85.8 78.2 72.3
SHC
21.8 31.4 41.2 41.7 21.9 33.0 44.7 55.8 34.7 47.4 60.1 37.6 54.3 66.7
kW
5.40 5.16 5.03 4.89 5.46 5.22 5.11 4.96
5.26 5.09 4.97 5.32 5.17 5.04
95
TC
80.7 73.8 67.4 60.2
76.3 68.3 60.5 77.5 69.3 62.3 82.0 72.8 67.5
SHC
18.7 27.0 37.6 47.9 28.2 40.1 51.6 30.2 43.7 56.2 33.6 49.2 62.9
kW
6.01 5.75 5.60 5.44
5.80 5.66 5.48 5.84 5.68 5.53 5.90 5.73 5.60
105
TC
68.4 62.6 55.9 71.4 64.3 56.2 72.1 64.6 58.3 75.7 67.0 62.4
SHC
22.3 33.5 43.5 23.4 36.5 48.0 25.4 38.4 50.2 29.1 45.2 56.2
kW
6.37 6.22 6.06 6.45 6.27 6.10 6.46 6.29 6.16 6.53 6.36 6.24
115
TC
63.4 57.8 50.7 66.0 60.1 51.5 66.4 59.6 54.5 68.8 60.8 57.5
SHC
18.1 29.5 38.9 18.8 32.9 44.1 20.7 33.3 43.8 24.3 41.4 49.7
kW
7.04 6.89 6.68 7.10 6.91 6.74 7.12 6.95 6.83 7.16 7.01 6.92
125
TC
55.5 49.6 45.8 58.4 52.4 46.1 57.6 52.1 49.5 59.2 52.8 53.1
SHC
15.3 24.0 35.2 15.7 27.5 39.0 17.5 27.5 38.4 20.9 34.6 44.4
kW
7.80 7.61 7.38 7.83 7.67 7.49 7.89 7.72 7.58 7.92 7.78 7.70
BF
Bypass Factor
Edb
Entering Dry Bulb
Ewb
Entering Wet Bulb
kW
Compressor Motor Power Input
SHC
Sensible Heat Capacity (1000 Btuh) Gross
TC
Total Capacity (1000 Btuh) Gross
t
ldb
=t
edb
sensible heat capacity (Btuh)
1.1 x cfm
t
lwb
= wet-bulb temperature corresponding to enthalpy of air
leaving indoor coil (h
lwb
)
h
lwb
=h
ewb
total capacity (Btuh)
4.5 x cfm