User Manual
C.  INSULATION
1.  Insulate supply and return lines separately.
2.  Material  should  be  of  good  quality  and  be 
covered  with  a  good  vapor  barrier.  Armaflex  or 
equivalent is recommended.
Wall thickness:
1/2" wall thickness - south of 40 ° N. latitude 
3/8" wall thickness - north of 40° N. latitude
D.  HEIGHT OF COIL 
ABOVE ABSORPTION UNIT
Maximum  vertical  distance  from  chiller  outlet  to 
top  of  coil  is  22  feet  for  both  sizes.  For  greater 
heights,  a  greater  pumping  head  is  required.  In
creasing the pipe size will not help.
E.  WATER COIL CONNECTIONS
1.  If  coil  is  located  in  warm  air  stream,  do  not 
connect  polyethylene  pipe  directly  to  coil.  Connect 
a minimum of 24 inches copper or galvanized pipe 
to  both  the  coil  inlet  and  outlet.  Then connect  the 
plastic pipe to these nipples.
2.  On  installations  where  the  outside  piping 
freezes and  the coil  is in  a heated  air stream,  pre
cautions  must be  taken  to provide  for  water expan
sion.  The  connecting  polyethylene  plastic  pipe 
acts  as an  expansion vessel  if there  is enough  foot
age  of  this  pipe  in  the  heated  space  (space  not 
subject  to  freezing).  The  following  table  shows 
the  minimum  lengths  (total  inlet  and  outlet)  of 
plastic  piping  of  various  diameters  that  are  re
quired  for  both  sizes  of  coils  to  provide  adequate 
expansion volume.
Nominal Pipe Size 
Inches
Length of Plastic Pipe 
in Feet
Size 36 Size 54
%
24
56
1
15
35
V k
8.5 20
6.5
14.5
If  the  total  plastic  chilled  water  line  footage  in 
the  heated  space  is  not  as  long  as  the  minimum 
values  shown  in  the  table,  tee  a  vertical  pipe  of 
sufficient  volume  into  either  of  the  coil  connec
tions  to  provide  for  expansion,  or  the  line  should 
be drained.
Ill,  ELECTRIC CONNECTIONS
1.  Make  all  electric  connections  in  accordance 
with  the  National  Electrical  Code  and  any  local 
ordinances or codes that might apply.
2.  Provide  a  separate  power  supply  for  the  air 
conditioner.
3.  Provide  a  fused  disconnect  switch  within  easy 
reach of the absorption unit.
Size  36  -  use  30  amp.  Standard  fuse  or  15  amp. 
fusetron.
Size  54  -  use  35  amp.  standard  fuse  or  20  amp. 
fusetron.
4.  The  absorption  unit  is  shipped  fully  wired  from 
the  factory.  Connection  of  115V  power  and  low 
voltage  connection  to  the  thermostat  control  are 
required  in  the  field.  Before  proceeding,  inspect 
factory  wiring  for  loose  connections  which  may 
have resulted during shipment.
5.  Figure 6 is  the Wiring  Diagram.  Do not  fasten 
power  leads  to  hot  tubing  since  wire  insulation 
could be damaged and a short circuit could result.
6.  Disconnect  pump  electrical  leads  at  terminals 
6  and  7 in  control  box  before  energizing unit  when 
ready  to  check  field  wiring.  Do  not  operate  the 
pump dry.
IV.  GAS CONNECTIONS
Consult  local  gas  company  before  making  any  gas 
connections.  In  case  of  conflict  with  this  instruc
tion, local requirements should be followed.
Before  selecting  the  size  and  type  of  pipe  that  is 
to  be  used  for  installing  the  absorption  unit,  be 
sure  to  check  with  local  gas  company  for  the 
necessary  information.  The  size  of  the  gas  pipe 
to be  used will  depend upon the  length of  run and 
the  allowable  pressure  loss  established  by  the 
utility.
The  gas  connection  to  the  unit  is  made at  the  com
bination  regulator-shut-off.  On  the  size  36  use  a 
V2"  X  3"  nipple  and  then  a  elbow.  The  supply 
pipe  enters  the  knockout  on  the  other  end  of  the 
unit  and  will  then  be  lined  Up  for  final  connection 
if  the  nipple  and  elbow  are  used  as  described.  On 
the size 54 use aVi" x 2 "nipple and then a^/i" x 
reducing ell and 3/4 inch pipe.
EH 451
- 4 -










