Instruction manual
(where permitted) or onto a gravel apron in ground level installa-
tions. Install a field-supplied condensate trap at end of condensate
connection to ensure proper drainage. Make sure that the outlet of
the trap is at least 1 in. lower than the drain-pan condensate
connection to prevent the pan from overflowing. Prime the trap
with water. When using a gravel apron, make sure it slopes away
from the unit.
If the installation requires draining the condensate water away
from the unit, install a field-supplied 2-in. trap at the condensate
connection to ensure proper drainage. Condensate trap is available
as an accessory or is field-supplied. Make sure that the outlet of the
trap is at least 1 in. lower than the unit drain-pan condensate
connection to prevent the pan from overflowing. Connect a drain
trough using a minimum of field-supplied 3/4 -in. PVC or
field-supplied 3/4 -in. copper pipe at outlet end of the 2 -in. trap
(See Fig. 12). Do not undersize the tube. Pitch the drain trough
downward at a slope of at least 1 in. every 10 ft. of horizontal run.
Be sure to check the drain trough for leaks. Prime the trap at the
beginning of the cooling season start-up.
Fig. 5—Roof Curb Dimensions
UNIT SIZE ODS CATALOG NUMBER
A
IN. (MM)
B
IN. (MM)
C
IN. (MM)
D
IN. (MM)
601A018-042 602A024-036
CPRFCURB006A00 8 (203) 11(279) 161/2 (419) 28-3/4 (730)
CPRFCURB007A00 14 (356) 11(279) 161/2 (419) 28-3/4 (730)
601A048-060 602A042-060
CPRFCURB008A00 8 (203) 16 3/16 (411) 17 3/8 (441) 40-1/4 (1022)
CPRFCURB009A00 14 (356) 16 3/16 (411) 17 3/8 (441) 40-1/4 (1022)
NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied, as required, to unit being installed.
3. Dimensions in ( ) are in millimeters.
4. Roof curb is made of 16-gage steel.
5. Table lists only the dimensions, per part number, that have changed.
6. Attach ductwork to curb (flanges of duct rest on curb).
7. Insulated panels: 1-in. thick fiberglass 1 lb density.
8. Dimensions are in inches.
9. When unit mounting screw is used (see Note A), a retainer bracket must be used as well. This bracket must also be used when required by code for hurricane or seismic
conditions. This bracket is available through Micrometl.
C00076
Gasket around
outer edge
Insulated
deck pan
Gasket around
duct
S/A
R/A
HVAC unit
base
*Gasketing
outer flange
Flashing field
supplied
Roofing material
field supplied
Cant strip
field supplied
*Provided with roofcurb
Roof
Duct work
field supplied
Insulation (field
supplied)
Roofcurb*
Wood nailer*
Gasketing
inner flange*
Screw
(NOTE A)
Roof Curb for Small Cabinet
Note A: When unit mounting screw is used,
retainer bracket must also be used.
HVAC unit
base
*Gasketing
outer flange
Flashing field
supplied
Roofing material
field supplied
Cant strip
field supplied
*Provided with roofcurb
Roof
Duct work
field supplied
Insulation (field
supplied)
Roofcurb*
Wood nailer*
Gasketing
inner flange*
Screw
(NOTE A)
Roof Curb for Large Cabinet
Note A: When unit mounting screw is used,
retainer bracket must also be used.
A
B Typ.
Supply opening
(B x C)
Long
Support
D
44
5
/16"
(1125.5mm)
Return opening
(B X C)
Insulated
deck pan
Short
Support
C Typ.
—6—