Instruction manual
To change the speed of the indoor fan motor (IFM), remove fan
motor speed lead from the Time Delay Relay (TDR) and replace
with the lead for the desired blower motor speed. The motor speed
lead is attached to terminal TDR-3. For low and medium speeds,
black must be connected to the jumper wire. Insulate removed lead
end to avoid contact with chassis parts. To select high speed on
460-v GE motors, separate the black female quick connect (QC)
from the jumper lead male quick connect (QC) and connect the
black lead to the BR. Insulate the jumper to avoid contact with any
chassis parts.
MAINTENANCE
To ensure continuing high performance, and to minimize the
possibility of premature equipment failure, periodic maintenance
must be performed on this equipment. This heat pump unit should
be inspected at least once each year by a qualified service person.
To troubleshoot unit, refer to Table 11.
NOTE TO EQUIPMENT OWNER: Consult your local dealer
about the availability of a maintenance contract.
WARNING: The ability to properly perform mainte-
nance on this equipment requires certain expertise, me-
chanical skills, tools and equipment. If you do not possess
these, do not attempt to perform any maintenance on this
equipment, other than those procedures recommended in
the User’s Manual. FAILURE TO HEED THIS WARN-
ING COULD RESULT IN SERIOUS INJURY OR
DEATH AND POSSIBLE DAMAGE TO THIS EQUIP-
MENT.
WARNING: Failure to follow these warnings could
result in serious injury or death:
1. Turn off electrical power to the unit and install lockout
tag before performing any maintenance or service on
this unit.
2. Use extreme caution when removing panels and parts.
As with any mechanical equipment, personal injury
can result from sharp edges.
3. Never place anything combustible either on, or in
contact with, the unit.
CAUTION: Errors made when reconnecting wires may
cause improper and dangerous operation. Label all wires
prior to disconnecting when servicing.
The minimum maintenance requirements for this equipment are as
follows:
1. Inspect air filter(s) each month. Clean or replace when
necessary.
2. Inspect indoor coil, drain pan, and condensate drain each
cooling season for cleanliness. Clean when necessary.
3. Inspect blower motor and wheel for cleanliness each
cooling season. Clean when necessary.
4. Check electrical connections for tightness and controls for
proper operation each cooling season. Service when neces-
sary.
5. Ensure wires are not contacting refrigerant tubing or sharp
sheet metal edges.
Fig. 24—602A Balance Point Worksheet
C00093
Balance Point Worksheet
0
10
20
30
40
50
60
70
-100 1017203040475060
Outdoor Air Temp (Deg F)
024
030
036
042
048
060
Based on Indoor Entering Air of 70 F and Rated CFM
Building Heat Loss, 1000BTUH
Unit Integrated Heating Capacity (x1000BTUH)
—19—