Instruction manual

49
Table 13 -- Orifice Size and Manifold Pressure (In. wc) for Gas Input Rate (Con’t.)
(Tabulated Data Based on 21,000 Btuh High--Heat/14,500 Btuh for Low-- Heat Per Burner, Derated 4 Percent for Each 1000 Ft.
(305 M) Above Sea level)
ALTITUDE RANGE
FT. (M)
AVG. GAS
HEAT VALUE
AT ALTITUDE
(BTUH/CU
FT.)
SPECIFIC GRAVITY OF NATURAL GAS
0.58 0.60 0.62 0.64
Orifice
No.
Manifold
Pressure
High/Low
Orifice
No.
Manifold
Pressure
High/Low
Orifice
No.
Manifold
Pressure
High/Low
Orifice
No.
Manifold
Pressure
High/Low
USA
Only
5001 to
6000
(1524 to
1829)
725 44 3.5/1.7 43 3.2/1.5 43 3.3/1.6 43 3.4/1.6
750 44 3.3/1.6 44 3.4/1.6 44 3.5/1.7 43 3.2/1.5
775 45 3.7/1.8 44 3.2/1.5 44 3.3/1.6 44 3.4/1.6
800 46 3.7/1.8 46 3.8/1.8 45 3.8/1.8 44 3.2/1.5
825 46 3.5/1.7 46 3.6/1.7 46 3.7/1.8 46 3.8/1.8
850 47 3.7/1.8 47 3.8/1.8 46 3.5/1.7 46 3.6/1.7
875 47 3.5/1.7 47 3.6/1.7 47 3.7/1.8 46 3.4/1.6
900 48 3.8/1.8 47 3.4/1.6 47 3.5/1.7 47 3.7/1.7
ALTITUDE RANGE
FT. (M)
AVG. GAS
HEAT VALUE
AT ALTITUDE
(BTUH/CU FT.)
SPECIFIC GRAVITY OF NATURAL GAS
0.58 0.60 0.62 0.64
Orifice
No.
Manifold
Pressure
High/Low
Orifice
No.
Manifold
Pressure
High/Low
Orifice
No.
Manifold
Pressure
High/Low
Orifice
No.
Manifold
Pressure
High/Low
USA
Only
6001 to
7000
(1829 to
2134)
675 44 3.5/1.7 43 3.2/1.5 43 3.3/1.6 43 3.4/1.6
700 44 3.3/1.6 44 3.4/1.6 44 3.5/1.7 43 3.2/1.5
725 45 3.7/1.8 45 3.8/1.8 44 3.3/1.6 44 3.4/1.6
750 46 3.6/1.7 46 3.8/1.8 45 3.7/1.8 45 3.8/1.8
775 46 3.4/1.6 46 3.5/1.7 46 3.6/1.7 46 3.8/1.8
800 47 3.6/1.7 47 3.8/1.8 46 3.4/1.6 46 3.5/1.7
825 47 3.4/1.6 47 3.5/1.7 47 3.6/1.7 47 3.8/1.8
850 48 3.7/1.7 48 3.8/1.8 47 3.4/1.6 47 3.5/1.7
ALTITUDE RANGE
FT. (M)
AVG. GAS
HEAT VALUE
AT ALTITUDE
(BTUH/CU FT.)
SPECIFIC GRAVITY OF NATURAL GAS
0.58 0.60 0.62 0.64
Orifice
No.
Manifold
Pressure
High/Low
Orifice
No.
Manifold
Pressure
High/Low
Orifice
No.
Manifold
Pressure
High/Low
Orifice
No.
Manifold
Pressure
High/Low
USA
Only
7001 to
8000
(2134 to
2438)
650 44 3.3/1.6 44 3.4/1.6 44 3.5/1.7 43 3.2/1.5
675 45 3.7/1.8 45 3.8/1.8 44 3.3/1.6 44 3.4/1.6
700 46 3.6/1.7 46 3.7/1.8 46 3.8/1.8 45 3.8/1.8
725 47 3.8/1.8 46 3.5/1.7 46 3.6/1.7 46 3.7/1.8
750 47 3.5/1.7 47 3.7/1.8 47 3.8/1.8 46 3.5/1.6
775 48 3.8/1.8 47 3.4/1.6 47 3.6/1.7 47 3.7/1.7
800 48 3.6/1.7 48 3.7/1.8 48 3.8/1.8 47 3.4/1.6
825 48 3.3/1.6 48 3.5/1.6 48 3.6/1.7 48 3.7/1.8
ALTITUDE RANGE
FT. (M)
AVG. GAS
HEAT VALUE
AT ALTITUDE
(BTUH/CU FT.)
SPECIFIC GRAVITY OF NATURAL GAS
0.58 0.60 0.62 0.64
Orifice
No.
Manifold
Pressure
High/Low
Orifice
No.
Manifold
Pressure
High/Low
Orifice
No.
Manifold
Pressure
High/Low
Orifice
No.
Manifold
Pressure
High/Low
USA
Only
8001 to
9000
(2438 to
2743)
625 45 3.7/1.8 45 3.8/1.8 44 3.3/1.6 44 3.4/1.6
650 46 3.6/1.7 46 3.7/1.8 46 3.8/1.8 45 3.8/1.8
675 47 3.8/1.8 46 3.4/1.6 46 3.5/1.7 46 3.7/1.7
700 47 3.5/1.7 47 3.6/1.7 47 3.7/1.8 46 3.4/1.6
725 48 3.7/1.8 48 3.8/1.8 47 3.5/1.7 47 3.6/1.7
750 48 3.5/1.7 48 3.6/1.7 48 3.7/1.8 48 3.8/1.8
775 49 3.8/1.8 48 3.4/1.6 48 3.5/1.7 48 3.6/1.7
USA
Only
9001 to
10,000
(2743 to
3048)
600 46 3.6/1.7 46 3.7/1.8 46 3.8/1.8 45 3.7/1.8
625 47 3.7/1.8 47 3.8/1.8 46 3.5/1.7 46 3.6/1.7
650 47 3.4/1.6 47 3.6/1.7 47 3.7/1.8 47 3.8/1.8
675 48 3.6/1.7 48 3.8/1.8 47 3.4/1.6 47 3.5/1.7
700 48 3.4/1.6 48 3.5/1.7 48 3.6/1.7 48 3.7/1.8
725 49 3.7/1.8 49 3.8/1.8 48 3.4/1.6 48 3.5/1.7
* Orifice numbers 43 are factory installed
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing, safety glasses and
gloves when handling parts, and servicing furnaces.
CAUTION
!
The minimum maintenance on this furnace is as follows:
1. Check and clean air filter each month or more frequently if
required. Replace if torn.
2. Check blower motor and wheel for cleanliness each heat-
ing and cooling season. Clean as necessary.
3. Check electrical connections for tightness and controls for
proper operation each heating season. Service as neces-
sary .
4. Inspect burner compartment before each heating season
for rust, corrosion, soot or excessive dust. If necessary,
have furnace and burner serviced by a qualified service
agency.
5. Inspect the vent pipe/vent system before each heating sea-
son for rust, corrosion, water leakage, sagging pipes or
broken fittings. Have vent pipes/vent system serviced by a
qualified service agency.
6. Inspect any accessories attached to the furnace such as a
humidifier or electronic air cleaner. Perform any service or
maintenance to the accessories as recommended in the ac-
cessory instructions.
315A