Specifications

© 2007-2008 Broseley Fires Ltd
If there is no existing chimney then either a prefabricated block chimney in accordance
with Building Regulations Approved Document J or a twin walled insulated stainless steel
flue to BS 4543 can be used. These chimneys must be fitted in accordance with the
manufacturer’s instructions and Building Regulations.
The liner diameter must not be less than 6”. If the draw on the chimney is excessive, a
flue draught stabiliser will help to slow this down. An excessive draw may cause over
firing and thus cause the internal components of the stove to wear out quicker.
Any bend in the chimney or connecting fluepipe should not exceed 45°. 90° bends
should not be used. Adequate provision e.g. easily accessible soot door or doors must
be provided for sweeping the chimney and connecting fluepipe.
SUMMARY OF FLUE PROBLEMS