INSTALLATION OF STOVE
READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION
These instructions cover the basic principles to ensure the satisfactory installation of the
stove, although detail may need slight modification to suit particular local site conditions.
In all cases the installation must comply with current Building Regulations, Local
Authority Byelaws and other specifications or regulations as they affect the installation
of the stove.
It should be noted that the Building Regulations requirements may be met by adopting
the relevant recommendations given in British Standards BS 8303, BS 6461 and BS 7566
as an alternative means to achieve an equivalent level of performance to that obtained
following the guidance given in Approved Document J.
We recommend that you seek the services of an installer who is conversant with stove
installations and Building Regulations. It is most likely that the shop where you
purchased the stove will be able to help in this respect. It is our general policy to supply
specialist Fireplace shops. These shops can offer an after sales service and will be able
to offer advice when necessary.
Please note that it is a requirement under the Broseley Fires Ltd’s warranty
system that the installation of the stove is carried out under by a Competent
Person registered with a Government approved Competent Persons Scheme.
HETAS Ltd operate such a Scheme and a listing of their Registered Competent
Persons can be found on their website at www.hetas.co.uk
.
Stove Performance
In the UK the stove has been approved by HETAS Ltd as an intermittent operating
appliance for burning manufactured or naturally occurring smokeless fuels and wood logs
only. It should be noted that it is an offence to burn wood logs in this stove if it is
installed within a Smoke Control Area in the UK.
The nominal heat outputs for the stove are as follows:
Serrano 3 Serrano 5 Serrano 7
Heat Output 3 kW 5 kW 7 kW Smokeless fuels
3 kW 5 kW 7 kW Wood logs
Additional Air A permanent air entry opening or openings with a total free area
of at least 550mm
2
per kW of appliance rated output above 5Kw.
If a flue draught stabiliser is used, extra ventilation will be
required.