Specifications

eVo5MS0711 08/07/2011
Hearth
Yourstovemustbeinstalledonasolid,levelnoncombustiblehearthandwithagapofatleast
600mmfromanycombustiblematerialsuchasbeamsorskirting.Thehearthdoesnotneedtobe
constructionalbutmustbeatleast12mmthick.Thehearthprotrusioninfrontof
thestoveto
carpetsorwoodenfloorsmustbeatleast300mm.Asitispossibleforfueltofalloutonopeningthe
door,afendermustbefittedifthehearthisflushwiththecarpet.Thesearejustafewhearth
specifications.PleaserefertoBuildingRegulations
ApprovedDocumentJ(Hearths)formorespecific
details.
Theapplianceshouldbesitedinaproperlyconstructedbrickfireplaceorrecessallowingagapof
100mmallround,attherearandbothsides.Thefireplacewallsmustbemadeofsolidnon
combustiblematerialandatleast75mmthick.It
ispossibletoreducetheallroundclearanceto
75mmbutthiswillreducetheabilityoftheappliancetoheattheroomandcouldleadtooverfiring
ofthestoveandstructuraldamagetothesurround.Ifthisreducedairgapisunavoidableitwillbe
necessaryto
increasethethicknessofthesurroundingwallto200mm.Iftheairgaparoundthe
applianceisreducedto75mm,thenincreasethegapaboveto375mmtoallowtheairtomoveinto
theroom.Thehearthshouldbelevelandtheappliancefittedatrightanglestoit.Fireplace
walls
needtobeatleast1.2mabovethehearthandatleast300mmabovetheappliance.Thehearthhas
tobeabletosupporttheweightoftheapplianceandanyfluebearingdownuponit.Theclearance
distancestocombustiblematerialbeneath,surroundingoruponthehearthand
wallsadjacentto
thehearthshouldcomplywiththeguidanceontheseparationofcombustiblematerialgivenin
BuildingRegulationsApprovedDocumentJandalsointhesestoveinstructions.
 Minimumhearththicknes s 12mm
ConstructionalhearthNOTrequired
StoveClearances A B C Above
NonCombustible 100mm 100mm 300mm 200mm
Combustible 400mm 180mm 300mm 600mm