Specifications

8200 Compressor Installation
Installation, Operation, and Service Instructions Preparing the Compressor Input-Power
Brooks Automation 8040353
Revision 108
4-7
Figure 4-3: 8200 Compressor Cooling Water Flow and Pressure Requirements
Figure 4-4: 8200 Compressor Water Cooling Requirements
Cooling Water: Heat Load and Temperature Rise
Heat load to facility water is approximately 5000
Btu/hr, or 1500 Watts. With a 1.0
GPM water flow this translates to an approximate water temperature rise of 10ºF
(5.6ºC)