User's Manual

Table Of Contents
Product Manual - RFID Reader UF70 Certum 133
Chapter 7
Operation
Parameter 26
(0x1A)
Watch port for sensor 1
This parameter defines the response of the device when triggering the respective
input.
Bit 0: 0 – message input open disabled
1 – message input open activated
Bit 1: 0 – message input closed disabled
1 – message input closed activated
Bit 4/5: 0 – no scanning
1 – EPC bulk reading
Bit 6: 0 – The device does not expect any confirmation from the host
1 – The device expects a confirmation from the host
Bit 7: 0 – The input signal is not inverted (normal)
1 – The input signal is inverted
Default: 0b00110011 (0x33) Report "input open" and "closed" and sensor-
triggered EPC bulk reading.
Parameter 27
(0x1B)
Watch port for sensor 2
See parameter 26.
Parameter 28
(0x1C)
Watch port for sensor 3
See parameter 26.
Parameter 29
(0x1D)
Watch port for sensor 4
See parameter 26.
Parameter 33
(0x21)
High-byte Auto Read Bulk Time
An EPC bulk reading is completed in the sensor-triggered automatic reading. The
duration of the bulk reading is specified in milliseconds. The high byte of the 2
byte time value is defined here.
0 – 255 page
Default: 0x01 (0x0100: 256 ms)
IMPORTANT
The sensor must be connected to the input, in order to use this response!