User's Manual

Hermos Technical Reports
Release 2.1 Page 9 of 22
For the actor signal a LED without a shunt (connection to PIN 4 and 5) is required.
For the sensor a potential free contact (connection to PIN 2 and 3) or a 24V-
sensor (3 wire version with npn-output, connection to PIN 1 to 3) is required.
Important:
Up to serial-no: TLG-00-1999
For devices which have been delivered before the end of November 1998,
please pay attention to the following when selecting the 24V-sensor:
In open wiring condition, maximally +5V may be applied to the npn-output!