User's Manual
Hermos Technical Reports
Release 2.1 Page 13 of 22
In the standard version, the devices are equipped with a FFT-10A transceiver.
For the transceiver FTT-10 following data are applied:
Cable type Max. length of node to node
Belden 85102 500m
Belden 8471 400m
Level IV, 22AWG 400m
JY (St) Y 2x2x0,8 320m
The bus-topology consists of a main cable on which the individual nodes will be
connected with short stub lines. Terminators have to be connected on both ends of
the cable.
For the transceivers FTT-10 following bus lengthes are applied:
Cable type Max. length of main cable
Belden 85102 2700m
Belden 8471 2700m
Level IV, 22AWG 1400m
JY (St) Y 2x2x0,8 900m
The maximal length of a stub line is 3m.
T T
Reader or gateway
Terminator (bus termination)
Connection cable (bus + power supply)
T