User's Manual

Table Of Contents
Product Manual - RFID Reader LF60C SoliD 60
Chapter 7
Operation
7.3.4 Parameters
Parameter 0
(0x00)
Sensor delay
Operation delay for the presence sensor.
01 .. 99 (0.1 seconds)
Default: 10 (1s)
Parameter 1
(0x01)
Read mode
Readmode for automatic read triggered by external input.
00 - read only one page
01 - read until end character or empty character
2)
02 - read all pages
10 - read only one page with sensor check first
1)
11 - read until end/empty character with sensor check first
1) 2)
12 - read all pages with sensor check first
1)
99 - deactivate sensor
1)
If the sensor check is activated (first byte is 1) the circuit state of the floating
contact connected to the external input is checked before a read- or write-process
triggered by the terminal. If it is not connected, the error message "NOTAG" is
sent, otherwise the read respectively write process is started.
2)
'E' respectively 'F' in ID Bit 0...3 of the reading ID
Default: 00 (read only one page)
No.
(dec.)
No.
(hex)
Parameter name
0 0x00 Sensor delay
1 0x01 Read mode
2 0x02 Read page
3 0x03 r/w repeat time
4 0x04 r/w max repeat
5 0x05 RS232 repeat time
6 0x06 RS232 max repeat
7 0x07 Watch port
F Reader address