Product Manual - RFID Reader LF60C SoliD 109
Chapter 7
Operation
The table below defines the transitions of the BROOKS SECS-I status model of the
transponder reader.
#
Previous
state
Trigger
New
status
Action Comment
1 Any Power-up or reset INITIALIZ-
ING
Initialize
hardware and
software
Default entry on power-up
2 INITIALIZ-
ING
Initialization is
complete.
RUNNING None The CIDRW is now able to
communicate.
3 INITIALIZ-
ING
Default entry into
OPERATING
IDLE None Internal
4 IDLE A service request to
read or write or
perform diagnostics
is received.
BUSY None
5 BUSY All services request
that effect
IDLE None
6 IDLE A user selects the
MAIN-TENANCE
status and all
heads are IDLE.
MAINTE-
NANCE
None The upstream controller
may send a request or the
operator may set a switch to
select the MAINTENANCE
status. Maintenance and
setup activities may now be
performed.
7 MAINTE-
NANCE
A user selects the
OPERATING status
and all heads are
IDLE
IDLE None The upstream controller
may send a request or the
operator may set a switch to
select the OPERATING
status. Normal operating
activities may now be
performed.
8 INITIALIZ-
ING
Default entry into
ALARM STATUS
ALARMS or
NO
ALARMS
None
9 NO
ALARMS
An alarm condition
is detected.
ALARMS None
10 ALARMS All alarm conditions
have cleared.
NO
ALARMS
None
11 Any A reset service
request is received.
CIDRW None