User's Manual

Table Of Contents
Brooks Automation
40 260301 Revision A
7 Operation ATR60LF RFID Reader CAN Bus
7.3 Data Items Dictionary Product Manual
Command Parameter Value (see description of message S18F13).
This parameter provides the command to be carried out by the target.
LEDStatus
LED state, 1 byte
0 = Off
1 = On
2 = Flash
3 - 255 = Reserved
LEDNo
LED number, 1 byte
1 = Status LED
2 = Status LED
3 = External output
4 - 9 = Reserved
OpStatus
Operation status: Maintenance or Idle
MT = Maintenance
OP = Operational/Idle
PageNo
PageNo refers to the page of the transponder.
PageNo takes values from 1 - 17.
Timeout
Timeout period, 2 bytes
Units: seconds
Range: 1 - 98
"99" has a special meaning: it specifies "always". For example, an LED is
turned on with the TIMEOUT value of 99; it will stay on until the host turns
it off or the device is reset.
Where used S18F13
Transponder data
Read or write data within the available capacity of the Auto-ID.
Foup transponder - single page ID: 8 bytes (read only)
Foup transponder - multi-page ID: depending on model number up to 120
bytes
Where used S18F6, S18F7
CPVAL Format: 41
DATA Format: 41